2Tech Support 770-844-4200www.productivity2000.com
General Specifications
Operating Temperature 0º to 60ºC (32º to 140ºF)
Storage Temperature -20º to 70ºC (-4º to 158ºF)
Humidity 5 to 95% (non-condensing)
Environmental Air No corrosive gases permitted
Vibration IEC60068-2-6 (Test Fc)
Shock IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation 1800VAC applied for 1 second
Insulation Resistance > 10MΩ @ 500VDC
Heat Dissipation 10000mW (Loop Power Included)
Enclosure Type Open Equipment
Module Keying to Backplane Electronic
Module Location Any I/O slot in a Productivity2000 System
Field Wiring
Use ZIPLink Wiring System ONLY. See “Wiring Options”
on page 5. Must use copper conductors 75°C or
equivalent.
EU Directive
See the “EU Directive” topic in the Productivity Suite
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type 24-Pin Molex Style 43025-2400
Weight 90g (3.2 oz)
Agency Approvals
UL 61010-1 and UL 61010-2-201 File E139594, Canada
and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-
201 Safety)*
Output Specifications
Output Channels 16
Module Signal Output Range 4–20 mA sourcing
Signal Resolution 12-bit
Resolution Value of LSB
(least significant bit)
4-20 mA = 3.9 μA / count
1 LSB = 1 count
Data Range 0 to 4095 counts
Output Type (sourcing) Current: 20mA max
Output Value in Fault Mode Less than 4mA
Load Impedance
0–570 Ω (19.2 VDC), 0–690 Ω (21.6 VDC),
0–810 Ω (24VDC), 0–930 Ω (26.4 VDC),
0–1100 Ω (30VDC)
Minimum Load: 0Ω @ 0–45°C
125Ω @ 45–60°C ambient temperature
Maximum Inductive Load 1mH
Allowed Load Type Grounded
Maximum Inaccuracy 1% of range (Including Temperature Drift)
Maximum Full Scale Calibration Error (Including
Offset) ±0.2% of range minimum
Maximum Offset Calibration Error ±0.2% of range maximum
Accuracy vs. Temperature ±75 PPM / °C maximum full-scale calibration change
(±0.005% of range / °C)
Max Crosstalk at DC, 50/60Hz -72dB, 1 LSB
Linearity Error (End to End) ±4 LSB max., (±0.1% of full scale)
Monotonic with no missing codes
Output Stability and Repeatability ±2 count after 10 min. warm up (typical)
Output Ripple ±0.1% of full scale
Output Settling Time 0.3ms max., 5µs min. (full scale range)
All Channel Update Rate 1ms
Maximum Continuous Overload Outputs open circuit protected
Field to Logic Side Isolation 1800VAC applied for 1 second (100% tested)
Type of Output Protection Electronically current limited to 20mA or less
Output Signal at Power Up and Power Down 4mA
External DC Power Required 24VDC @ 410mA (includes loop power)
*Meets EMC and Safety requirements. See the D.O.C. for details.