
7
Level I Parameters (Table 1)
Level I parameters are identified as those that have an
LED indicator on the front panel. The green indicator
illuminates next to the name of the active control
settings. The end user has access to all of these
parameters. In general, pressing the down arrow (↓)
button displays the Level I Parameters in the following
order:
•Time of Day
•Time of Regen
•Factor A
•Factor B
•Capacity
If you continue to press the down arrow (↓) button, the
parameters startover withTime of Day. Pressingthe up
arrow (↑) button displays the parameters in reverse
order. Refer to Table 1 for a description of these
parameters and the available ranges for each
parameter.
Press the SET button and the far right digit of the
display starts flashing. If you want to change this
number, press the up arrow (↑) button to increase the
number or the down arrow (↓) button to decrease the
number. To skip the number without changing, press
the left arrow (←) button. When you reach the far left
digit, pressing the left arrow (←) button will return you
to the far right digit.
Note: If you press and hold either the up arrow (↑)
button or the down arrow (↓) button for more than one
second, the flashing number will increment or
decrement at the rate of 10 counts per second.
When the number is correct, press the left arrow (←)
button. The far right digit stops flashing and the next
digit to the left starts flashing. You can only change
the flashing number. Continue changing numbers
until you reach the desired setting. Press the SET
button. The numbers stop flashing and the control
accepts the new setting. After approximately 30
seconds, the control starts alternating the display
between Time of Day and Capacity.
Note:If the new setting is not accepted because itwas
outside the allowable range, the old value will be
displayed.
Time of Day
Press the SET button. The display will show the Time
of Day with the minutes digit blinking. If you want to
change this number, press the up arrow (↑) button to
increase the number or the down arrow (↓) button to
decrease the number. To skip the number without
changing, press the left arrow (←) button. The first
number stops flashing and the next number starts
flashing. You can only change the flashing number.
When you have reached the far left digit, pressing the
left arrow (←) button returns you to the far right digit.
Continue changing numbersuntil you each the desired
setting. Press the SET button again to enter the value.
Time of Backwash
The next value displayed is the Time of Backwash. It is
similar to Time of Day programming. It has a default
value of 2:00 a.m. If 2:00 a.m. is acceptable, press the
down arrow (↓) button. If this is not acceptable, press
the SET button and change the numbers. Press the
SET button again to enter the value.
Factor A
Factor A is the next value displayed. The 960F control
usesthisvaluetocalculatethesystemcapacity.Factor
A must be set to 10 (100 for metric units) for the
960F control to accurately calculate system
capacity. The default value is 10 (100 for metric units).
If the Factor A setting is not correct, press the SET
button and change the value. Press the SET button
again to enter the new value.
Factor B
Factor B is the next value displayed. This value is used
by the control to calculate the pause for the refill cycle.
Because the refill cycle is not required for 960F
operation, Factor B should be set to 0.2 (0.1 for metric
units). This is the minimum setting and will cause the
control to skip the refill cycle, thereby shortening the
backwash cycle time. The default value for Factor B is
0.2 (0.1 for metric units). To change Factor B, press the
SET button and change to the correct value. Press the
SET button again to enter the new value.
Capacity
Capacity is the next value displayed and is used by the
960F control in combination with Factor A to determine
the capacity of the filter. The Capacity value should be
set to the actual capacity of the filter expressed as
gallons/100 (cubic meters/10 for metric units).
Example: If the actual filter capacity is 950 gallons,
enter 9.5 for the Capacity setting. The default value for
Capacity is 1.0 (0.1 for metric units). To change the
Capacity setting, press the SET button and adjust the
correct value. Press the SET button again to enter the
new value.
At this time, all of the Level I parameters are
programed.The display will alternate between the Time
of Day and Capacity if no keys are pressed for 30
seconds. The Capacity value displayed is the volume
remaining in gallons (cubic meters for metric) before a
backwash is needed.