WARNING FOR INSTALLER –IMPORTANT INSTALLATION
INSTRUCTIONS
1. This page of brief instruction is to be read in conjunction with other plumbing and electrical
installation requirements contained within this Installation Instruction and Owner’s Manual
2. All installation work must be carried out by an appropriately qualified Tradesperson/s.
3. The installation must be performed by Qualified and Authorised Persons and comply with the
requirements of AS/NZS 3500.4, AS/NZS 3000, and all local codes and regulatory authority
requirements.
4. It is recommended the solar storage tank be installed at ground or floor level. The water heater
must stand vertically upright.
5. This Water Heater Is Not Suitable For Pool Heating
6. Section 4 “Solar Collector Installation” must be read and understood prior to installation of collectors
to roof top.
7. Plastic pipemustnot be used on a solarwater heater installation due to the effectsof high water
temperatures and pressures. USE COPPER PIPE ONLY. All compression fittings must use brass
or copper olives.
8. Hot and cold copper pipes to andfrom the collectors must be completely insulated with a suitably
temperature rated insulation that is UV rated and weatherproof with minimum thickness of 19mm.
9. Valves andfittings supplied with this water heaterare suppliedwith insulationcovers which must be
fitted as part of the solar installation. Failure tofully insulate pipework andfittings increases the risk
of freeze damage and will void warranty
10. The maximum height of solar flow and return pipes must be where these pipes enter and exit the
solar collectors to avoid the possibility of air locks in the solar installation.
11. The maximum length of the copper tubefrom the solar pump to the collectors is reliant on mains
pressure (minimum 200kPa) and the number of bends and fittings in therun. As a guide, for DN15
copper pipe, the maximum length should not exceed 20 metres for 2 collectors and 15 metresfor 3
collectors. Note that maximum pipe lengths are based on minimal bends.
12. Valves andfittings supplied with this solar water heater form part of the installation andmust be
fitted in accordance with this manual.
13. The pump and controller assembly is fitted with an AVG FlowMeter FM15-1.4. This flow meter is
pre-set to 1.0L/Min for optimal performanceand must not be adjusted at time of installation.
14. Working on roofs should always be considered a hazardous activity; by lawyou must observe
certain minimum safety precautions. These safety precautions are outlined in the Work Cover Code
of practice “Safe work on roofs” Part 1 and 2 and in the Occupation Health and Safety Act 2011.
15. A 240V 50 Hz 10 Amp power outlet, connected to continuous tariff, is requiredfor the pump and
controller and must be installed by a licensed Electrician. This maybe aweatherproof outlet
depending on location. Steps should be taken to ensure power point is not turned off or plug pulled
out as the solar controller is the primaryfrost protection for the solar system.
16. The responsibility for all OH&S issues relating to the installation of the system resides with the
installing tradesperson/s.
17. The system should only be connected to water supply of acceptable quality otherwise the warranty
provided for the system may become void. Refer to Warranty conditions and section entitled “Water
Supply” contained within this manual.