enervent eWind Series User manual

12.7.2017
Enervent eWind
Installation instruction
ENG

2
Copyright © Enervent 2017.
Unauthorized copying and lending are prohibited.
Approvals and version history
Revision Date Description of change Approved by
0.0 2016-01-25
1.0 2017-07-12

3Installation instructions
EN
Contents
Approvals and version history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
READ ME FIRST......................................................................................................6
Type plate .......................................................................................................6
Type designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SAFETY .............................................................................................................7
General .........................................................................................................7
Electrical ........................................................................................................7
TERMINOLOGY......................................................................................................8
BEFORE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Selecting installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Pinion, Pingvin, Pingvin XL, Pandion, Pelican, Pegasos and Pegasos XL 9
LTR-2, LTR-3, LTR-4, LTR-6, LTR-7 and LTR-7 XL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
BUILDING THE VENTILATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Insulating ventilation ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ventilation duct insulation examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outside air duct (fresh air duct) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Supply air duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Extract air duct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Exhaust air duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Extractor hood duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installing duct coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Duct coil for uids. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical duct coils. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installing ventilation unit ceiling installation plate (OPTIONAL) 13
Installing geo-cooling equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Option 1 (standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Option 2 ...................................................................................................14
Installing geothermal CHG pre-heating / pre-cooling equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Option 1 ...................................................................................................15
Option 2 ...................................................................................................15
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Preparing for electrical installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
eWind card connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
External sensors ...............................................................................................18
Installing eWind control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing one control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing two control panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing with Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
INSTALLATION ....................................................................................................19
Additional installation materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Installing models Pinion, Pingvin, Pingvin XL, Pandion, Pelican, Pegasos and Pegasos XL 20
Wall installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Ceiling installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Floor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installing models LTR-2, LTR-3, LTR-4, LTR-6, LTR-7 and LTR-7 XL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installing model eWind W. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Draining condensate water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

4
COMMISSIONING .................................................................................................25
Requirements .................................................................................................25
Calibrating airow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Commissioning checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Control system, eWind operating panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Important to know about control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Setting up fan speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Information view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
eWind Info list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Measurements view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
eWind Measurements list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Documenting commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
USING THE EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
General .......................................................................................................30
Fans........................................................................................................... 30
CO (accessory) and humidity boosting of fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fireplace / extractor hood mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Manual boosting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Temperature control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Heat recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cooling recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Heat recovery anti-freezing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Heat recovery eciency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Alarms ........................................................................................................31
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Service reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Filters ......................................................................................................... 32
Filter types ................................................................................................. 32
Replacing lters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fans........................................................................................................... 34
Inspecting ................................................................................................. 34
Cleaning ...................................................................................................34
Heat exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Inspecting ................................................................................................. 34
Cleaning ...................................................................................................34
Replacing heat exchanger belt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TECHNICAL INFORMATION AND ATTACHMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Models with duct coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
CHG Pre-heating and pre-cooling coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
CHG Left-handed coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
CHG Right-handed coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
List of extra equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Models and components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Technical features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pinion right hand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pinion left hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

5Installation instructions
EN
Pingvin right hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Pingvin left hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Pingvin XL right hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Pingvin XL left hand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Pandion.................................................................................................... 54
Pelican.....................................................................................................55
Pegasos....................................................................................................56
LTR 2....................................................................................................... 57
LTR 3....................................................................................................... 58
LTR 4....................................................................................................... 59
LTR 6 25 mm ...............................................................................................60
LTR 6 50 mm ...............................................................................................61
LTR 7....................................................................................................... 62
Wiring digrams ................................................................................................ 63
eWind basic wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
eWind basic wiring diagram Pingvin XL, Pegasos (XL) and LTR-7 (XL) 64
eWind basic external connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
eWind basic internal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
eWind electrical heater ≤ 2kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
eWind electrical heater > 2kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
eWind external electrical heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
eWind electrical pre-heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
eWind extractor hood connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Principal diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
eWind HW .................................................................................................72
eWind CG principle scheme 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
eWind CG principle scheme 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
eWind CG principle scheme 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
eWind CG principle scheme 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
eWind CG principle scheme 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
eWind CG connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
eWind CHG principle scheme ground loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
eWind CHG principle scheme heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
eWind CW principle scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Control Charts.................................................................................................82
eWind control charts component catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
eWind E (ARCTIC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
eWind W Pingvin, Pingvin (XL), LTR-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
eWind W Pandion, Pelican, Pegasos, Pegasos XL, LTR-2, LTR-4, LTR-6, LTR-7, LTR-7 XL 85
eWind E-CG Pingvin XL, Pegasos XL, LTR-3, LTR-7, LTR-7 XL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
eWind E-CG Pandion, Pelican, Pegasos, LTR-4, LTR-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
eWind CHG ................................................................................................ 88
eWind AGH ................................................................................................ 89
Record of measuring air amounts and sound levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
EU declaration of conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Representatives for the products outside of Finland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Quick guide for contractor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

6
READ ME FIRST
This document is intended for everyone involved
in installation of Enervent ventilation units. The
equipment described in this manual must be installed
by skilled persons only, according to the instructions
given in this manual and local law and regulations.
Failure to comply with instructions in this manual voids
the warranty of the equipment, and possibly results in
harm to people or property.
The equipment described in this manual must not be
used by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been
given supervision or instruction concerning use of the
equipment by a person responsible for their safety.
Tables at the end of this manual list:
• Ventilation units introduced in this document
• Components included in the delivery.
NOTE: If your delivery does not include all
the components listed in the Models and
components table at the end of this manual,
check your order and contact your seller or
Enervent before starting installation.
Type plate
The type plate is located near the main power switch or
inside the ventilation unit. Before you start reading,
check the type of the unit from the plate.
Type designation
The type designation contains three parts:
1. The rst part of the type designation indicates the
chassis of the ventilation unit, for instance LTR-3, or
Pandion.
2. The next letters indicate the type of automation
that the ventilation unit is equipped with, in this
case eWind.
3. The next letter of the type designation indicates
the type of supply air heater that the ventilation
unit is equipped with, E= electrical, W= water.
4. The next letters if any, indicate the type of pre-
heater/pre-cooler or supply air cooler, CHG=
Cooling Heating Geo, CG=Cooling Geo.
Example: Pandion eWind-E-CHG.
ilmanvaihtolaite
ventilation unit
TYYPPI/TYPE:
W/ V/ HZ / A:
www.enervent.com
SRJ. NRO/SERIAL NO:
IP 20

7Installation instructions
EN
SAFETY
General
DANGER
DANGER: Before opening the service hatch,
always make sure that the unit’s supply voltage
is switched o.
WARNING
WARNING: In case of malfunction, always nd
out the cause for it before restarting the unit.
WARNING
WARNING: After switching o the unit
power, wait two (2) minutes before starting
maintenance work. Even though the power is
switched o, the fans continue spinning and the
after-heater coil remains hot for some time.
CAUTION
CAUTION: All ventilation units that come with
a water coil must be equipped with dampers to
avoid freezing of the coil during possible power
failure.
Electrical
DANGER
DANGER: Only a qualied electrician may
open the electrical box.
DANGER
DANGER: Follow the local regulations for
electrical installations.
CAUTION
CAUTION: Make sure that the unit is fully
detached from the electrical network before
carrying out voltage tests, insulation resistance
measuring or other electrical work or measuring.
This kind of work can cause damage to sensitive
electronic equipment.
CAUTION
CAUTION: Control equipment used in
ventilation units can cause leakage current.
This can aect the functionality of fault current
protection.
CAUTION
CAUTION: All ventilation units with a control
system must be equipped with over voltage
protection.

8
TERMINOLOGY
Term Explanation
CG, CHG, AGH
CG (Cooling Geo) is cooling of the supply air using brine, which circulates in pipes under ground.
CHG (Cooling Heating Geo) is cooling or pre-heating using brine, which circulates in pipes under
ground.
AGH (Air Ground Heat exchanger) is cooling or pre-heating using air, which ows in ducts under
ground.
after-heating After-heating warms the supply air after the heat recovery wheel. It ensures that the incoming
air is not too cold. After-heating can be realized with either an electrical or water coil. Suitable
temperature for the incoming air is 5°C less than the room temperature if no extra heating of the
room is desired.
click models New ceiling installation method for models Pingvin and Pandion.
eWind Control panel for managing the ventilation unit.
exhaust air (waste air) Air removed from house after-heat recovery.
extract air Outbound air ow from rooms.
Modbus Communication protocol that is used here for communication between ventilation unit and home
automation systems (+ possible accessories).
outside air Outside air supply to ventilation unit.
supply air Inbound air ow to rooms.
%RH Relative humidity percent that is used here for determining whether ventilation should be
boosted to remove excessive humidity.
active cooling Cooling created by a cooling unit included in some ventilation units.
cool recovery In the summer the rotating heat recovery wheel can cool the supply air, if the extract air is cooler
than the outside air. The function is automatic.

9Installation instructions
EN
BEFORE INSTALLATION
Selecting installation location
Before you start installing the ventilation unit, make
sure that the installation location is suitable for the
model you are installing.
Pinion, Pingvin, Pingvin XL, Pandion,
Pelican, Pegasos and Pegasos XL
Installation location:
Unit Installing location
Pinion, Pingvin, Pingvin
XL and Pandion On the wall.
Pinion, Pingvin, Pingvin
XL and Pandion
Hanging from the ceiling.
• Requires ceiling installation
plate, (sold as accessory).
Pandion, Pelican,
Pegasos and Pegasos XL
On the oor
• On a suitable at plane.
Installation space:
Unit Installation space
Pinion, Pingvin, Pingvin
XL, Pandion, Pelican,
Pegasos and Pegasos XL
Warm space (over +5°C).
• We recommend the unit is installed in a technical
space.
• Do not install the unit in spaces with high
temperature and high humidity level.
• In certain conditions these can cause
condensation on the unit’s outer shell.
• Consider the unit noise level when choosing the
installation location.
• If possible, install the unit on a soundproof
wall.
• Do not install the ventilation unit directly
outside a bedroom, since even though the
ventilation unit is quiet, it is never completely
silent.
• Install an insulating plate at the back of the
ventilation unit, or otherwise try to prevent
structure borne noise.
• Soft, foamed plastic sheets are recommended
for this (not included in the delivery).
• Make sure that it is possible to connect the
condensate water drain and water lock.
• Consider the space needed for the condensate
water connection.
• Make sure that you install re shuto valves if the
unit is placed in a separate re area.
• Install wall mounted units on a partition wall rather
than on an exterior wall.
• Consider the unit maintenance tasks when
installing the unit.
• Doors of the unit must be fully opened for
maintenance work.
• Leave minimum 15 mm space surrounding the
ventilation unit to the sides. Otherwise, the
service doors cannot be fully opened.
• Consider the space needed for duct coils (if
included).
LTR-2, LTR-3, LTR-4, LTR-6, LTR-7 and
LTR-7 XL
Installation location:
Unit Installing location
All LTR-2, LTR-3 and
LTR-4
In two positions:
• Maintenance hatch up.
• Maintenance hatch on the side.
Standard LTR-6, LTR-7
units and LTR-7 XL
Maintenance hatch up.
• On request, units can be made
for installation with the hatch
on the side. This must be
mentioned when the unit is
ordered.
LTR-4, LTR-6, LTR-7
and LTR-7 XL
ventilation units
equipped with built in
cooling coil
We recommend to order with the
maintenance hatch to the side.
• This will enable the
condensation formed in the
cooling coil to drain more easily.
Installation space:
Unit Installation space
LTR-2, LTR-3, LTR-4,
LTR-6, LTR-7 and
LTR-7 XL
Either warm or cold space.
• For example in a storage space
or attic.
CAUTION
CAUTION: Do not install any LTR units so that
the maintenance hatch is facing downwards or
so that the unit is standing upright. Always make
sure that one of the condensate water drain is
downwards.

10
• Consult the ventilation planner regarding possible
need for additional insulation of the unit if
mounted in a cold space.
• If you use solid (hard) insulation, make sure
that the insulation does not carry sound to the
frame of the house.
• Do not install the unit in spaces with high
temperature and high humidity level.
• In certain conditions these can cause
condensation on the unit’s outer shell.
• Consider the unit noise level when choosing the
installation location.
• Do not install the ventilation unit directly
outside a bedroom, since even though the
ventilation unit is quiet, it is never completely
silent.
• Set the unit on top of a soundproong 100 mm
insulation.
• Make sure that it is possible to connect the
condensate water drain and water lock.
• Consider the space needed for the condensate
water connection.
• Make sure that you install re shuto valves if the
unit is placed in a separate re area.
• Consider the unit maintenance tasks when
installing the unit.
• Make sure that there is enough space in front
of or above the maintenance hatch:
Unit Free space in front of the hatch
LTR-2 and LTR-3 min. 50 cm
LTR-4 and LTR-6 min. 60 cm
LTR-7 and LTR-7 XL min. 70 cm
• Make sure that the electrical connections can be
easily accessed.
• Take into account the space needed for opening
the maintenance hatch locking latches.
• Consider the space needed for duct coils (if
included).
BUILDING THE VENTILATION
SYSTEM
Designing the ventilation system must be done by a
professional ventilation designer. By following closely
the design plan when building the ventilation system,
you ensure the operation of the whole ventilation
system and customer satisfaction. Use the Enervent
Energy Optimizer calculation program at the Enervent
home page to calculate the performance and estimated
heating/cooling power of a particular ventilation unit.
• Use type-approved factory made materials when
building the ventilation system.
• Use valves that are suitable for mechanical
ventilation.
• Do not cover the outside air grating with mosquito
net.
• This would make it very dicult to keep clean.
• Prevent rain water and snow from entering the
outside air and exhaust air duct.
• Install enough inspection hatches in the
ventilation network to enable cleaning of the
ventilation ducts.
• To make it easier to nd the inspection
hatches, mark their location for example on
the rafters.
• Ventilation systems for dierent re areas must be
separate.
• For example garage is one re area whereas
living quarters are another re area, which
means that they cannot be connected to the
same ventilation system.
• Use an extractor hood with its own fan, above the
stove.
• The extractor hood must have its own extract
duct directly out.
• A motorless extractor hood can be connected
to the ventilation unit only if the ventilation
unit has an extractor hood connection.
• The extractor hood used must be equipped
with a grease lter and a timer controlled ap
that prevents any airow through the extractor
hood when not in use.
• A drying cabinet with its own fan can be indirectly
connected to the outlet valve using the connection
system of the drying cabinet.
• A part of the extract air is taken from the living
space and a part from the drying cabinet.
• The extract air must ow through the valve at
a speed of 12 litres / second minimum.
• Install silencers at least in the supply and extract
ducts.

11Installation instructions
EN
• The amount of silencers must be considered
case by case.
• We recommend that automatically closing
dampers are installed in outside and exhaust air
ducts.
• In case of a power failure, the dampers will
close and block out cold air, preventing any
water coil from freezing.
• If cold air gets into ventilation ducts, it will
create condensate when mixing with warm air.
NOTE: The ventilation ducts must be blanked
o until the ventilation system is taken into use.
This is in order to keep warm air from owing
into the duct. Warm air causes condensation if
it meets cold outside air or surfaces in the duct.
Furthermore the plugging keeps dirt and other
unwanted particles from clogging the system.
Insulating ventilation ducts
Insulate the ventilation ducts appropriately. This is
especially important when the ventilation unit comes
with a cooling functionality.
Ventilation ducts must be thermally insulated to
prevent water from condensing to the inner or external
duct surfaces in any circumstances. Additionally, the air
temperature must not decrease or increase excessively
in the ducts because of external factors. The ventilation
engineer calculates the insulation requirements
depending on the placement of the ducts and the air
temperatures.
Ventilation duct thermal insulation in heating use
Supply air duct from
the ventilation unit to
the supply valve.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
Extract air duct from
the extract valve to
the ventilation unit.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
Ventilation duct thermal insulation in cooling use
Supply air duct from
the ventilation unit
to the supply valve.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C. At least
19mm of cellular rubber insulation
on the duct surface.
Extract air duct from
the extract valve to
the ventilation unit.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
Ventilation duct insulation
examples
NOTE: Sound insulation is not taken into
account in these insulation instructions and
examples.
NOTE: Semi-warm space = +5°C - +15°C. A
semi-warm space refers also to dropped ceilings,
sub-oors, and casings.
Outside air duct (fresh air duct)
Cold spaces
• 100 mm of sheet, mat, or pipe-covering insulation
(plus the blown wool, when used).
Warm/semi-warm spaces, dropped ceilings, sub-
oors, and casings
• Option 1
• 80 mm insulation with vapour-proof external
surface.
• Option 2
• 20 mm of cellular rubber insulation on the
duct surface and 50 mm insulation with
vapour-proof external surface.
The insulation must prevent water vapour from
condensing to the external duct surface and excessive
air temperature rise during summer.
Supply air duct
Cold/semi-warm spaces and also by dropped
ceilings, sub-oors, and casings:
• In standard ventilation the insulation must be
designed and implemented so that the maximum
air temperature change in the duct is less than 1°C.
• For example, 100 mm of sheet, mat, or pipe-
covering insulation can be used (plus the blown
wool, when used).
Warm spaces
• Insulation is not required in standard ventilation.
In heating and cooling use see tables "Ventilation duct
thermal insulation in heating use" on page 11 and
"Ventilation duct thermal insulation in cooling use" on
page 11.

12
Extract air duct
Warm spaces
• Insulation is not required in standard ventilation.
Cold/semi-warm spaces
• In standard ventilation the insulation must be
designed and implemented so that the maximum
air temperature change in the duct is less than 1°C.
• For example, 100 mm of sheet, mat, or pipe-
covering insulation can be used (plus the
blown wool, when used).
In heating and cooling use see tables "Ventilation duct
thermal insulation in heating use" on page 11 and
"Ventilation duct thermal insulation in cooling use" on
page 11.
Exhaust air duct
Cold spaces
• 100 mm of sheet, mat, or pipe-covering insulation.
Warm/semi-warm spaces
• Option 1
• 80 mm insulation with vapour proof external
surface.
• Option 2
• 20 mm of cellular rubber insulation on the
duct surface and 50 mm insulation with
vapour proof external surface.
The insulation must prevent water vapour from
condensing to the external and internal duct surfaces.
Extractor hood duct
• The extractor hood duct must be insulated and
constructed in accordance with local building and
re safety regulations.
Installing duct coils
Duct coils are used in several unit models both as pre-
heaters, after-heaters and coolers. For information what
type of coils are used with your ventilation unit model,
refer to tables listing models with duct coils at the end
of this manual. For correct mounting of duct coils, refer
to the principal diagrams at the end of this manual.
Ventilation unit models equipped with duct coils for
after-heating or cooling (see table "Models with duct
coils" on page 36).
• These coils are installed in the supply air duct (after
the ventilation unit).
Ventilation unit models equipped with pre-heating/pre-
cooling coils (see table "Pre-heating and pre-cooling
coils" on page 37).
• These coils are installed in the outside air duct
(before the ventilation unit).
• Duct coils must be accommodated in the
ventilation ducts.
• There must also be sucient room for
maintenance and draining of condensate water.
NOTE: For more technical details about the
coils, see the technical data table at the end of
this manual.
Duct coil for uids
When installing duct coils:
• Place the duct coil in the supply air duct after the
ventilation unit or in the outside air duct before
the ventilation unit depending on its function.
• Make sure that there is a lter before pre-heater
coils in the outside air duct to prevent dirt from
entering the coil.
• Do not install the coil too close to a fan outlet or a
bend in the ducting.
• This can result in lower eciency.
• Connect the coil so that the system is easy to
empty for maintenance.
• Install duct heaters in a horizontal or a vertical duct
with optional direction of airow.
• To facilitate venting of the coil, the unit
must be tted with the longitudinal tubes
horizontal.
• Install duct coolers in a horizontal duct with airow
in the direction of the arrow.
• Insulate the cooler externally to prevent the
formation of condensation.
• Connect the cooler to a condensate drain
and water trap and tilt it at an angle of 10-15
degrees to the horizontal in the direction of
the drain.
• Insert the coil into standard spiral ducting and
attach it to the ducting with screws.
• Support the weight of the coil.
• Connect the coil with clamping ring
connectors.

13Installation instructions
EN
• Connect the water inlet to the lowest pipe
connector in order to facilitate venting of the coil.
• Consult the principal drawings at the end of
this manual on how to construct the hydronic
circulating system.
• Install a venting valve near the coil or at the
highest point in the system.
• Inspect the duct coil and its connections for leaks
immediately after the system has been lled with
liquid.
• Place the supply air temperature sensor (TE10) in
the duct after the coil.
• Place the water coil return water sensor (TE45)
on the return water pipe of the coil, if the coil is
mounted in the supply air duct.
• Place the outside air temperature sensor (TE01)
in the outside air duct before the coil, if the coil is
mounted in the outside air duct.
• Connect the sensor to the ventilation unit control
circuit board.
• Refer to the electrical schematics at the end of this
manual for correct connections.
Electrical duct coils
NOTE: The heater is designed for insertion
into standard spiral ducting and is xed to the
ducting with screws.
NOTE: The air must ow through the heater in
the direction indicated by the arrow on the side
of the connection box.
To install:
• Install the heater in either horizontal or vertical
ducting.
• The heater must only be tted in ducts that
are made of incombustible and heat-and-cold
resistant material.
• The connection box can be freely placed
facing upwards or sideways to a maximum
angle of 90°.
CAUTION
CAUTION: Do not install the connection box
facing downwards.
• The distance from (to) the heater to (from) a duct
bend, valve, lter, etc., must be at least twice the
duct diameter.
• Otherwise there is a risk that the airow
through the heater will be uneven which can
cause activation of the overheating cut-out.
• Insulate the duct heater in accordance with local
regulations for ventilation ducting.
• Make sure that the insulation is incombustible.
• Do not cover the lid with insulation, since the
rating plate must be visible and the lid must
be removable.
• Do not cover any heatsinks, nor the side of the
connection box where the SCR’s (Triac’s) are
mounted with insulation.
• The duct heater must be accessible for
replacement and inspection.
• Make sure that the distance from the heater metal
casing to any wood or other combustible material
is at least 30 mm.
• Install the duct sensor TE10 (delivered with the
heater) in the duct after the heater, if the heater is
mounted in the supply air duct.
• If the heater is mounted in the outside air duct,
install the temperature sensor (TE01) before
the heater in the outside air duct and connect
the sensor(s) to the ESC control circuit board.
NOTE: We recommend installing a safety switch
for the electric heater.
Installing ventilation unit ceiling
installation plate (OPTIONAL)
NOTE: Ceiling installation plate is separately
sold extra equipment available for ventilation
unit models Pinion, Pingvin, Pingvin XL and
Pandion.
Before installation:
• Make sure that the ceiling is even so that the plate
will be stable and straight when installed.
• The gap between the plate and the back wall must
be at least 10 mm (recommendation) and at least
15 mm between the plate and the side walls.
• The ceiling installation plate top surface must
not be more than 15 mm above the ceiling inner
height.
• Otherwise you will not be able to hook
the ventilation unit front on to the ceiling
installation plate.

14
To install:
1. Prepare the holes in the ceiling for the ventilation
ducts.
2. Attach the plate on the ceiling using screws that
are suitable for the ceiling material.
3. Seal the ceiling installation plate against the
ceiling’s vapor barrier using for example duct tape.
4. Attach the ducts to the ceiling installation plate
with rivets.
• Make sure that there are no gaps between the
insulation and the ducts.
• Consider the unit’s weight when screwing the
plate to the ceiling.
• The ceiling installation plate must be
absolutely rigid.
• Weights for all units are found in the technical
table in the end of this manual.
Installing geo-cooling equipment
If a geothermal heat pump is in use, the cold brine in
the ground loop can be used in the summertime to
cool the incoming air.
The system can be implemented in two ways:
• In a standard delivery, a separate pump is used
(Option 1).
• Alternatively, the brine is circulated through the
geothermal pump (Option 2).
The cooling coil can be either built in the ventilation
unit or it can be a duct coil, depending on the model.
A duct coil is mounted in the supply air duct after the
ventilation device.
Detailed principal charts are found at the end of this
manual.
Option 1 (standard)
A separate pump is used for circulating brine in the
supply air coil.
The delivery includes:
• A relay for starting up the circulation pump for the
ventilation unit’s cooling coil.
• The relay is situated on the unit motherboard
connection DO8.
• A 3-way control valve (Belimo R3) needed for
cooling.
• An actuator (Belimo TR24-SR).
The temperature is controlled using the ventilation
unit’s own automatic control. The ventilation unit
controls the circulation pump and the 3-way valve.The
heat pump is not started up for ventilation cooling.
To install:
1. Install the cooling coil in the supply air duct (in
case of a duct coil).
2. Connect the condense water outlet.
3. Build a separate pump group with valve and
actuator for circulating cool brine adjacent to the
ventilation unit cooling coil.
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
• Follow the principal chart at the end of this
manual.
NOTE: The valve and actuator must be in the
same position when connected. When the valve
is in the open position, the actuator is turned
counter-clockwise before connecting, and
when the valve is closed, the actuator is turned
clockwise before connecting. Figure 1 on page
15 shows the valve and markings on valve
spindle in valve open (cooling/heating on max)
position.
5. Prepare / connect wiring between the ventilation
unit, the geothermal pump and the actuator, as
shown in the connection diagram at the end of
this manual.
Option 2
A geothermal heat pump is used for circulating brine
also in the supply air coil.
The delivery includes:
• A relay for starting up the brine pump.
• The relay is situated on the unit motherboard
connection DO8.
• A 3-way control valve (Termomix D32S) needed for
cooling.
• An actuator (Belimo NRYD24-SR-W + installation
set MS-NRE).
The temperature is controlled using the ventilation
unit’s own automatic control. The ventilation unit
controls the geothermal heat pump and the 3-way
valve.
To install:
1. Install the cooling coil horizontally in the supply air
duct (in case of a duct coil).
2. Isolate a separate loop for the cooling coil.
• Make sure to include the one-way valve.
• Follow the principal chart at the end of this
manual.
3. Connect the condense water outlet.
4. Install the 3-way valve and the actuator in the
ground collector’s piping.

15Installation instructions
EN
• The actuator controls the brine ow to the
cooling coil as needed.
5. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
Figure 1. Valve and actuator open counter-clockwise and
close clockwise. The gure shows the valve and actuator
in the fully open position. Also, shown is the allowed direc-
tion of the liquid ow.
NOTE: The valve and actuator must be in the
same position when connected. When the valve
is in the open position, the actuator is turned
counter-clockwise before connecting, and
when the valve is closed, the actuator is turned
clockwise before connecting. Figure 1 above
shows the valve and markings on valve spindle
in valve open (cooling/heating on max) position.
6. Prepare / connect the wiring between the
ventilation unit, the geothermal pump and the
actuator.
Installing CHG geothermal pre-
heating / pre-cooling equipment
A geothermal pre-heating / pre-cooling coil for
improving the system energy eciency can be installed
in the ventilation system. A duct coil is always used
when a hydronic pre-heating coil is needed. The coil is
installed in the outdoor air duct before the ventilation
unit. The duct or the coil must have a lter to keep dirt
out of the coil.
To avoid freezing the coil, the brine used in the coil
system must meet the local rated temperature value.
• For example in Helsinki, the brine must still
be functional at -26°C whereas in Lapland the
temperature value is -38°C.
It is also possible to use earth to air heat exchangers
(earth tubes) for pre-heating or pre-cooling. The earth
tube must be combined with a normal outside air
duct and a damper that switches the outside air ow
between the earth tube and the normal outside air
duct depending on the actual need for pre-cooling and
pre-heating. The damper can be controlled from the
same relay that controls the circulation pump for the
hydronic pre-cooler / heater.
The CHG pre-heating / pre-cooling system can be built
as a separate system (option 1) or as a part of the geo-
thermal heat system (option 2).
Detailed principal charts are found at the end of this
manual.
Option 1
A ground loop is built for the pre-heating / cooling
coil. To avoid freezing of the system, brine in the
loop must meet the local rated temperature value.
The ventilation unit automatic control regulates the
system’s temperature. The ventilation unit controls the
circulation pump and the 3-way valve.
To install:
1. Install the cooling / heating coil in the outside air
duct.
2. Connect the condense water outlet.
3. Build a separate pump group for circulating cool
brine adjacent to the ventilation unit cooling /
heating coil.
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
5. Prepare / connect wiring between the ventilation
unit, the circulation pump and the actuator.
6. Install and connect the outside air temperature
sensor (TE01) in the outside air duct before the
duct coil.
• Refer to the electrical connection diagrams at
the end of this manual.
Option 2
A separate loop is isolated from the geothermal pump
brine loop for the cooling coil. To avoid freezing the coil,
brine in the loop must meet the local rated temperature
value. In addition to this, a heat exchanger is installed
in the coil system to ensure the functionality of the
geothermal pump. For the pre-heating / pre-cooling
coil to yield any benets there must be some ow in the
collector of the geothermal pump.

16
Temperature is controlled using the ventilation unit’s
own automatic control. The ventilation unit controls the
circulation pump and the 3-way valve.
To install:
1. Install the cooling coil in the outside air duct.
2. Connect the condense water outlet.
3. Build a separate pump group for circulating cool
brine adjacent to the ventilation unit cooling coil.
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
5. Install a heat exchanger in the coil system.
6. Install and connect the outside air temperature
sensor (TE01) in the outside air duct before the
duct coil.
7. Prepare / connect wiring between the ventilation
unit, the geothermal pump and the actuator.
Refer to the electrical connection diagrams at the
end of this manual.
eWind external connections
Connection/Functionality
Location
on eWind
controller card
Voltage/current Cable (example) Wiring outside AHU
AI NTC
TE01 Outside air temperature TE01 3.3VDC Quick connector 5m
cable supplied with AHU
Yes, if pre-heater/
preecooler (CHG/
AGH) or electrical duct
mounted pre-heater
TE10 Supply air temperature TE10 3.3VDC Quick connector 5m
cable supplied with AHU
Yes, if duct heater/
cooler coil
TE45/TE46 Heating/cooling coil
return water temperature
TE45 3.3VDC Quick connector 5m
cable supplied with AHU
Yes, if duct heater/
cooling coil (W/E-CG)
Digital outputs DO Potential free contact
ON/OFF Control for heating DO2 Max 250VAC/50VDC
8A/2A inductive load
MMJ 3x1.5 Yes, if hydronic heating
(W)
ON/OFF Control for dampers DO5 Max 250VAC/50VDC
8A/2A inductive load
MMJ 3x1.5 Yes
A alarm output (NO) (Default)
ON/OFF Control for pre-
heating (CHG/AGH or electrical
pre-heater)
ON/OFF Control for cooling (CG)
DO8 Max 250VAC/50VDC
8A/2A inductive load
MMJ 3x1.5 Yes, except built in pre-
heater coil
Analog inputs AI
%RH or CO2 external transmitter AI1 (user
congurable)
0-10VDC KLM 4x0.8 Yes
Analog Outputs AO
Control voltage for heating AO5 0-10VDC 10mA KLM 2x0.8 Yes, if hydronic heating
(W)
Control voltage for pre-heater /
Control voltage for cooling
(CHG/CG)
AO6 0-10VDC 10mA KLM 2x0.8 Yes, except built in
pre-heater
Digital inputs DI Potential free NO
contact
Emergency stop DI1 (xed) 24VDC KLM 2x0.8 Yes
Manual boost mode DI4 24VDC KLM 2x0.8 Yes
Away mode DI5 24VDC KLM 2x0.8 Yes
Overpressure mode DI6 24VDC KLM 2x0.8 Yes
Miscellaneous connections
Operating panel connectors OP1, OP2 10m cable supplied with
AHU
Yes
Modbus-RTU X26 Instrumentation cable
2x2x0.5
Yes
The functions and accessories listed in the following table may need external wiring or connecting to function:

17Installation instructions
EN
ELECTRICAL CONNECTIONS
DANGER
DANGER: Only an authorized electrician
is allowed to perform electrical work on the
ventilation units.
Refer to the electrical drawings at the end of this
manual.
Preparing for electrical
installations
Before you start the installation, make sure that:
• Appropriate power supply is available for the
ventilation unit.
• At least 30 mA fault current protection is installed.
• Because of this, no other electrical appliances
should be plugged into the same outlet.
• There is appropriate cabling between the unit and
the control panel wall mount.
• The cable must run inside a protective conduit
of at least Ø 20 mm.
• The cable included in the basic delivery is
10m. Optionally a 30 m cable is available.
• The cable heads are type RJ4P4C.
eWind card connections
eWind card connections
NTC sensors
Input Use
TE01 Outdoor temperature measuring TE01.
TE05 Supply air temperature after-heat recovery TE05.
TE10 Supply air temperature TE10
TE32 Exhaust air temperature TE32
TE02 Pre-heated outside air temperature TE02 (CHG/
AGH)
TE45 Return water temperature TE45 (W)
Return water temperature TE46 Option (CG).
Analog inputs AI 0-10V
Analog input AI1 for voltage range 0-10V
Functionality of this input is decided by user. (Parameter
c27)
Input Use
AI1 External CO2 or %RH transmitter
Analog inputs AI7 - AI8 for voltage range 0-5V
Functionality of these inputs are locked by software.
AI7 Extract air humidity RH30
AI8 Extract air temperature TE30
eWind card connections
Analog Outputs AO 0 - 10V
Output Use
AO1 Control voltage for supply fan
AO2 Control voltage for extract fan
AO4 Control voltage for HRW
AO5 Control voltage for heating
AO6 Control voltage for electrical pre-heater. Control
voltage for (CHG). Control voltage for cooler (CG)
Digital outputs DO relays, potential free normally open
contacts.
Output Use
DO2 ON/OFF Control for heating
DO5 ON/OFF Control for dampers
DO8 A/AB alarm output NO (Default)
ON/OFF control for pre-heating (optional)
ON/OFF control for cooling (CG/CHG/AGH)
(optional)
Digital inputs DI (buttons and indications).
Connection to GND only! No voltage allowed to be
connected to digital inputs.
Input Use
DI1 Emergency stop
DI2 External electrical after-heater or pre-heater alarm
DI4 Manual boost
DI5 Away mode. Away mode is active as long as the
input is grounded.
DI6 Fireplace/extractor hood mode. The replace
switch is a momentary push-button switch.
Fireplace mode is active 10 minutes from when
input is grounded. If connected to a changeover
switch, the circuit must be cut for the mode to
reactivate. The extractor hood mode is active
as long as the input is grounded. The selection
between replace mode or extractor hood mode
is done in parameter c12.
DI11 Supply fan tacho input
DI12 Extract fan tacho input
Miscellaneous connections
OP1,
OP2
Operating panel connections for eWind
X26 ModBus RTU
24VDC +24VDC
GND GND

18
External sensors
It is possible that external sensors must be installed
depending on model of ventilation unit.
• The sensor element for duct mounted
temperature, RH and CO2 sensors must be
installed inside the duct.
• Most temperature sensors are supplied with a
readymade 5m long cable.
• RH and CO2 sensors need wiring on site.
To install:
1. Choose the place for the sensor according to the
unit of measurement that is to be measured.
Refer to the control diagram at the end of this
manual.
2. Place the sensor in the duct at a straight segment,
at least 2x the duct Ø before and after any duct
coil, bends or ttings.
3. Drill a suitable hole for the sensor and a rubber
grommet in the duct.
4. Push sensors attached to a cable trough the
rubber grommet so that the sensor element is a
few centimetres inside the duct.
The rubber grommet must be air tight, and tight
enough that the sensor cable cannot slip through
by itself.
• You can use a cable tie to lock the sensor in
place.
5. Install sensors with rigid pipe type sensor elements
through an adjustable ange mounted to the duct.
• Push the sensor element through the ange
and lock in place with a screw at suitable
depth.
• Conduct electrical connections according to
the electrical schematics at the end of this
manual.
• The functions and accessories listed in the
table "eWind external connections" on page
16 may need external wiring or connecting
to function:
• Make sure the cable grommets in the duct and
ventilation unit are absolutely air and water
tight. If in doubt, use an elastic sealer to seal
the grommets.
6. To select a CO2 sensor active the CO2 boosting
function must be selected "on" from parameter
c27.
For more information on electrical connections, see
the control and connection diagrams at the end of this
manual.
Installing eWind control panel
The eWind control panel (see chapter "Control system,
eWind operating panel" on page 26) is installed
in a wall mounted recessed junction box, or using
the supplied surface mounted junction box. One
ventilation unit can be controlled with the maximum of
2 panels.
Installing one control panel
To install:
1. Install the connection cable supplied with the unit.
2. Attach the connection cable to the connector on
the eWind control panel.
3. Install the eWind control panel to the wall junction
box.
4. Attach the connection cable to connector OP1 of
the eWind controller card.
• Make sure the cable grommets in the ventilation
unit are absolutely air and water tight.
• If in doubt, use an elastic sealer to seal the
grommets.
Installing two control panels
If the ventilation unit is controlled with two control
panels, each panel is attached to the eWind controller
card with its own cable.
To install:
1. Install the eWind control panels as instructed
above. Attach the connection cable of the rst
eWind panel to connector OP1 and cable of the
second eWind control panel to connector OP2 of
the eWind controller card.
2. Remove jumper J1 from the eWind controller card.
Installing with Modbus
The ventilation unit can also be controlled via Modbus
connector X26.
Specication of Modbus:
• Modbus address 1 (default)
• Communication standard RS485
• Modbus trac via Modbus connector X26 of
controller card
• Speed 9600, 19200 or 115200 bps
• 8 bit
• No parity or parity.

19Installation instructions
EN
Additional installation materials
Material Description of use
Screws For hanging the rear attachment
bracket and ventilation unit on
the wall (if applicable). Select
the screws according to the wall
material.
Sheet metal screws For attaching the rear attachment
bracket onto the ventilation unit.
Wall mounting box For installing eWind operating
panel.
Cables As specied in chapter "Preparing
for electrical installations" on
page 17.
Duct tape For sealing.
Insulation sheets (soft foamed
plastic)
For preventing structure-borne
noise.
Insulation material (foamed
plastic and/ or wool,
depending on where the unit
will be installed)
For retaining heat and coolness.
Rivets For attaching the ventilation
ducts onto the unit.
Spirit level For making sure that the unit is
level.
Water pipe For connecting duct coils and for
disposing of condensate water.
Water trap For condensate water drain.
Reducing ttings for duct
connections
For tting the ducts in the
ventilation system. NOTE: Always
use reducing ttings, if necessary.
Dampers To keep cold air out.
Silencers To reduce possible noise.
Suitable grommets for duct
mounted sensors
For mounting sensors in the
ducts.
Shut-o valves To facilitate servicing of unit.
Hydronic balancing valves To properly adjust the water ow.
The order of Freeway connector’s pins is marked on the
controller card.
Modbus registers are available on Enervent webpage
www.enervent.
CAUTION
CAUTION: Do not connect the external bus to
the motherboard before the bus is programmed
and compatible with the unit control.
INSTALLATION
NOTE: Before you install the ventilation unit,
make sure that there are no foreign objects in
the ventilation unit and duct system.
• Refer to the model-specic dimensional drawings
in the back of this manual for your specic
ventilation unit type.
• Inspect the order of duct connections to avoid
cross connections.
• Do not start the ventilation unit when it is installed
until the building is taken into use.
• If the ventilation unit is started too early, the
ventilation system can be contaminated by
building dust.
• Make sure that the ventilation unit duct
connections are the same size as the duct.
• Use a circular duct tting to connect the unit
to the duct.
• Insulate the duct all the way to the unit casing.

20
Installing models Pinion, Pingvin,
Pingvin XL, Pandion, Pelican,
Pegasos and Pegasos XL
Wall installation
Pinion, Pingvin, Pingvin XL and Pandion
To prepare:
1. Prepare the holes in the wall.
2. Bring in the ducts through the cross cut in the
vapor barrier to the height to which the unit will
be mounted.
3. Seal the gap between the duct and the vapor
barrier using for example duct tape.
4. Install an insulating plate at the back of the
ventilation unit or otherwise prevent the structure
borne noise.
• Soft foamed plastic sheets are recommended
(not included in the delivery).
5. Install an extra layer of insulation outside the
ventilation unit (for example foamed plastic), if the
unit is installed with its side against exterior wall
or if there is any other reason to suspect that the
outside of the unit will condensate.
• Condensation risk is present in areas where the
climate is cold.
• Installation varies for dierent models.
To install:
1. Install the rear attachment bracket at the desired
height.
2. Lift the unit on the bracket.
NOTE: Remove the heat exchanger before you
lift the unit. This will make the unit much lighter
to handle. Remove or secure the doors so that
they do not open during lifting.
3. Attach the unit to the wall by the upper mounting
lugs.
• Make sure to install the rubber bushings for
the fastening screws. (Pingvin and Pandion
only).
4. Attach the rear attachment bracket to the unit’s
base using sheet metal screws.
NOTE: It is essential for the proper disposal of
condensate water that a Pingvin unit is installed
slightly tilted backwards. This must be veried
using a spirit level.
• Make sure that the ventilation ducts are
insulated according to the instructions in
chapter "Insulating ventilation ducts" on page
11.
5. Make the applicable electrical and plumbing
connections according to the electrical and
principal diagram at the end of this manual.
Ceiling installation
Pinion, Pingvin, Pingvin XL and Pandion
The dimensional drawings for each of the models can
be found at the end of this manual.
To install:
1. Install the installation plate on the ceiling.
2. Install the supplied duct couplings and insulation
rings (Pingvin, Pingvin XL and Pandion), or
insulation sheet (Pinion) on top of the unit.
3. Unscrew the cover of the electrical cabinet.
• Prepare the lead-ins on unit for the cables
coming through the ceiling.
• Leave the electrical cabinet cover open.
4. Guide the unit power cable to run in front of the
hook to keep the cables from squashing between
the unit and the ceiling installation plate.
NOTE: Remove the heat exchanger before you
lift the unit. This will make the unit much lighter
to handle. Remove or secure the doors so that
they do not open during lifting.
• Make sure that there is enough space
underneath the ceiling plate to t the unit.
5. Lift the unit up.
6. Hook the unit to the front side of the ceiling
installation plate.
This manual suits for next models
13
Table of contents
Popular Control System manuals by other brands

CTC Union
CTC Union EcoLogic PRO Installation and maintenance manual

heat-timer
heat-timer Mini-MOD Installation and operation instruction

Centroid
Centroid OAK Install manual

TeeJet Technologies
TeeJet Technologies Dynajet FLEX 7140 INSTALLATION, SETUP AND USER GUIDE

GEA
GEA T.VIS M-20 FDD Operating instruction

REGLOPLAS
REGLOPLAS RT 45 operating instructions

Hitachi
Hitachi PSC-A32MN instruction manual

Leica Geosystems
Leica Geosystems iCON grade iGG Series installation manual

WaterCop
WaterCop SmartConnect owner's manual

Mitsubishi Electric
Mitsubishi Electric M70V Series Connection manual

PRESSCON
PRESSCON LOX user manual

Toshiba
Toshiba BMS-SM1280HTLE Network configuration guide