ATL ATL-9000 Series User manual

Version No. 5027120315
User’s Manual of CFT-QGL-9000 Fire Alarm Control Panel (Linkage Type)
Fire Alarm Control Panel (Linkage Type)
ATL-9000 SERIES
ATL-9000-2
ATL-9000-4
ATL-9000-6
Angel Technologies Hongkong, Ltd.
Add: 3 F,South Gate,Chuangsheng Building, XiIi Twon, Yangguang Industrial
Zone, Nanshan District, Shenzhen, Guangdong,China
Post code: 518055
Tel: +86(755) 29810540
Fax: +86(755) 23707411
www.atlfire.hk

Version No. 5027120315
User’s Manual of CFT-QGL-9000 Fire Alarm Control Panel (Linkage Type)
Preface
The ATL-9000 fire alarm control panel (linkage type) complies with the requirements and spirit of the national
standards for Fire Alarm Control Units (GB 4717-2005) and Automatic Control Systems for Fire Protection (GB
16806-2006), and the related requirements of European standards EN 54-2 and EN 54-4.
The fire alarm control panel has a modular design and is characterized by great functions, large capacity
flexible configurations and an excellent price-performance ratio. The system has a large screen supporting Chinese
display and a standard special mini printer that can print all the alarms, faults and operations of the system into
Chinese. The system can realize comprehensive on-site programming and solve complicated linkage relation
settings. The system simulates the operating interfaces of Windows and is therefore easy to learn, use and realize
Chinese input. Each fire alarm control panel has a maximum capacity of 25,920 bus alarm linkage control points.
The ATL-9000 intelligent two-bus alarm and linkage control panel may be used with intelligent fire detectors,
input modules, output modules, manual control panels and multi-line linkage control units to form an integrated fire
control system combining buses and multiple lines to meet the needs of fire protection projects.
Thank you for using our quality products.
Please read this User’s Manual carefully before operating the
equipment. After the debugging acceptance, this User’s Manual
should be properly kept by a special person for future reference.

Chapter one: System overview
1.1 System introduction
The ATL -9000 fire alarm control panel (linkage type) (fire alarm control panel) is a new generation product
launched by ATL, In order to adapt to the needs of engineering design, the fire alarm control panel is designed with
a linkage control function that enables it to be flexibly used with other related products from ATL to form a fire
alarm and linkage integrated control system. It is particularly suitable for applications in large and medium-sized fire
alarm and linkage integrated control systems. The fire alarm and linkage control system is extensively applied in
high-grade office buildings, big residence communities, department stores, gymnasiums, exhibition halls, libraries,
factory buildings, supermarkets, hotels and other large and medium-sized fire protection projects.
1.2 System characteristics
It adopts new generation high-speed microprocessor technology that has a data processing
speed and a data storage capacity 100 times and 1000 times higher than that of conventional
technology respectively.
It has a 7.4″16-grey-scale LCD Chinese-supporting display and with a display resolution of
640×480.
Its operating interfaces simulate the menus and interfaces of Windows and therefore ensure
operation habits similar to that of computers and is easy to learn.
It uses a flexibly and conveniently controllable standard PS/2 computer keyboard and mouse
as on-site programming devices.
It provides a Chinese Pinyin input method and a Chinese section-position code input method
and can therefore realize Chinese input freely and easily.
It can copy or restore both setting files and historical files through a CF intelligent storage
card (optional), making system maintenance convenient.
It adopts a non-polarity two-bus intelligent alarm linkage mode and has a total of 324
intelligent detectors or modules for a single circuit. The addresses of the intelligent detectors
or modules may be hashed with No.1 to No.324.
It is equipped with multiple high-speed CAN-bus interfaces, ensuring quick and reliable data
transmission.
It has super high single-machine capacity (maximum single-machine capacity:
40×2×324=25,920 alarm points).
It supports the networking of 20 ATL-9000 fire alarm control panels. It has
a maximum capacity of 518,400 alarm points (20×25,920) after networking.
It can be connected with a multi-line linkage control unit and has a maximum capacity of
4,000 points for a standalone linkage control unit.
It can store the historical information of system operation, including 1,000 pieces of historical
fire alarm information, historical request information, historical feedback information,
historical fault information and historical operation information respectively.
Users can customize the equipment type, making system integration convenient.
It introduces the concept of a virtual interface board to realize the linkage operations of
general semantics, thus realizing the most complicated system linkage relations easily.
It has manual single-point start and stop functions for modules, making on-site debugging
and tests convenient.
It has a single-point test function for detectors or modules, making the operating conditions
and test data of detectors intuitive.
It has a standard special mini printer, enabling it to print various operating conditions in a
real-time way.
It can be accessed to a zone display panel, a building display panel or a floor display panel to
send the information displayed on it to locations like corridors.
It can be connected with the ATL-982 graphical display device (optional, ATL-982 for
short) in the fire control room to display the specific locations of fires and faults intuitively.
It executes administration by different levels for users of multiple levels and grants the users
1

at different levels the corresponding system operation authorities, making system
administration convenient.
It can realize local or remote software upgrades, thus enabling it to operate stably and
reliably.
Executive standards: Fire Alarm Control Units (GB4717-2005), Automatic Control System for Fire Protection
(GB16806-2006)
-2 -

485A
485B
485A
485B
Powersupply
电源
通讯
故障
消音
按键
通讯
故障
消音
按键
通讯
故障
消音
按键
火警
电源
火警
电源
火警
Powersupply
火灾 显示 盘
查询
传
传
Powersupply
火灾 显示 盘
查询
机检
恢复
消音
按键( 允/禁)
服务热线: 0 7 5 -8 2 2 1 85 6 1 85 6 63真: 0 7 5 -8 2 2 6 2
Powersupply
火灾 显示 盘
查询
机检
恢复
消音
按键 允/禁)(
服务热 :0 7 5 -8 6 2 1 8 线521 85 26 2真:0 7 5 - 8 6 2 6 3
电源
火警
通讯
故障
消音
按键
火灾 显示 盘
机检
恢复
消音
按键( 允/禁)
服务热线: 0 7 5 -8 2 2 1 856185 26 2
传真 :0 7 5 -8 6 2 6 3
查询
机检
恢复
消音
按键( 允/禁)
服务热线: 0 7 5 -8 2 2 1 85 6 1 8
传真: 0 7 5 -8 2 2 6 25 6 63
Fire display
panel
1 L+
1 L-
Fire display
panel
Two
non-polarity
buses, mixed
compilation
allowed,
address code:
1-324
Fire display
panel
Fire display
panel
1 L+
1 L-
PH O NE通话 指示
A LA R M火警
Powersupply
PRE SS HER E
按下报 警
1.3 System schematic diagram
CFT-QGL
-9000
巡检闪亮动作常亮
CFT-QGL
-9000
Intelligent
80 L+ smoke
detector
80 L-
Intelligent
heat detector
Intelligent
module
Intelligent
manual alarm
80 L+
Intelligent
horn/strobe
3
3
Multi-line
linkage
equipment 1
Multi-line
linkage
equipment 2
Fig.1-1 System Schematic Diagram
-3-
CAN2H
CAN2L
80 L-
Two-corepowe
r line
PC
CRT-9000
Fire control
graphic
display
device
3
Multi-line
linkage
equipment n
CFT-QTL
-9000
CFT-QTL
-9000
Overall
Wiring
Diagram of
the
Fire Alarm
Control
System

1.4 System equipment
As shown in Fig.1-1, in addition to a fire control unit, the system also includes other
corresponding equipment. To acquaint you with the system, we will introduce its equipment
briefly below. The fire control system includes the following main components:
Main control unit
The main control panel processes and analyzes the data information transmitted from other
components of the system and commands other components of the system to execute the
corresponding commands according to the results of data analyses. For example, it can make
the buzzer give a fire alarm.
Display component
The display component provides a main output interface for alarm information and the daily
maintenance and query interfaces as well.
Input equipment
The system is transplanted with a standard external peripheral interface for computers and
uses a PS/2 keyboard and mouse as input equipment, which makes system setting and
maintenance highly convenient for users.
Power supplies
They provide electricity for the internal equipment of the entire system. The system has
special fire equipment power supplies with an output voltage of DC 24V. The power supplies
can provide alarm or feedback signals like AC FAULT, DC FAULT, DC LACK, DC CHARGE
and have an excellent anti-interference characteristic.
Interface board
It is a driver board for the detector or module bus. Each interface board has two circuits. Each
of the two circuits can drive 324 intelligent detectors or modules.
Fire detector
The system can be accessed to multiple intelligent smoke, heat or composite detectors
produced by Fanhai Sanjiang. The main fire detector models include JTY-GD-930, JTW-ZD
-920 and so on.
Input module, output module, audible and visual alarm, manual alarm and
fire hydrant
The system may be accessed to multiple intelligent modules produced by kai wei xin .
The main product models include JK-952 (input module), JS-951 (input module), KZ-953
(output module) and KZJ-956 (I/O module). Meanwhile, the system may also be accessed to
an SG-991 intelligent audible and visual alarm, a J-SAP-M-960 intelligent manual alarm
button, a J-SAP-M-961 intelligent fire hydrant, etc.
Bus manual control panel
Each manual control panel has 30 manual control buttons each of which corresponds to an
I/O module on the bus. In the permissible manual control state, pressing such a manual
control button can realize manual start and stop operations of the corresponding I/O module.
Multi-line linkage control unit
Each group of DX900-05A multi-line linkage control units include 5 multi-line control points
that may control five pieces of key equipment needing direct control, such as fire pumps, etc.
A 2U panel may be installed with 15 multi-line linkage control points (three units).
Printer
The system has a standard special mini printer (printer for short) that may print information like
alarm information, feedback information, fault information and some other information for
future reference.
-4 -

Fire display panel
A fire display panel is also called a floor display panel. Its application is expanded in the
system, so it can be used as either a zone display panel or a building display panel or floor
display panel. The fire display panel model that may be accessed to the system is
CFT-FSD-982
1.5 Technical parameters of the products of the system
1.5.1 Power supplies:
Main power supply: AC 220V±20%/50Hz or DC24V
Emergency power supply: Maintenance-free DC24V battery (its capacity depends on the
system size).
1.5.2 Operating conditions:
Ambient temperature: -10℃~+55℃during system operation
Ambient humidity: ≤95% (40℃±2℃, without condensation)
1.5.3 Peripheral equipment:
For the specific technical parameters of equipment like detectors, modules and audible
and visual alarms, see the corresponding instruction manuals.
-5-

Chapter two: Installation and dimensions of system
engineering
2.1 Outline drawing and dimensional drawing of the product
Appearance and dimensions of CFT-QTL-9000
Main control unit
Manual control unit
Linkage unit
Blank cover
Printer
Fig.2-1 Qintai Dimensions
-6 -

Appearance and dimensions of CFT-QGL-9000
Host cover
Manual control unit
Linkage unit
Keyboard, mouse
Printer
Blank cover
Fig.2-2 Cabinet Dimensions
-7-

Lashing eye
Scale3:1
Lashing eye
Scale3:1
Inlet wire
Fig.2-3 CFT-QBL-9000 diagrammatic sketch
-8 -

CFT-QBL-9000E
Main control unit
Manual control unit
Linkage unit
Shenzhen Convoys Fire TechnologyCo.,Ltd.
Blank cover
Fig.2-4 CFT-QBL-9000 Dimensions
2.2 System installation
2.2.1 Unpacking inspection
It is necessary before installation to inspect the on-site equipment. After unpacking the box,
check the goods in it one by one according to the content of the packing list. The main content of
the check should cover the Installation and Operation Manual, the protector tubes, the spare
screws, the control panel key and so on. After checking the above, do necessary inspections for
the appearance of the fire alarm control panel. If any non-conformities are discovered in the check
or inspections, call our salespersons.
2.2.2 Engineering configuration inspection
Inspect whether the contents of the packing list of the control equipment complies with the
engineering configurations and matches with the design drawings or not.
2.2.3 Inspection of the internal configurations and connection condition of the
fire alarm control panel
Do simple routine inspections for the internal configurations of the fire alarm control panel,
such as the number of the interface boards, the number of the manual control panels, the power
-9-

supply connection condition, etc. Meanwhile, inspect whether or not the internal connecting lines
of the equipment suffer falling or abnormalities due to transportation.
2.2.4 Power on self test
If no abnormalities are discovered in the inspections above, do a simple power on self test for
the fire alarm control panel as instructed in 2.4.2 to check whether its power supplies and basic
functions (such as keys, indication function and so on) are normal or not.
2.2.5 Inspection and connection of external equipment
Inspect the conditions of the buses in connection with the fire alarm control panel and
measure the insulation resistances between the buses of different circuits and that between the
buses and ground as well as the loads of the circuits. The insulation resistances should be larger
than 20MΩ and the circuit resistances should be smaller than 40Ω.
Use debugging devices to inspect whether the conditions of the circuit equipment (including
quantity, codes and operating conditions) comply with the design requirements or not, so as to
eliminate the faults (if any) and prepare for system connection.
Access the external equipment or connecting lines of the system to the input terminals of the
system controller. See the descriptions on the labels for the definitions of the terminals. The
contact should be good and there should be neither short circuits nor open circuits during the test
done with a multimeter.
-10 -

Chapter three: System debugging and operation
3.1 System debugging
If no abnormalities are discovered in the careful inspections done following system
connection, the system may be powered on for debugging. The main content of debugging
includes the login and tests of detectors and modules, the settings of the bus manual control
panels, the multi-line linkage control units, the linkage relations, etc.
3.2 Directions for system operation
3.2.1 Panel functions
The layout of the CFT-QGL-9000 panel is shown in the figure below.
CFT -QGL-9000E FIRE ALARM CONTROL PANEL
PERMIT
POWER
FIRE
START
FEEDBACK
FAULT
PRHB.
SYSTEM FAULT
SURVEILLANCEALARM
OPERATIONDELAY
POWERFAULT
HO /RNS TROBEFAULT
C MN AOM U IC TION
SURVEILLANCEFAULT
SYST TESTEM
AUTO
MANUAL
K OREYBA D
ISO TIOLA N
GN AE ER LL KGINA E
R ETES
SO N ERUDLIN A EKG
SELE TC
SSE T SY T ME T
MN AAU L
C N IROF M
CNEA CL
P N M TEA EL U
O TSIDUEM TEU
Fig.3-1 Layout of the Panel
The panel design includes the basic functions regarding alarm query and control. Hereunder
are detailed introductions to the figure above.
Indication function zone:
FIRE
ALARM
POWER
STARTUP
FEEDBACK
TROUBLE
SYSTEM
FAULT
OPERATION
DELAY
POWER
TROUBLE
S&L
TROUBLE
SELF-TEST
Fig.3-2 Indication Function Zone
No.
Silk screen
printed
POWER
Color
of the
light
Green
Function description
It will be lit after the mainboard is normally powered
on by the power supply source of the fire alarm
control panel (or the emergency power supply
- 11 -
01

02
03
04
05
06
07
08
FIRE ALARM
STARTUP
FEEDBACK
TROUBLE
SYSTEM FAULT
SURVEILLANCE
ALARM
OPERATION
DELAY
Red
Red
Red
Yellow
Yellow
Red
Red
source).
User’s Tip: If it is lit, it does not suggest that all
other components of the system other than the
mainboard have been normally powered on, in
other words, it will be lit as log as the mainboard is
normally powered on.
It will be lit upon a fire alarm discovered in the
system.
It will be lit after the system sends a linkage request
of a module.
It will be lit after the system receives the linkage
feedback of a module.
It will be lit after an alarm fault is discovered in the
system (no matter which type the fault is).
It will be lit when the fire alarm control panel suffers
a fault or the system is not running normally.
It is currently meaningless as a reserved function.
It will be lit when a fire alarm triggers a linkage; and
it will go out when all the linkage delays have
ended and all the linkages have been established.
It will be lit when a power supply alarm of the fire
alarm control panel is discovered in the system (no
matter which type the power supply fault is). It is
specially set against the possibility that power
supply faults may make the entire system fail to
operate normally.
It will be lit when there is an audible and visual
alarm fault or a sounder (alarm bell) fault in the
system.
It will be lit when the fire alarm control panel has
normal communication.
Warm tip: Communication speed is fast, so this light
is actually in a flashing state.
It is currently meaningless as a reserved function.
It will be lit when the fire alarm control panel is
undergoing a self test or single-point test. It will go
out automatically after the self test.
09
POWER
TROUBLE
Yellow
10
S&L TROUBLE
Yellow
11
COMMUNICATION
SURVEILLANCE
TROUBLE
SELF-TEST
Green
12
13
Yellow
Yellow
Key function zone:
Fig.3-3 Key Function Zone
-12 -

1) KEYBOARD function key (with a light)
When the system is powered on, the initial state is that the panel keyboard is closed and the
KEYBOARD light is out. After the KEYBOARD key is pressed or the CTRL , ALT and DEL keys on
the PS/2 keyboard are pressed at the same time, a password input box and a figure selection box
(there will be no figure selection box if login is realized through the PS/2 keyboard) will pop up on
the screen. At this time, user may log in the system after inputting the correct password (for
details, see the instructions on user login). If the system receives the correct password, the panel
keyboard will be opened and the KEYBOARD light will be lit at the same time. When the panel
keyboard is opened, the system will close the keyboard and exit the login after the KEYBOARD
key is pressed or the CTRL , ALT and DEL keys on the PS/2 keyboard are pressed at the same
time.
User’s Tip: If no operations are done on the system for about 10min when the
panel keyboard is opened, the system will exit the login automatically and close the
panel keyboard. All the function keys (all those introduced below) except for the
LOCAL MUTE key can be operated when the panel keyboard is opened only.
2) INTEGRATION function key (with a light)
If the integration control is in the PRHB state, press the INTEGRATION key to switch it to the
PERMIT state. During the process, the INTEGRATION light will be lit. If the IINTEGRATION key
is pressed again, the integration control will be in the PRHB state again and the INTEGRATION
light will go out at the same time. If multiple fire alarm control panels are networked and the
INTEGRATION key on the No.1 fire alarm control panel in the network is pressed, the integration
control states of all the fire alarm control panels will be changed at the same time; if the
INTEGRATION key on any other fire alarm control panel is pressed, only the integration control
state of the fire alarm control panel will be changed. The integration control state will be saved
upon a power failure. In other words, if the system suffers a power failure and is then powered on
again, the integration control state before the power failure will be restored.
User’s Tip: Integration refers to the integration control except for the sounder.
Sounder refers to a kind of linkage control of the system over the alarm bell, the
audible and visual alarm and other alarm devices. These alarm devices are used
extensively in projects and have independent muting operations. In order to simplify
the settings for users, we list the integrations of this sort separately for independent
operations.
3) SOUNDER function key (with a light)
If the sounder control is in the PRHB state, press the SOUNDER key to switch it to the
PERMIT state. During the process, the PERMIT light near the SOUNDER key will be lit. If the
SOUNDER key is pressed again, the sounder control will be in the PRHB state again and the
PERMIT light will go out at the same time. If multiple fire alarm control panels are networked and
the SOUNDER key on the No.1 fire alarm control panel in the network is pressed, the sounder
control states of all the other fire alarm control panels will be changed at the same time to make
them the same as that of the No.1 fire alarm control panel; if the SOUNDER key on any other fire
alarm control panel is pressed, only the sounder control state of the fire alarm control panel will be
changed. The sounder control state will be saved upon a power failure. In other words, if the
system suffers a power failure and is then powered on again, the sounder control state before the
power failure will be restored.
4) MANUAL function key (with a light)
If the MANUAL control of the system is in the PRHB state, press the MANUAL key to switch all
the accessed manual control panels to the PERMIT state. During the process, the PERMIT light
below the MANUAL key will be lit. If the MANUAL key is pressed again, the MANUAL control will
be in the PRHB state again and the PERMIT light will go out at the same time. If multiple fire
alarm control panels are networked and the MANUAL key on the No.1 fire alarm control panel in
the network is pressed, the manual control states of all the other fire alarm control panels will be
changed at the same time to make them the same as that of the No.1 fire alarm control panel; if
- 13 -

the MANUAL key on any other fire alarm control panel is pressed, only the manual control state of
the fire alarm control panel will be changed. The manual control state will be saved upon a power
failure. In other words, if the system suffers a power failure and is then powered on again, the
manual control state before the power failure will be restored.
5) LOCAL MUTE function key
Pressing the LOCAL MUTE key can mute the alarm sounds given by the buzzer and fire display
panel in the fire alarm control panel and the graphical display device in the fire control room. Upon
a new alarm under the mute state, the buzzer and other audible alarm devices will be restarted.
The LOCAL MUTE key is the only key not under the password protection in the system and it can
be operated no matter whether the keyboard panel is opened or closed.
6) OUTSIDE MUTE function key (with a light)
Pressing the OUTSIDE MUTE key can mute the alarm sounds of external equipment (including
the alarm bell and the audible and visual alarm). If there is a fire alarm, this key can disable or
enable the alarm sounds of corresponding alarm devices. After this key is pressed, the alarm
sounds will be muted and the OUTSIDE MUTE light will be lit. Upon a new fire alarm discovered
in the system when the alarm bell or the audible and visual alarm is linked, the OUTSIDE MUTE
light will go out and the alarm sounds of the corresponding alarm devices will be enabled again.
This key can be operated after the user logs in the system only.
7) ISOLATION function key (with a light)
If the ISOLATION key is pressed, all the bus equipment (it may be any bus equipment in the
networked system) currently under the alarm state (the fire alarm state, the feedback state or the
fault state) will be isolated. If a piece of bus equipment is isolated, the system will not give any
audible/visible alarms for the alarm information of the bus equipment. The fault information of the
interface boards, the power supplies, the printer, the display panels and the communication of the
fire alarm control panel should not be isolated. If any bus equipment in the system is isolated, the
ISOLATION light will be lit.
User’s Tip: Only the superuser is allowed to use this function. Isolation involves
displayed information. The isolated bus equipment can run normally. Only a current
alarm key will be available on the panel in this case. Isolation operations like
ISOLATION QUERY and CANCEL ALL ISOLATIONS may be done through menu
operations.
8) SELF-TEST function key
After the SELF-TEST key is pressed, the system will enter the self-test procedure: All the lights
will be lit for a light inspection; the buzzer will try multiple sound modes (fire alarm, fault,
feedback); and the screen will light the dot matrixes in order. After the self-test, the system will
exit automatically. If the SELF-TEST key is pressed during the self-test, the system will exit the
self-test state.
△Caution: Under the self-test state, the system will not receive alarm signals.
!
9) RESET function key
After the RESET key is pressed, all the present alarms will be eliminated and the system will
be restarted. The entire process needs about 30s to 60s. If multiple fire alarm control panels are
networked and the RESET key on the No.1 fire alarm control panel in the network is pressed, all
the networked fire alarm control panels will execute the reset operation; and if the RESET key on
any other fire alarm control panel networked is pressed, only the fire alarm control panel will be
reset.
△Caution: If multiple fire alarm control panels are networked and the No.1 fire alarm
control panel is the concentrator (the system’s principal fire alarm control panel), then,
when the RESET key, the ISOLATION key, the LOCAL MUTE key, the OUTSIDE
MUTE key, the INTEGRATION key, the SOUNDER key or the MANUAL key on the
concentrator is pressed, all the other zone fire alarm control panels networked (the
!
-14 -

No.2 fire alarm control panel to the No.20 fire alarm control panel) will execute the
corresponding operation; and if the said key on an zone fire alarm control panel is
pressed, only the state of the zone fire alarm control panel will be changed. If the
RESET key on the concentrator is pressed by an operator when an zone fire alarm
control panel in the networked system is in the set state, the zone fire alarm control
panel will immediately respond to the restoration command and the file is set by it at
that time will lose the content updated this time, namely the data newly set after the
last time saving will not be saved automatically. Therefore, when the networked
system is debugged by several debugging personnel at the same time, it is
necessary to disconnect the networking cables of the set fire alarm control panel
temporarily before inputting mass data.
10) Selection and query of the content on the LCD
In this part, there are four keys, including ▲, SELECT, CONFIRM and ▼. The specific
meanings of the four keys depend on the content currently displayed on the screen. The four keys
mainly have two applications:
Query alarms:
▲: Upward rolling
SELECT: Select the activity area (fire alarm
request/feedback area, fault area).
CONFIRM: Confirm the activity area (fire alarm
request/feedback area, fault area).
▼: Downward rolling
Input the
area,
area,
password:
▲: Move the cursor
upward.
SELECT: Select a figure.
CONFIRM:Confirmthe
completion of password
inputting.
▼: Move the cursor
downward.
11) Reserved keys for reserved functions
Keys like F1, F2, F3, F4, ◄and ►have no practical meanings at present and are
reserved for future system expansion.
12) Functional key lock
△Caution: The key lock functions are designed for multi-line
linkage control units only.
!
PERMIT
PRHB.
AUTO
MANUAL
“PERMIT/PRHB.” key lock function: When the “PERMIT/PRHB.” key
lock is put on the PERMIT position, the system’s multi-line linkage function
will be enabled; and when it is put on the PRHB. position, the system’s
multi-line linkage function will be disabled.
“AUTO/MANUAL” key lock function: When the “AUTO/MANUAL” key
lock is put on the AUTO position, the multi-line linkage control units will run
automatically and priority will be given to the manual mode. In case a
piece of fire alarm information discovered in the system, the
corresponding multi-line linkage control unit will run automatically. When it
is put on the MANUAL position, the multi-line linkage control units can only
be started manually. At this time, the system can give alarms only and the
multi-line linkage control units will fail to run automatically.
- 15 -

Chapter six: Functions of manual control panel
The system may be externally connected with multiple manual control panels to serve as direct
manual control equipment for users. Each bus manual control panel (2U panel) contains 30
manual control buttons for the control over 30 bus modules. Each of the manual control buttons
has two lights (a REQ. light and a FEEDBACK light) to indicate the state of the module
controlled by it.
Hereunder is an outside view of a manual control panel.
FIRE MA N PANE L
FIRE MA N PANE L
FIRE MA N PANE L
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
R EQ.
V RF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
Fig.6-1 Manual Control Panel
Each manual control button needs to occupy a module address, so each manual control panel
needs to occupy 30 continuous bus module addresses. The quantity of the manual control
panels that may be accessed to a fire alarm control panel depends on the quantity of the
interface boards. There are 11 initial positions of the 30 module addresses for selection: 1, 31,
61, 91, 121, 151, 181, 211, 241, 271 and 301. The specific address settings may be determined
by four jumpers JP1, JP2, JP3 and JP4 on the circuit board. When the jumpers jump to the
upper end, it is “1” (HIGH); when they jump to the lower end, it is “0” (LOW). The corresponding
addresses are given as follows.
FIREMAN PANEL
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
REQ.
VRF.
Fig.6-2 Detailed Outside View (10 Points)
:
User’s Tip:
Each 30 manual control panels are designed to
be a group. During configuration, the manual
control panels should be increased by the
integral multiples of 30.
Fig.6-3 Address Coding
The functions of the manual control panels of the system are not introduced here in details. For
more information about the functions, please refer to the instruction manual of the multi-line
linkage control units (ZX900-10A) of our company.
- 16 -

Chapter seven: Functions of multi-line linkage control unit
The system may be accessed to multiple multi-line linkage control units produced by our
company. Each group of multi-line linkage control unit groups includes five multi-line control
points. Each multi-line control point includes the following parts.
REQ. button
UNSET button
REQ. light
VRF. light
NOR. light
TRB. light
In the figure below, the three groups of multi-line linkage control units installed on the housing
have 15 multi-line control points in all.
MANUAL CONTROL UNIT
MANUAL CONTROL UNIT
MANUAL CONTROL UNIT
RE Q.
REQ.
REQ.
RE Q.
REQ.
REQ.
R EQ.
RE Q.
REQ.
REQ.
RE Q.
REQ.
REQ.
RE Q.
REQ.
RQE.
VR F.
VRF.
R.EQ
VRF.
R.EQ
V RF.
R.EQ
VRF.
RQE.
VRF.
R.EQ
V RF.
R.EQ
VR F.
RQE.
VRF.
R.EQ
VRF.
R.EQ
VR F.
R.EQ
VRF.
R.EQ
VRF.
R.EQ
V RF.
R.EQ
VRF.
RQE.
NOR.
NOR .
NOR.
NOR.
NOR .
NOR.
N OR.
NOR.
NOR .
NOR.
NOR.
NOR .
NOR.
NOR.
NOR .
U STNE
TR B.
TRB .
U SENT
TRB.
US TNE
TR B.
U STNE
TRB .
U STNE
TRB.
USN ET
T RB.
US TNE
TR B.
U STNE
TRB .
U SENT
TRB.
US TNE
TR B.
U STNE
TRB .
U SENT
TRB.
US TNE
TR B.
U STNE
TRB .
U STNE
Fig.7-1 Multi-line Linkage Control Unit
The quantity of the multi-line control points that may be accessed depends on the quantity of the
interface boards. Each group of multi-line linkage control units occupies five bus addresses.
Each multi-line terminal board may be connected with five multi-line output circuits.
MANUAL CONTROL UNIT
RE Q.
RE Q.
RE Q.
REQ.
RE Q.
RQE.
VRF.
NOR.
V RF.
NOR.
RQE.
V RF.
NOR.
RQE.
VRF.
NOR.
RQE.
VRF.
NOR.
RQE.
US TNE
TRB.
TRB.
US TNE
TRB.
US TNE
TRB.
US TNE
TRB.
US TNE
Fig.7-2 Outside View of Each Group of Multi-line Linkage Control Units (5 Points)
Fig.7-3 Wiring Method (One
Circuit)
User’s Tip:
Each 5 multi-line linkage control
unit is designed to be a group.
Duringconfiguration,the
Fig.7-4 Address Coding
multi-line linkage control units
should be increased by the
integral multiples of 5 according
to the actual need.
The functions of the multi-line linkage control units of the system are not introduced here in
details. For more information about the functions, please refer to the instruction manual of the
multi-line linkage control units (DX900-05A) of our company.
-17 -

Chapter eight: Cause analysis and troubleshooting of faults
² Fault phenomenon: After the system reports a fire alarm, the
corresponding alarm bell and audible and visual alarm fail to act.
Possible causes and troubleshooting methods:
a. Check whether the SOUNDER light on the panel is lit or not;
b. Check whether there is any fault information about the alarm bell or audible and visual
alarm or not;
c. Check whether the alarm bell or audible and visual alarm has a 24V power supply or not;
d. Check whether the type of the control module of the alarm bell is set to be sounder or
audible and visual alarm or not; or
e. Check whether there is a sounder or audible and visual alarm output in the linkage setup
or not.
² Fault phenomenon: After the system reports a fire alarm, the
equipment executes no requests.
Possible causes and troubleshooting methods:
a. Check whether the INTEGRATION light on the panel is lit or not; or
b. Check whether there are linkage setting data in the linkage setup or not, or whether the
Register option in the linkage data is selected or not.
² Fault phenomenon: After the system reports a fire alarm, the
multi-line linkage control units on the fire alarm control panel fail
to execute a linkage request or fail to act.
Conditions for the automatic start of the multi-line linkage control units:
a. The PRHB/PERMIT lock-control switch is in the PERMIT state;
b. The AUTO/MANUAL lock-control switch is in the AUTO state;
c. The INTEGRATION light is lit; and
d. Check whether there are linkage setting data in the linkage setup or not, or whether the
Register option in the linkage data is selected or not.
After the system reports a fire alarm, linkage may be realized after three of the conditions above
are met at the same time only.
Generally speaking, the multi-line linkage control units on the fire alarm control panel are
important fire protection equipment for control. In order to avoid wrong operations, they are
generally designed with multiple protection measures. In addition to the control of the
INTEGRATION switch, automatic linkage is also under the control of the PRHB/PERMIT
lock-control switch and AUTO/MANUAL lock-control switch on the fire alarm control panel. In the
PERMIT state, no operations can start the multi-line modules. The multi-line modules can
respond to the action requests of the fire alarm control panel in the PERMIT and AUTO states only.
Both in the AUTO and MANUAL states, the multi-line linkage control units can be started and
stopped manually.
² Fault phenomenon: After the system reports a fire alarm, the
on-site equipment executes a request, but it fail to act.
The feedback signals of the on-site equipment need to be returned by control and monitoring
modules. The possible causes of the fault include:
a. The on-site equipment is not in the auto state and therefore fails to start under module
control;
b. The on-site equipment has started, but its feedback signal wire has fallen off; or
c. The on-site equipment is not connected with a proper power supply.
² Fault phenomenon: The fire alarm control panel reports an AC
fault and a DC fault.
处理方法及可能的原因有:
Possible causes and troubleshooting methods:
- 18 -
This manual suits for next models
3
Table of contents
Other ATL Control Panel manuals
Popular Control Panel manuals by other brands

THOMPSON PUMP
THOMPSON PUMP J1939 product manual

Crowcon
Crowcon Gasmaster 1 Installation, commissioning and maintenance instructions

Beninca
Beninca HEADY manual

Busch-Jaeger
Busch-Jaeger Busch-Welcome 83200-FM Series manual

Siemens
Siemens CP-2ER Operation, installation, and maintenance manual

Honeywell
Honeywell Fire-Lite Alarms ES-1000X manual