Automated Logic OptiFlex G5CE Owner's manual

1150 Roberts Boulevard, Kennesaw, Georgia 30144
770-429-3000 Fax 770-429-3001 | www.automatedlogic.com
OptiFlex™ BACnet Integrator (part no. G5CE)
Technical Instructions
Automated Logic® Proprietary & Confidential • All rights reserved
Rev. 6/9/2022

Verify that you have the most current version of this document. Go to the Automated Logic® Partner
Community website to download it.
Important changes are listed in Document revision history at the end of this document.
A Carrier Company
© 2022 Carrier. All rights reserved.

Contents
What is the OptiFlex™ BACnet Integrator (part no. G5CE)? ..........................................................................1
Critical Product Announcement ................................................................................................... 2
Specifications ............................................................................................................................. 2
Zone sensors............................................................................................................................... 5
Touchscreen devices ................................................................................................................... 5
To mount the G5CE .................................................................................................................................6
Wiring for power......................................................................................................................................7
To wire for power ......................................................................................................................... 8
Addressing the G5CE...............................................................................................................................8
To set up autobaud...................................................................................................................... 9
To set the IP address ................................................................................................................. 10
To set the Port S1 address and baud rate ................................................................................... 12
To set the Port S2 address and baud rate ................................................................................... 12
Wiring for communications ....................................................................................................................13
Wiring specifications ................................................................................................................. 13
To connect the G5CE to the Ethernet .......................................................................................... 14
To wire to a BACnet/ARCNET network ........................................................................................ 14
To wire to a BACnet MS/TP network ........................................................................................... 14
To wire a third-party device ........................................................................................................ 15
Wiring devices to the G5CE's Rnet port ...................................................................................................15
To communicate through the BACnet/IP Service Port network ...................................................................15
Downloading the G5CE..........................................................................................................................16
To download from the WebCTRL® interface ............................................................................... 17
Adjusting the G5CE driver properties.......................................................................................................17
Driver........................................................................................................................................ 17
Device....................................................................................................................................... 19
Notification Classes .................................................................................................................. 19
Calendars ................................................................................................................................. 20
Common and Specific Alarms .................................................................................................... 21
BACnet Router Properties .......................................................................................................... 22
BACnet Firewall......................................................................................................................... 23
Network Diagnostics - Statistics ................................................................................................ 24
Network Diagnostics - Packet Capture ....................................................................................... 26
Communication Status.............................................................................................................. 27
To set up Network Statistic trends .............................................................................................. 28
To set up the controller through the Service Port .......................................................................................29
ModStat tab.............................................................................................................................. 29
Device tab................................................................................................................................. 30
Ports tab ................................................................................................................................... 31
BACnet tab ............................................................................................................................... 31
Modbus tab .............................................................................................................................. 33
Security tab............................................................................................................................... 33
To communicate locally through the Rnet port..........................................................................................34
To set up a Local Access connection in the WebCTRL® interface ................................................ 35
Troubleshooting....................................................................................................................................36
LEDs ......................................................................................................................................... 36
To get a Module Status report .................................................................................................... 38
To get a Device Log.................................................................................................................... 39
To get the G5CE's serial number ................................................................................................ 39
To replace the G5CE's fuse........................................................................................................ 39
To take the G5CE out of service.................................................................................................. 40
To revert to default settings........................................................................................................ 41
Compliance..........................................................................................................................................42
FCC Compliance ....................................................................................................................... 42

CE and UKCA Compliance.......................................................................................................... 42
Industry Canada Compliance..................................................................................................... 42
BACnet Compliance .................................................................................................................. 42
Appendix - Module Status field descriptions ............................................................................................43
Document revision history......................................................................................................................45

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
1
What is the OptiFlex™ BACnet Integrator (part no. G5CE)?
The OptiFlex™ BACnet Integrator (part no. G5CE):
•Provides BACnet routing between any supported BACnet communication types
•Runs control programs
•Can have two BACnet/IP networks communicating on the Gig-E port
•Can serve as a BACnet Broadcast Management Device (BBMD) on each of the BACnet/IP networks
•Supports Foreign Device Registration (FDR)
•Supports DHCP IP addressing
•Has built-in network diagnostic capture functionality for troubleshooting
•Has network statistics that can be viewed numerically or as trend graphs
•Supports Rnet devices
•Works with the WebCTRL® v6.5 or later system with the latest cumulative patch
•Can serve as a gateway that can act as a:
○Master or slave on a Modbus serial network
○Server or client on a Modbus TCP/IP network

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
2
The G5CE has 4 physical ports for BACnet or Modbus communication:
Port
Port type
For routing this type
of communication...
At...
Gig-E
10/100/1000 Mbps Ethernet
BACnet/IP,
BACnet/Ethernet, and/or
Modbus TCP/IP
10, 100, or 1000 Mbps
(1 Gbps)
S1
High-speed EIA-485 port
BACnet/ARCNET
or
BACnet/MSTP
or
Modbus Serial
156 kbps
9.6 to 115.2 kbps
9.6 to 115.2 kbps
S2
Electrically isolated EIA-485 port
BACnet/MSTP
or
Modbus Serial
9.6 to 115.2 Kbps
9.6 to 115.2 kbps
Service
Port
10/100 Mbps Ethernet
HTTP/IP
BACnet/IP Service Port
10 or 100 Mbps
The G5CE also has the following ports:
•Rnet port for ZS sensors, Wireless Adapter for wireless sensors, and an Equipment Touch
•USB port for recovery
•Ethernet Service Port for connecting locally to controller setup pages and the OptiPoint™ interface
Critical Product Announcement
Due to the global semiconductor supply chain uncertainty, starting July 2022, the G5CE will no longer
support communication over the ARCNET network. ARCNET-disabled G5CE controllers have a serial
number starting with the prefix RT5 and have an updated label. See To get the G5CE's serial number
(page 39).
The G5CE's driver properties and controller setup pages only show available communication selection
options.
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs*
999
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
1500
Third-party Modbus integration points
25
* Depends on available memory.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
3
Power
24 Vac ±10%, 50–60 Hz, 50 VA
26 Vdc ±10%, 15 W
Gig-E port
10/100/1000 BaseT, full duplex, Ethernet port for BACnet/IP and/or
BACnet/Ethernet, or Modbus TCP/IP communication.
Port S1
For communication with either of the following:
•A BACnet ARCNET network at 156 kbps
•A BACnet MS/TP network at 9600 to 115200 bps
•A Modbus serial network at 9600 to 115200 bps
This port's End of Net? switch can be set to Yes to terminate the network
segment.
Port S2
For communication with either of the following:
•A BACnet MS/TP network at 9600 to 115200 bps
•A Modbus serial network at 9600 to 115200 bps
This port's End of Net? switch can be set to Yes to terminate the network
segment.
Rnet port
•Supports Up to 15 ZS wireless and/or ZS sensors, and one Equipment
Touch or OptiPoint™ interface
•Supports local connection for a laptop running the WebCTRL®
application
•Supplies 12 Vdc/62.5 mA power across its rated temperature range.
NOTE Ambient temperature and power source fluctuations may
reduce the power supplied by the Rnet port.
NOTE If the total power required by the sensors on the Rnet exceeds the
power supplied by the Rnet port, use an external power source. The
Wireless Adapter, Equipment Touch, or OptiPoint™ interface must be
powered by an external power source. See the specifications in each
device's Technical Instructions to determine the power required.
Service Port
Ethernet port at 10 or 100 Mbps for setting up the controller and
troubleshooting through a local connection to a computer or connecting to
the OptiPoint™ interface
USB port
USB 2.0 host port for device recovery
Microprocessor
32-bit ARM Cortex-A8, 600MHz, processor with multi-level cache memory
Memory
16 GBs eMMC Flash memory and 256 MB DDR3 DRAM (22 MB available
to use).
User data is archived to non-volatile Flash memory when parameters are
changed, every 90 seconds, and when the firmware is deliberately
restarted.
NOTE When you change a parameter, you must wait 30 seconds before
turning the power off, in order for the change to be saved.
Real-time clock
Real-time clock keeps track of time in the event of a power failure for up to
3 days.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
4
Protection
Device is protected by a replaceable, fast acting, 250 Vac, 2A, 5mm x
20mm glass fuse.
The power and network ports comply with the EMC requirements
EN50491-5-2.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
LED status indicators
•Tricolor NET LED to show network status
•Tricolor SYS LED to show system status
•A TX (Transmit) and RX (Receive) LED for the following ports:
•Gig-E
•Port S1
•Port S2
•Rnet
See LEDs (page 36).
Environmental operating
range
-40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing
NOTES
•The G5CE is suitable for installation inside or outside the building
envelope.
•Install in a UL Listed enclosure only.
•Do not change the position of the power or End of Net switch at
temperatures below -22°F (-30C) to ensure proper operation and
electrical connectivity.
Physical
Fire-retardant plastic ABS, UL94-5VA
Terminal blocks and
connectors
Screw-type terminal blocks.
0.2 in (5.08 mm) pitch connectors
Mounting
35mm DIN rail mounting or screw mounting
Overall dimensions
A:
B:
Depth:
7.1 in. (18.03 cm)
6.95 in. (17.65 cm)
2.09 in. (5.31 cm)
Screw mounting
dimensions
C:
D:
6.45 in (16.38 cm)
4.1 in. (10.4 cm)
Weight
1 lb. 1 oz. (0.482 kg)
BACnet support
Conforms to the BACnet Building Controller (B-BC) Standard Device Profile
as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 14

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
5
Compliance
United States of America:
FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart
B, Class A; UL Listed to UL 916, PAZX, Energy Management Equipment
Canada:
Industry Canada Compliant, ICES-003, Class A
cUL Listed UL 916, PAZX7, Energy Management Equipment
Europe: Mark, UK:
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
RoHS Compliant: 2015/863/EU
REACH Compliant
Australia and New Zealand:
C-Tick Mark, AS/NZS 61000-6-3
Zone sensors
You can wire ZS sensors and/or a Wireless Adapter that communicates with wireless sensors to the
G5CE's Rnet port. You can have up to 15 ZS and/or wireless sensors.
NOTES
•A control program can use no more than 5 ZS sensors, so you must use multiple control programs
if your Rnet network has more than 5 sensors.
•ZS and wireless sensors can share the Rnet with an Equipment Touch or OptiPoint™ interface.
CAUTION Rnet power
The Rnet port provides 12 Vdc at 62.5 mA maximum that can be used to power zone sensors. When
determining which devices to put on the Rnet, verify that the total current draw of the sensors does not
exceed the controller's Rnet power. See the sensor's Technical Instructions to determine the power
required.
Touchscreen devices
You can connect the G5CE to the touchscreen devices using the Rnet port or the Ethernet Service port.
Rnet port
You can wire an Equipment Touch or OptiPoint™ interface to the G5CE's Rnet port to view or change
the controller's property values, schedule equipment, view trends and alarms, and more, without having
to access the system's server. The Rnet port can have one Equipment Touch or OptiPoint™ interface,
plus ZS sensors and/or a Wireless Adapter that communicates with wireless sensors.
NOTE These touchscreen devices are not powered by the Rnet port.
•The OptiPoint™ interface requires a 24 Vdc external power source.
•The Equipment Touch requires a 24 Vac external power source.
•

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
6
Ethernet port
You can connect the OptiPoint™ interface to the G5CE's Ethernet Service port to view or change the
controller's property values, schedule equipment, view trends and alarms, and more, without having to
access the system's server.
NOTES
•These touchscreen devices are not powered by the Ethernet port.
•The OptiPoint™ interface requires a 24 Vdc external power source.
CAUTION A touchscreen device can share a power supply with the Automated Logic® controller
if:
•The power source shared by the controller and Equipment Touch is AC power.
•The power source shared by the controller and OptiPoint™ interface is DC power.
•You maintain the same polarity.
•You use the power source only for Automated Logic® controllers.
To mount the G5CE
The G5CE must be mounted in a metal enclosure or cabinet which is properly rated for the location
where it is being installed.
NOTE We recommend screw mounting when installing in a high temperature and high humidity
environment.
DIN rail mount
1 Push down and pull out the center tabs shown below to clear the din rail trough on the back of the
controller.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
7
2 Place the controller on the DIN rail so that the rail is in the trough on the back of the controller.
3 Push the center tabs towards the controller until you hear them click.
4 Pull gently on the controller to verify that it is locked in place.
Screw Mount
Leave about 2 in. (5 cm) on each side of the controller for wiring.
Insert #6 screws through the mounting holes. Use no more than 8 in.lbs. torque to secure plastic tab to
mounting surface.
A:
B:
C:
D:
Depth:
7.1 in. (18.03 cm)
6.95 in. (17.65 cm)
6.45 in. (16.38 cm)
4.1 in. (10.4 cm)
2.09 in (5.31 cm)
Wiring for power
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
•The G5CE is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
•Automated Logic® controllers can share a power supply as long as you:
○Maintain the same polarity.
○Use the power supply only for Automated Logic® controllers.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
8
To wire for power
1 Make sure the G5CE’s power switch is in the OFF position to prevent it from powering up before you
can verify the correct voltage.
2 Remove power from the power supply.
3 Pull the red screw terminal connector from the controller's power terminals labeled 24 Vac/Vdc
(+/-).
4 Connect the power supply's wires to the red screw terminal connector.
5 Connect an 18 AWG or larger wire from the power supply's negative (-) terminal to earth ground.
This wire must not exceed 12 in. (30.5 cm).
6 Apply power to the power supply.
7 Measure the voltage at the red screw terminal connector to verify that the voltage is within the
operating range of 20 to 30 Vac or 23.4 to 30 Vdc.
8 Insert the red screw terminal connector into the controller's power terminals.
9 To verify the polarity of the wiring, measure the voltage from the negative terminal of the red screw
terminal connector to a nearby ground. The reading should be 0V.
10 Turn on the expander's power switch.
11 Verify that the LED on top of the controller is on.
12 Measure the voltage at the red screw terminal connector to verify that the voltage is within the
operating range of 20 to 30 Vac or 23.4 to 30 Vdc.
Addressing the G5CE
Set this port's address ...
In this location...
See...
IP
Service Port
To set the IP address (page 10)
Port S1
On the controller's
rotary switches
To set the Port S1 address and baud rate
(page 12)
Port S2
Service Port
To set the Port S2 address and baud rate
(page 12)

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
9
To access the controller setup through the Service Port:
1 Connect an Ethernet cable from a computer to the controller as shown below.
2 Turn off the computer's Wi-Fi if it is on.
3 If your computer uses a static IP address, use the following settings:
○Address: 169.254.1.x, where x is 2 to 7
○Subnet Mask: 255.255.255.248
○Default Gateway: 169.254.1.1
4 If it uses a DHCP address, leave the address as it is.
5 Open a web browser on the computer.
6 Navigate to http://local.access or http://169.254.1.1 to see the Service Port controller setup
pages.
See To set up the controller through the Service Port (page 29) for general information on using the
controller setup pages.
To set up autobaud
The G5CE can automatically receive or establish the baud rate on a serial network. When you configure
a device on the network for autobaud and then power it up, the device detects the incoming baud rate
on the network and sets its baud to match.
Autobaud does not work unless there is a device on the network, whether Automated Logic® or third
party, that has the baud rate already set. You can manually set the baud rate on more than one device,
as long as the rate is the same for every device.
NOTES
•The received baud rate stays intact during power cycles.
•We recommend you set the baud rate manually on the router for the network.
MS/TP
MSTP Autobaud can be configured in either the:
•Service Port controller setup pages > BACnet tab > Port S1 or Port S2
or
•The WebCTRL® interface, on the Network tree, select your G5CE > Driver > BACnet Router
Properties > MS/TP Configuration on Port S1 or on Port S2. See BACnet Router Properties (page
22).

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
10
Modbus
Modbus Serial Autobaud can be configured in either the:
•Service Port controller setup pages > Modbus tab > Modbus RS-485 > Port Configuration
or
•The WebCTRL® interface, on the Network tree, select your G5CE and go to Driver >
Communication Status > Modbus Serial
NOTE See the Modbus Integration Guide.
NOTE If you set Autobaud or make other changes in the controller setup pages, you must upload the
changes to the system database the first time you access the controller in the WebCTRL® interface.
This preserves those settings when you download memory or parameters to the controller.
To set the IP address
You must define the G5CE's IP addressing (IP address, subnet mask, and default gateway) in the
Service Port controller setup pages so that the controller can communicate with the WebCTRL Server
on the IP network. This IP addressing must match the IP addressing defined in SiteBuilder in the
controller's Properties dialog box.
Use one of the IP addressing schemes described below with the associated instructions that follow.
Use a...
If...
DHCP IP Address
generated by a DHCP server
The IP network uses a DHCP server for IP addressing
Custom Static IP Address
from your network administrator
You do not use a DHCP server and the answer to any of the
following questions is yes. Will the WebCTRL® system:
•Share a facility's existing IP data network?
•Have 254 or more devices with static IP addresses?
•Be connected to the Internet?
•Have at least one device located on the other side of an
IP router?
•Have any third-party IP devices?
Default IP Address
that your system creates
The answer to all of the above questions is no.
NOTE Carefully plan your addressing scheme to avoid duplicating addresses. If third-party devices are
integrated into the system, make sure your addresses do not conflict with their addresses.
To set a DHCP IP address
1 On the controller setup Modstat tab, find the controller’s Ethernet MAC address and write it down.
2 On the Ports tab under IP Port, select DHCP.
3 Click Save.
4 Write down the IP Address.
5 Give the DHCP network administrator the IP address and Ethernet MAC address and ask him to
reserve that IP address for the controller so that it always receives the same IP address from the
DHCP server.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
11
To set a custom IP address
1 Obtain the IP address, subnet mask, and default gateway address for the controller from the facility
network administrator.
2 On the controller setup Ports tab under IP Port, select Custom Static.
3 Enter the IP Address, Subnet Mask, and Default Gateway addresses that the network
administrator gave you.
4 Click Save.
To set a default IP address
Default IP addressing assigns the following to the controller:
•IP address = 192.168.168.x
where x is the setting on the rotary switches in the range from 1 to 253
•Subnet Mask = 255.255.255.0
•Default Gateway = 192.168.168.254
1 Set the controller's three rotary switches to a unique address on the network. Set the left rotary
switch to the hundreds digit, the middle switch to the tens digit, and the right switch to the ones
digit.
EXAMPLE The switches below are set to 125.
2 On the controller setup Ports tab under IP Port, select Default IP Address.
3 Click Save.
CAUTIONS
•If you are using Port S1, the rotary switches also determine that network's address. Although the
ARCNET address range is 1 to 255, the Default IP address range is 1 to 253. Setting the rotary
switches to 0 will set the Default IP address to 1. Setting the switches to 255 will set the Default IP
to 253. Do not set the switches to 254.
•If you set the Default IP address on the controller setup Ports tab and then change the rotary
switches, you must do one of the following to correct the IP address in the controller:
○Go to the controller setup Ports tab and click the Update IP Address.
○Cycle the controller's power.
You will then need to correct the IP address in SiteBuilder.
NOTE The default address is an intranet address. Data packets from this address are not routable to
the Internet.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
12
To set the Port S1 address and baud rate
The address should be in one of the following ranges based on the port's use.
•For ARCNET, the range is 1 to 255.
•For MS/TP, the range is 0 to 127.
•For Modbus, the range is 1 to 247.
You set this address on the G5CE's three rotary switches. Set the left rotary switch to the hundreds
digit, the middle switch to the tens digit, and the right switch to the ones digit.
EXAMPLE The switches below are set to 125.
CAUTION If you are using a Default IP address, the rotary switches also determine the IP address.
For MS/TP, set up autobaud or the port's baud rate
1 On the controller setup BACnet tab under Port S1, select the MSTP Baud Rate or select Yes for
MSTP Autobaud. The default is 76,800 bps.
NOTES
○See To set up autobaud (page 9) for details.
○If not using autobaud, enter the identical baud rate for all devices on the same MS/TP network
segment.
2 Click Save.
Modbus
For Modbus, see the Modbus Integration Guide.
To set the Port S2 address and baud rate
For MS/TP, set up autobaud or the port's baud rate
1 On the controller setup BACnet tab under Port S2, type the address in the MSTP Address field. The
address must be in the range 0 to 127.
2 Select the MSTP Baud Rate or select Yes for MSTP Autobaud. The default is 76,800 bps.
NOTES
○See To set up autobaud (page 9) for details.
○If not using autobaud, enter the same baud rate for all devices on the MS/TP network.
3 Click Save.
Modbus
For Modbus, see the Modbus Integration Guide.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
13
Wiring for communications
The G5CE communicates on the following ports.
Port
Protocol
Port type(s)
Speed(s)
Gig-E
BACnet/IP,
BACnet/Ethernet, and/or
Modbus TCP/IP
Ethernet
10, 100, or 1000 Mbps
(1 Gbps)
Port S1 1
BACnet/ARCNET
EIA-485
156 kbps
Port S1 1
or
Port S2
BACnet/MSTP
Modbus Serial
EIA-485
9.6 to 115.2 kbps 2
9.6 to 115.2 kbps 2
Service Port 3
HTTP/IP
Ethernet
10 Mbps
100 Mbps
Rnet Port
See Wiring devices to the G5CE's Rnet port (page 15).
USB Port
USB2.0
USB
1Set the Port S1 Configuration rotary switch to:
0if port is not used
1for MS/TP
2for ARCNET
3for Modbus
4is for future use
2Default for MS/TP is 76.8 kbps.
Default for Modbus is 38.4 kbps.
3See To set up the controller through the Service Port.
Wiring specifications
For...
Use...
Maximum Length
Ethernet
Cat5e or higher Ethernet cable
328 feet (100 meters)
ARCNET 1
and
MS/TP 2
22 AWG, low-capacitance, twisted,
stranded, shielded copper wire
2000 feet (610 meters)
1See the ARC156 Wiring Technical Instructions.
2See the MS/TP Networking and Wiring Technical Instructions.
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
14
To connect the G5CE to the Ethernet
Connect an Ethernet cable to the Gig-E Ethernet port.
NOTE If your system has controllers on different IP subnets separated by an IP router, you must
configure one controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not
configure more than one BBMD per subnet as this may cause circular routes. See "Setting up BACnet
Broadcast Management Devices (BBMDs)" in SiteBuilder or WebCTRL® Help.
To wire to a BACnet/ARCNET network
1 Turn off the G5CE's power.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to Port S1’s screw terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
4 If the controller has a Port S1 Configuration rotary switch, set it to 2.
5 If the G5CE is at either end of a network segment, set the port's End of Net? switch to Yes.
NOTE The controller’s End of Net switch applies network termination and bias. If the controller is at
the end of a network segment that includes a DIAG485 that has its Bias jumper in the ON position,
set the End of Net? switch to No and connect a 120 ohm termination resistor to the Net+ and Net-
terminals. See DIAG485 Technical Instructions for more information.
6 Turn on the controller's power.
7 To verify communication with the network, get a Module Status report in the WebCTRL® interface
for a controller on the ARCNET network.
NOTE This step requires that you have set up the router in SiteBuilder and downloaded it from the
WebCTRL® interface.
To wire to a BACnet MS/TP network
An MS/TP network can be wired to either Port S1 or Port S2.
1 Turn off the G5CE's power.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the Port S1 or Port S2 screw terminals labeled Net +, Net -,
and Shield.
NOTE Use the same polarity throughout the network segment.
4 If you are using Port S1, and the controller has a Port S1 Configuration rotary switch, set it to 1.
NOTE If Port S1 is not being used for any network, set this rotary switch to 0.
5 If the G5CE is at either end of a network segment, set the port's End of Net? switch to Yes.
NOTE The controller’s End of Net switch applies network termination and bias. If the controller is at
the end of a network segment that includes a DIAG485 that has its Bias jumper in the ON position,
set the End of Net? switch to No and connect a 120 ohm termination resistor to the Net+ and Net-
terminals. See DIAG485 Technical Instructions for more information.
6 Turn on the controller's power.
7 To verify communication with the network, get a Module Status report in the WebCTRL® interface
for a controller on the MS/TP network.
NOTE This step requires that you have set up the router in SiteBuilder and downloaded it from the
WebCTRL® interface.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
15
To wire a third-party device
BACnet: You can wire a third-party BACnet device to the G5CE's Gig-E port, Port S1, or Port S2. See the
BACnet Integration Guide for the G5CE.
Modbus: You can wire a third-party Modbus TCP/IP device (client or server) to the G5CE's Gig-E port or
a Modbus master or slave device to Port S1 or Port S2. See Modbus Integration Guide for the G5CE.
Wiring devices to the G5CE's Rnet port
You can wire the following devices to the G5CE's Rnet port in a daisy-chain configuration:
•ZS sensors
•Wireless Adapter that communicates with wireless sensors
•Equipment Touch
•OptiPoint™ interface
See the device's Technical Instructions for complete wiring instructions.
NOTES
•ZS sensors, a Wireless Adapter, and an Equipment Touch can share the same Rnet.
•The Rnet communicates at a rate of 115.2 kbps.
To communicate through the BACnet/IP Service Port network
You can connect to the Service Port to access your network through the WebCTRL® application.
1 Connect an Ethernet cable from a computer to the controller as shown below.
2 Turn off the computer's Wi-Fi if it is on.
3 If your computer uses a static IP address, use the following settings:
○Address: 169.254.1.x, where x is 2 to 7
○Subnet Mask: 255.255.255.248
○Default Gateway: 169.254.1.1
4 If it uses a DHCP address, leave the address as it is.

OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
16
5 Open a web browser on the computer and login to your WebCTRL® application.
6 On the System Configuration tree, select Connections > Properties > Configure tab.
7 Select BACnet/IP Service Port Connection from the drop-down list and click Add.
8 If needed, enter the Service Port Network Number as follows:
○0- the computer or the OptiPoint™ interface communicates only with the G5CE and not the
network
○1to 65534 - the G5CE's network number for network communication
○65535 - searches for an available network number from 65531 to 65534. If any of these
numbers are not available, you will have to assign a network number and enter it.
9 Click Accept.
10 On the right of the page, in the Networks using selected connection table, click the checkbox next
to the network you want to connect to.
11 Click Accept.
12 On the Configure tab, select the BACnet/IP Service Port Connection and click Start. The status
changes to Connected.
Downloading the G5CE
Download to send the following items to the G5CE:
Item
Notes
Up to 999 control
programs, depending
on available memory
Must be in WebCTRLx.x\webroot\<system_name>\programs.
drv_fwex driver
The driver must be in WebCTRLx.x\webroot\<system_name>\drivers.
NOTE To verify that you have the driver's latest version, Go to the Automated
Logic® Partner Community website. Compare the latest version to the
G5CE's driver in SiteBuilder.
Editable properties
Schedules
If you change any of the above items or the G5CE's address after the initial download, you must
download again. The first download takes longer than subsequent downloads.
CAUTIONS
•The G5CE will lose stored data, such as trends, when you download.
•The G5CE outputs will not maintain their states when you download. This could cause equipment
controlled by the G5CE to shut down and/or restart.
Table of contents
Popular Network Hardware manuals by other brands

Ruijie
Ruijie Reyee RG-EST Series Release notes

Idis
Idis DR-2100P Series Operation manual

Patton electronics
Patton electronics Model 2711 user manual

Digi
Digi ConnectCore 6 Plus Hardware reference manual

Elo TouchSystems
Elo TouchSystems I-Series user manual

D-Link
D-Link ShareCenter Shadow DNS-325 user manual