AUMA SGM 04.1 User manual

Control
Parallel
Profibus DP
→Modbus RTU
Part-turn actuators
SGM 04.1 –SGM 12.1
SGMR 04.1 –SGMR 12.1
with integral actuator controls
Assembly, commissioningOperation instructions

Read operation instructions first.
●Observe safety instructions.
●These operation instructions are part of the product.
●Retain operation instructions during product life.
●Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff.It is intended
to support device installation and commissioning.
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
41. Safety instructions................................................................................................................. 41.1. Basic information on safety 41.2. Range of application 51.3. Warnings and notes 51.4. References and symbols
72. Identification........................................................................................................................... 72.1. Name plate 82.2. Short description
93. Transport, storage and packaging........................................................................................ 93.1. Transport 93.2. Storage 93.3. Packaging
104. Assembly................................................................................................................................ 104.1. Mounting position 104.2. Actuator: mount to valve 104.2.1. Actuator for assembly: prepare 104.2.2. Output drive for coupling 114.2.2.1. Mounting with coupling
135. Electrical connection............................................................................................................. 135.1. Basic information 155.2. Connection via bayonet connector 155.2.1. Mains and fieldbus cables: connect 175.3. Earth connection, external 185.4. Accessories for electrical connection 185.4.1. Local controls mounted on wall bracket
196. Indications.............................................................................................................................. 196.1. Mechanical position indication via indicator mark 196.2. Indication lights
217. Signals (output signals)......................................................................................................... 217.1. Signals via fieldbus
2
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Table of contents Modbus RTU

228. Operation................................................................................................................................ 228.1. Manual operation 228.2. Motor operation 228.2.1. Local actuator operation 238.2.2. Actuator operation from remote
259. Commissioning (basic settings of controls)....................................................................... 259.1. Cover to controls: open 259.2. Setting via hardware (switches) or via software 269.3. Type of seating: set 279.4. Torque switching: set 289.5. Fieldbus address (slave address), baud rate, parity and monitoring time: set 309.6. Termination resistor: connect 309.7. Operating time: set 329.8. Cover to controls: close
3310. Commissioning (basic settings at actuator)........................................................................ 3310.1. End stops in part-turn actuator 3410.1.1. End stop CLOSED: set 3410.1.2. End stop OPEN: set 3510.2. End position detection: verify setting 3510.3. End position detection: set again via local controls 3610.3.1. End position CLOSED: set again 3710.3.2. End position OPEN: set again 3710.4. Switch compartment: open 3810.5. Mechanical position indicator: set 3810.6. Switch compartment: close
3911. AUMA CDT software (accessories).......................................................................................
4012. Corrective action.................................................................................................................... 4012.1. Fault indications and warning indications 4112.2. Fuses 4112.2.1. Fuses within the actuator controls 4112.2.2. Motor protection (thermal monitoring)
4213. Servicing and maintenance................................................................................................... 4213.1. Preventive measures for servicing and safe operation 4213.2. Maintenance 4213.3. Disposal and recycling
4314. Technical data......................................................................................................................... 4314.1. Technical data Part-turn actuator
4815. Spare parts............................................................................................................................. 4815.1. Part-turn actuators SGM 04.1 –SGM 10.1/SGMR 04.1 –SGMR 10.1 5015.2. Part-turn actuators SGM 12.1/SGMR 12.1
5216. Certificates.............................................................................................................................. 5216.1. Declaration of Incorporation and EC Declaration of Conformity
55Index........................................................................................................................................
57Addresses...............................................................................................................................
3
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Table of contents

1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others:
●Applicable configuration guidelines for fieldbus applications.
Safetyinstructions/warn-
ings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
●Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●Only operate the device if it is in perfect condition while observing these instruc-
tions.
●Immediately report any faults and damage and allow for corrective measures.
●Observe recognised rules for occupational health and safety.
●Observe national regulations.
●During operation,the housingwarmsupand surfacetemperatures>60 °C may
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators are designed for the operation of valves, e.g.butterfly
valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●Industrial trucks according to EN ISO 3691
●Lifting appliances according to EN 14502
4
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Safety instructions Modbus RTU

●Passenger lifts according to DIN 15306 and 15309
●Service lifts according to EN 81-1/A1
●Escalators
●Buried service
●Continuous submersion (observe enclosure protection)
●Potentially explosive atmospheres
●Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk.Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning could result in minor or moderate injury. May also be
used with property damage.
Potentially hazardous situation. Failure to observe this warning could result
in property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→Measures to avoid the danger
→Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
5
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Safety instructions

< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
6
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Safety instructions Modbus RTU

2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Additional plate, e.g. KKS plate (Power Plant Classification System)
Description of actuator name plate
Figure 2: Actuator name plate (example)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation
[4] Order number
[5] Actuator serial number
[6] Operating time
[7] Torque range
[8] Current type, mains voltage, mains frequency
[9] Electric power (motor)
[10] Wiring diagram number
[11] Control
[12] Can be assigned as an option upon customer request
[13] Enclosure protection
[14] Type of lubricant
[15] Setting range of swing angle
[16] Permissible ambient temperature
[17] Rated current
[18] Type of duty
[19] Data Matrix code
7
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Identification

Type designation Figure 3:Type designation (example)
1. Type and size of actuator
2. Flange size
Type and size These instructions apply to the following devices types and sizes:
Part-turn actuators for open-close duty: SGM 04.1, 05.1, 07.1, 10.1, 12.1
Part-turn actuators for modulating duty: SGMR04.1, 05.1, 07.1, 10.1, 12.1
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagramsand technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Actuator serial number Table 1:
Description of the serial number (with example of 0516NS12345)
NS123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationNS12345
Control Modbus RTU = Control via Modbus RTU interface.
Data Matrix code Whenregistered asauthoriseduser, youmay use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 4: Link to AUMA Assistant App:
For further Service & Support, software/apps/...refer to www.auma.com.
2.2. Short description
Part-turn actuator Definition in compliance with EN ISO 5211:
A part-turn actuator is an actuator which transmits a torque to the valve for less than
one full revolution.It need not be capable of withstanding thrust.
AUMA part-turn actuators are driven by an electric motor. For control in motor
operation and for processing the actuator signals, controls are integrated within the
housing.The actuator can be operated easily on site via the local controls.A
handwheel or crank is provided for manual operation.Manual operation is possible
without change-over.
The swing angle is limited by internal end stops. Switching off in end positions may
be either by limit or torque seating.
AUMA CDT The AUMA CDT software (accessories) can be used to establish a connection to a
computer (PC, laptop or PDA). Among others, the software can be used to read in
and out data and to save and modify settings.
The connection between computer and the integral actuator controls is made using
a service cable.
8
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Identification Modbus RTU

3. Transport, storage and packaging
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→Do NOT stand below hovering load.
→Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
3.2. Storage
Danger of corrosion due to inappropriate storage!
→Store in a well-ventilated, dry room.
→Protect against floor dampness by storage on a shelf or on a wooden pallet.
→Cover to protect against dust and dirt.
→Apply suitable corrosion protection agent to uncoated surfaces.
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion.If first signs of corrosion show, apply new corrosion protec-
tion.
Plastic protective caps supplied when leaving the factory are for transport protection
only.They have to be replaced for long-term storage.(Heed protection type indicated
on name plate.)
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory.The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil.For the disposal of the packaging material, we
recommend recycling and collection centres.
9
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Transport, storage and packaging

4. Assembly
4.1. Mounting position
The product described in this document can be operated without restriction in any
mounting position.
4.2. Actuator: mount to valve
4.2.1. Actuator for assembly: prepare
Prior to mounting, both valve and actuator must be in the same end position!
●For butterfly valves, the recommended mounting position is end position
CLOSED.
●For ball valves, the recommended mounting position is end position OPEN.
In compliance with the order, the actuator is supplied either in position CLOSED or
position OPEN.The mechanical position indicator supplies information on the set
position.
If the actuator position was not modified and agrees with the valve position, the
actuator can be mounted in the supplied position.
In case the actuator is in an incorrect position:
1. Operate the actuator into the same position as the valve via push buttons OPEN,
STOP, CLOSE while in motor operation.For motor operation, please refer to
<Actuator operation at the local controls> chapter.
2. Should the electrical connection not be available at the time of assembly, the
actuator can be operated into the required end position using the handwheel.
2.1 Turn the handwheel or the crank handle until reaching the internal end
stop of part-turn actuator (same end position OPEN or CLOSED as valve).
2.2 Turn handwheel by approximately two turns (overrun) in the opposite dir-
ection.
After this procedure, the actuator can be mounted to the valve.
4.2.2. Output drive for coupling
Application ●For valves with connections according to EN ISO 5211
●For rotating, non-rising valve stem
Assembly ●The actuator is mounted to the valve using a coupling placed onto the valve
shaft.
●Unbored couplings must be adapted and machined to match the valve shaft
prior to mounting (e.g. with bore and keyway, two-flat or square bore)
10
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Assembly Modbus RTU

Figure 5: Coupling variants
[1] Bore with keyway
[2] Square bore
[3] Bore with two-flats
[4] Valve shaft
[5] Output drive flange (size 12.1)
4.2.2.1. Mounting with coupling
Condition:Valve and actuator are in the same end position.
Figure 6: Coupling fitting dimensions
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Screw
Table 2:
Coupling fitting dimensions
Z max [mm]Y max [mm]X max [mm]Type, size - output mounting flange
4062.5SGM/SGMR 04.1-F07
4062.5SGM/SGMR 05.1-F07
5062.5SGM/SGMR 07.1-F07
60103.5SGM/SGMR 10.1-F10
62105SGM/SGMR 12.1-F12
1. Thoroughly degrease mounting faces of output mounting flanges.
2. Apply a small quantity of grease to the valve shaft [2].
3. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3], a retaining ring or a screw [4].Thereby, ensure that dimensions
X,Y or Z are observed (refer to figure and table <Coupling fitting dimensions>).
4. Apply non-acidic grease at splines of coupling.
11
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Assembly

5. Fit actuator.
Information: Ensure that the spigot (if provided) fits uniformly in the recess
and that the flanges are in complete contact.
6. If flange bores do not match thread:
6.1 Slightly rotate handwheel until bores line up.
6.2 If required, shift actuator by one tooth on the coupling.
7. Fasten actuator with screws.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
→Fasten screws crosswise to a torque according to table.
Table 3:
Tightening torques for screws, valid for all actuators which are not shock resistant and all
actuators with housing made of bronze
Tightening torque [Nm]Screws
Threads Strength class 8.8
24M8
48M10
Table 4:
Tightening torques for screws, valid for actuators with housing made of aluminium in
shock-resistant version.1)
Tightening torque [Nm]ScrewsFlange
Strength class 8.8Min. reach of screw into the ac-
tuator
Threads
2812 mmM8F07
5414.5 mmM10F10
Actuators with aluminium housing are powder coated, colour: standard AUMA silver-grey.1)
12
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Assembly Modbus RTU

5. Electrical connection
5.1. Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
→The electrical connection must be carried out exclusively by suitably qualified
personnel.
→Prior to connection, observe basic information contained in this chapter.
→After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan The pertaining wiring diagram/terminal plan (both in German and English) is attached
to the device in a weather-proof bag, together with these operation instructions.It
can also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks
(supply networks) The actuators are suitable for use in TN and TT networks with directly earthed star
point.Use in IT networks is permitted while observing the respective <Protection on
site>.
Protection on site For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current value for respective sizing is derived from the current consumption of
the actuator (refer to electrical data sheet).
The actuators are suitable for use in current circuits with a maximum short-circuit
1-phase AC current value of 5,000 A root-mean-square (R.M.S).The output data of
the fuses to be provided on site must not exceed the following values:15 A/250 V
at a maximum mains current of 5,000 A AC.
Use appropriate insulation monitors when working in power installations, for example
an insulation monitor measuring the pulse code.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B.
Power supply for the
controls (electronics) In case of external supply of the controls (electronics):The external power supply
must have a reinforced insulation against the mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance
with IEC 61800-5-1.
Safety standards All externally connected devices shall comply with the relevant safety standards.
All connected electric circuits shall comply with the requirements for protective
separation.
Type of current, mains
voltage and mains fre-
quency
Figure 7: Name plate (example)
[1] Type of current
[2] Mains voltage
[3] Mains frequency (for 1-ph AC motors)
13
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Electrical connection

Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Cable installation in ac-
cordance with EMC Signal and fieldbus cables are susceptible to interference.
Motor cables are interference sources.
●Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
●If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
●For the connection of remote position transmitters, screened cables must be
used.
Connecting cables ●For device insulation, appropriate (voltage-proof) cables must be used.Specify
cables for the highest occurring rated voltage.
●It is advised to use a shielded cable.
●For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
●The cross-sectional area of every protective earthing conductor which does not
form not part of the supply cable or the cable enclosure, shall, in any case, not
be less than:
- With mechanical protection: minimum 2.5 mm²
- Without mechanical protection: minimum 4 mm²
Fieldbus cables Only cables complying with the recommendations of EIA 485 specifications should
be used for Modbus wiring.
Cable recommendation:
Impedance: 135 to 165 Ohm, at a measurement frequency
between 3 and 20 MHz
Cable capacity: < 30 pF per metre
Wire diameter: > 0.64 mm
Wire cross section: > 0.34 mm², corresponding to AWG 22 or bigger
Loop resistance: < 110 Ohm per km
Screening: CU shielding braid or shielding braid and shielding
foil
Prior to installation, please note:
●Connect maximum 32 devices to one segment.
●If more devices are to be connected:
- Connect several segments using repeaters.
●Respect a distance of minimum 20 cm between the fieldbus cable and other
cables.
●If possible, fieldbus cables should be laid in a separate, conductive, and earthed
cable tray.
●Make sure to avoid potential differences between the individual devices on the
fieldbus (perform an equipotential earth bonding).
14
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Electrical connection Modbus RTU

5.2. Connection via bayonet connector
Figure 8: Arrangement of connections
[XK1] Power terminals (mains cables)
[XK2] Control contacts/fieldbus cables ↑from previous device
[XK3] Control contacts/fieldbus cables ↓to next device
Cross sections:
●Power terminals: max. 1.5 mm² flexible
●Control contacts: max. 1.5 mm² flexible
Hazardous voltage at open connector (capacitor discharge)!
Risk of electric shock.
→After disconnecting the power supply (removing connector for power terminals),
wait at least 5 seconds before touching the pins/sockets.
5.2.1. Mains and fieldbus cables: connect
Observe prior to connec-
tion ●Observe permissible cross sections of connectors used.
●Use suitable crimping tools to connect wires:
- For bayonet connectors:
e.g.Cannon four indent crimping tool
●Observe operation instructions of the connector manufacturer.
●Upon request, AUMA provide suitable connection sets.
●For further information refer to separate "Technical data Connector".
●Observe characteristics of network topology used.
15
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Electrical connection

Figure 9: Structure for line topology
further fieldbus devices will follow□
last fieldbus device, termination must be activated
■
from the previous device↑
to the next device↓
Figure 10: Structure for redundant loop topology
Input□
Output▣
from the previous device↑
to the next device↓
Information ●For loop topology, automatic termination is performed as soon as the actuator
is connected to the power supply.
●In case of a power failure, the two RS-485 loop segments will be automatically
connected so that the actuators following these segments remain available.
●Redundant loop topology may only be established when using a SIMA Master
Station.
16
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Electrical connection Modbus RTU

Steps 1. Connectmains andfieldbuscablesaccording to the order related wiringdiagram.
Table 5:
Assignment of fieldbus cables
ColourAssignmentPinPlug/socket connector
Green1AAFor XK2 (socket)
Red1BB
E 1)
ShieldScrew connection
Green2AAFor XK3 (socket)
Red2BB
E 1)
ShieldScrew connection
As an option, pin E can be connected to the shielding.This is, however, not recommended.1)
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→Connect all protective earth conductors.
→Connect PE connection to external protective earth conductor of connecting
cables.
→Start running the device only after having connected the protective earth con-
ductor.
2. Connect protective earth conductor according to wiring diagram, symbol: .
3. If the actuator is the last fieldbus device, seal open connector [XK3] with pro-
tective cap. Heed protection type indicated on name plate.Plastic protective
caps supplied when leaving the factory are for transport protection only.They
are not appropriate for permanent use.
5.3. Earth connection, external
The housing is equipped with an external earth connection (U-bracket) to integrate
the device in equipotential earth bonding.
Figure 11: Earth connection
Earth connection (U-bracket), external
17
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Electrical connection

5.4. Accessories for electrical connection
5.4.1. Local controls mounted on wall bracket
—Option —
The wall bracket allows separate mounting of local controls and actuator.
Application If the actuator cannot be accessed safely.
[1] Wall bracket
[2] Local controls
[3] Phoenix connector with connecting cable
Observe prior to connec-
tion ●Permissible length of connecting cables: max. 30 m.
●We recommend using an AUMA cable set (5 m).
●A retrofit kit is available for actuators without wall bracket.
●Establish cable connection via plug/socket connector as illustrated.
18
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Electrical connection Modbus RTU

6. Indications
6.1. Mechanical position indication via indicator mark
Figure 12: Mechanical position indicator
[1] End position OPEN reached
[2] End position CLOSED reached
[3] Indicator mark at cover
Characteristics ●Independent of power supply
●Used as running indication:Indicator disc rotates during actuator operation and
continuously indicates the valve position
(For “clockwise closing version”, the symbols / rotate in counterclockwise
direction for operation in direction CLOSE)
●Indicates that end positions (OPEN/CLOSED) have been reached
(Symbols (OPEN)/ (CLOSED) point to the indicator mark at cover)
6.2. Indication lights
Figure 13: Indication lights on local controls
[1] Indication light OPEN/warning/fault (green/yellow/red)
[2] Indication light CLOSE/LOCAL/set end position (yellow/blue)
Table 6:
Indication light [1] (default setting)
DescriptionSignificationColour/state
Actuator is in end position OPEN.OPENilluminated in green
Strokebetween selected end positions (OPEN/CLOSED) is below
the preset minimum stroke (factory setting 60 % of maximum
rotation). Refer to <Corrective action> chapter.
Warningblinking in yellow
The number of blinking signals indicates the number of fault
signal. Refer to <Corrective action> chapter.
Faultblinking in red
19
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Modbus RTU Indications

Table 7:
Indication light [2] (default setting)
DescriptionSignificationColour/state
Actuator is in end position CLOSED.CLOSEilluminated in yellow
Operation mode LOCAL is active.The actuator can be operated
via push buttons.
LOCALblinking in blue
(1 Hz)
Setting mode for end position setting is active.Set end positionblinking in blue
(5 Hz)
20
SGM 04.1 –SGM 12.1 / SGMR 04.1 –SGMR 12.1
Indications Modbus RTU
Other manuals for SGM 04.1
2
This manual suits for next models
16
Table of contents
Other AUMA Controllers manuals

AUMA
AUMA PROFOX PF-Q80 User manual

AUMA
AUMA TIGRON TR-M30X User manual

AUMA
AUMA MEC 03.1 User manual

AUMA
AUMA SAR 16.2 User manual

AUMA
AUMA SA 25.1 User manual

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SQEx 05.2 User manual

AUMA
AUMA SVCR 05.1 User manual

AUMA
AUMA SV 05.1 User manual

AUMA
AUMA PF-M25 Series Manual

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SA 07.1 User manual

AUMA
AUMA SA 07.2 User manual

AUMA
AUMA SQ Series User manual

AUMA
AUMA ABG 10.2 User manual

AUMA
AUMA SQVEx 05.2 User manual

AUMA
AUMA SG 05.1-FA07 User manual

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SAI 6 User manual

AUMA
AUMA GST 10.1 Administrator Guide