
8 37
The following may be needed in fleet operations. The manual will assume NO in
all cases. If you select YES, you will be asked to input the information or perform
certain checks as requested in each test.
CONFIGURING THE BVA-2100/RYD (Cont.)
To require vehicle ID numbers select
YES. The manual will assume NO.
To require technician numbers select
YES. The manual will assume NO.
To require visual checks select YES.
The manual will assume NO. The visual
checks, when required for a particular test,
will request CHECKS before continuing
such as:
To require a battery serial number before
each battery test select YES. The manual
will assume NO. If YES is selected then
before each battery test the tester will
prompt for a 14 digit alpha-numeric serial
number. This serial number will be printed
near the bottom of the printout along with
the warranty code.
To require battery date code select
YES. The manual will assume NO.
Select MARGINAL BATTERY to allow
the test result to be MARGINAL
BATTERY when a battery is close to
being bad or select GOOD OR BAD
ONLY to not allow marginal as a test
result.
--CONFIGURATION--
>REQUIRE VEHICLE
ID NUMBERS? YES
USE +/-
'Y' TO SELECT
--CONFIGURATION--
>REQUIRE TECHNICIAN
NUMBERS? YES
USE +/-
'Y' TO SELECT
--CONFIGURATION--
>REQUIRE VISUAL
CHECKS? YES
USE +/-
'Y' TO SELECT
--CONFIGURATION--
>REQUIRE BATTERY
NUMBERS? NO
USE +/-
'Y' TO SELECT.
--CONFIGURATION--
>USE TEST RESULTS:
MARGINAL BATTERY.
USE +/-
'Y' TO SELECT.
--CONFIGURATION--
>REQUIRE BATTERY
DATE CODES? NO
USE +/-
'Y' TO SELECT.
When inputting numbers when required in each test, there will be a set of 0000. Use
the (UP) or (Down) key to select the desired number for the rst zero then press
(ENTER) to advance to the next 02000.
INSPECT BELT CONDITION – TENSION
INSPECT CABLES AND ALTERNATOR OUTPUT
INSPECT BATTERY FOR DIRT, LEAKS OR CRACKS
INSPECT POSTS AND CONNECTIONS
The date code has a letter for the
month (A to M) and 01/00 for the day
and the year. You have to increment
each of these to the desired date that
will print out in the standard 00/00
format.
Charging
Cables
TEST SYSTEM PASS/FAIL
12 Volt Maximum drop at rated alternator output is 0.5 Volts
Maximum drop at rated alternator output is 1.0 Volts
Maximum drop at 500 Amps is 0.5 Volts
Maximum drop at 250 Amps is 1.0 Volts
Maximum drop at 80 Amps is 1.0 Volts
Maximum drop at 40 Amps is 2.0 Volts
Reports the drops at the entered current
Reports the drops at the entered current
24 Volt
12 Volt
24 Volt
12 Volt
24 Volt
12 Volt
24 Volt
Main
Starting
Cables
Magnetic
Circuit
Straight
Drive
Maximum drop at 300 Amps is 1.0 Volts
Maximum drop at 225 Amps is 2.0 Volts
12 Volt
24 Volt
Magnetic
Circuit
Gear
Reduction
Generic
Voltage
Drop Test
DEFINITIONS - SYSTEM SPECIFICATIONS
VOLTAGE DROP TESTS
The specications for those tests are listed below.
The minimum system voltage to run a test is 12.25 Volts for a 12 Volt
system and 24.5 Volts for a 24 Volt system.
During each battery test the BVA-2100/RYD uses various results that are
displayed after each test. The denition of those results are as follows:
• % Charge = an approximate amount of charge the battery is
currently holding. This is based upon the batteries voltage.
• Est. CCA = is the approximate CCA of the fully charged battery.
• GOOD BATTERY = a battery that is good and is charged.
• GOOD NEEDS CHARGE = a battery that is good but is low on
charge.
• MARGINAL BATTERY = a battery that has passed the load
test but the estimated CCA is getting low or the battery is
approaching its end of life.
• CHARGE and RETEST = a battery with insufcient charge to
provide accurate test results.
• BAD BATTERY = a battery that is bad and should be replaced.
A bad battery is a battery that failed the load test or had an
estimated CCA below about 70% of the rated value.
BATTERY TEST