In the Event of a Fire Alarm
One or several fire detectors or manual call points
in one or several detection zones are signalling a
Fire Alarm.
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
(Display Picture - Example)
Actions to be taken - Operation Mode
1
Follow all precautions described in the
local fire instructions, step by step.
2
To silence the internal buzzer, press the
black Mute Panel button
3
Press
4
Observe the zone(s) in Alarm state on the
display.
If you need to find out more detailed zonal / point
information before investigating the scene(s), follow the
General Procedure, Step 4, a) to e) on the last page of
this folder, How to View Detailed Information.
If not, go directly to step 5.
5
Investigate the scene(s) and carry out the
necessary actions.
6
To silence all alarms, press the red
Silence Alarms button
To manually resound the alarm zones, digit 1
(RESOUND) can be pressed.
When the fire is extinguished and all necessary repair
work is implemented (smoke is exhausted, new glass
replaced in the manual call-points, etc.), the system
should be returned to normal operating mode.
7
Press the green Reset button
If there are points still signalling an alarm after system
reset and no actions are taken, the points will
automatically be reactivated after a predefined timeout.
If you want to disable the point(s) before timeout - for
example, a manual call-point still signalling alarm -,
press
A point can also be reactivated (digit 3) at any time after
the disablement. To reset the system, repeat step 6 and
7.
Step
Interactive Fire Alarm System
Release 3
P-ASAFE-SH/LE, Rev. A, 010531
NOTE: To operate the panel, turn
the key to the left
(Access Level 2).
Fire Alarm with Alarm Delay
A point is sending an alarm signal from a
Delayed Action detection zone (alarm delay is
active).
1*KITCHEN
FIRST DELAYED ACTION MSG 14:40
FIRE ALARMS
19:23
Total: 1
(Display Picture - Example)
Actions to be taken - Operation Mode
1
Follow all precautions described in the
local fire instructions, step by step.
2
To silence the internal buzzer, press the
black Mute Panel button
3
Press
4
Observe the zone(s) in Alarm state on the
display.
If you need to find out more detailed zonal / point
information before investigating the scene(s), follow the
General Procedure, Step 4, a) to e) on the last page of
this folder, How to View Detailed Information.
If not, go directly to step 5.
5
Investigate the scene(s) and carry out the
necessary actions.
6
To Prolong the delay period for the
selected zone, if necessary, press digit 4
(PROLONG DELAY) and investigate the
scene(s).
7
If there is not a fire, the procedure can be
ended by pressing the green Reset button
If there really is a fire, press digit 2
(ACTIVATE) or activate the nearest manual
call-point to activate alarm, implement the
necessary measures, then go to step 8.
8
To silence all alarms, press the red
Silence Alarms button
When the fire is extinguished and all necessary repair
work is implemented (smoke is exhausted, new glass
replaced in the manual call-points, etc.), the system
should be returned to normal operation mode.
9
Press the green Reset button
If there are points still signalling an alarm, the points will
automatically be reactivated after a predefined timeout.
Before timeout, the points can be disabled (Enter). The
points can be reactivated at any time after the
disablement (digit 3).
In the Event of a Fire Warning
A fire detector in one of the detection zones has
entered the Fire Warning state (Prealarm or Early
Warning).
PREALARM
2 CANTEEN
FIRE WARNING
19:23
Total: 1
(Display Picture - Example)
Actions to be taken - Operation Mode
1
Follow all precautions described in the
local fire instructions, step by step.
2
To silence the internal buzzer, press the
black Mute Panel button
3
Press
4
Observe the zone(s) in Fire Warning state.
If you need to find out more detailed zonal / point
information before investigating the scene(s), follow the
General Procedure, Step 4, a) to e) on the last page of
this folder, How to View Detailed Information.
If not, go directly to step 5.
5
Investigate the scene(s) and carry out the
necessary actions.
After the scene(s) are investigated and the necessary
actions are taken, you can accept the Fire Warning(s).
6
To accept the selected Fire Warning,
press digit 4 (ACCEPT FIRE WARNING).
If there are several zones in Fire Warning state, each
one can be accepted in turn. Fire warnings that are
accepted, will no longer blink in the display. This allows
you to see on the screen whether a detection zone in
Fire Warning state is accepted or not.
When the situation is under control, the system should
be returned to normal operation mode.
7
Press the green Reset button
Step Step
In the Event of Faults
A fault is indicated by one of the components
(fire detectors, external equipment or other
faults).
FAULT WARNINGS
19:23
Total: 2
Total: 1
Total: 1
DZ FAULTS
1 OFFICES
OTHER FAULTS
1 LOOP (2)
(Display Picture - Example)
Actions to be taken - Operation Mode
1
Notify service/technical personnel.
2
To silence the internal buzzer, press the
black Mute Panel button
3
Press
4
Observe the Fault Warnings.
If you need to find out more detailed information before
investigating the scene(s), follow the General
Procedure, Step 4, a) to e) on the last page of this
folder, How to View Detailed Information.
If not, go directly to step 5.
5
Investigate the scene(s) and carry out the
necessary actions, i.e. repair the fault(s).
After the scene(s) are investigated and the necessary
actions are taken, you can accept the fault warning(s).
6
If there are several fault warnings, select
the one you want to accept by scrolling
with the arrow buttons, then press
In this example a detection zone includes several points
in fault warning state. Note that other types of faults are
operated differently than what is described in this
example. A FAD in fault warning state, for example, can
be accepted at this stage by pressing Action Digit 3
(ACCEPT FAULT WARNING).
7
To view all points in fault warning state
within the selected zone, press Action
Digit 1 (SHOW POINTS).
8
Select the point, then press
9
To accept the selected point, press digit 3
(ACCEPT FAULT WARNING).
If there are several fault warnings, each one can be
accepted in turn. When the first fault has been accepted
and the message «Successfully Completed» is shown,
the Close button can be pressed to return quickly to the
previous menu where the next fault warning can be
accepted.
Fault warnings that are accepted, will no longer blink in
the display. This allows you to see on the screen
whether a fault warning is accepted or not.
How to Toggle Between Menu
Mode and Operation Mode
You can easily toggle between Menu Mode and
Operation Mode by pressing the Menu Button.
If an alarm condition occurs when you are using Menu Mode,
you have to press the Menu Button to enter Operation Mode
in order to operate the control panel.
If no buttons are pressed when the system is in Menu Mode,
the system will return automatically to Operation Mode after a
short period.
How to View Detailed Info
The SHOW STATUS gives detailed information on
the current status of all conditions, i.e. Alarms,
Faults, Disablements and Detection Zones in Test.
The Show Status menu is the first menu selection in Menu Mode.
SHOW STATUS
1 FIRE ALARMS
2 PRELARMS
3 FAULTS
4 DISABLEMENTS
5 DETECTION ZONES IN TEST
19:23
Detailed zonal information and a list of the points in alarm for the
selected zone can also be accessed directly from Operation Mode.
Follow the general procedure below.
General Procedure - Operation Mode
An event has occured, for example, a Fire Alarm
Condition, and you want to view detailed zonal
information for the selected detection zone(s).
3
Press
4
Observe the zone(s).
Here you can find out detailed zonal / point information
before investigating the scene(s).
a) To select a zone (if several zones), scroll with the
arrow buttons
6
PQR
(up) or
9
YZ
(down)
b) To view detailed zonal information for the selected
zone, press , then to go one step backwards,
press
c) To view points in alarm for the selected zone, press
digit 1 (SHOW POINTS).
d) To go one step backwards, press
e)
To select another zone, follow b) to d), if not go to
step 5.
Step
Step
!
"

This manual suits for next models

2

Other Autronica Fire Alarm manuals

Autronica BS-420 Service manual

Autronica

Autronica BS-420 Service manual

Autronica AutroGuard Multicriteria Protector V-430... Release Note

Autronica

Autronica AutroGuard Multicriteria Protector V-430... Release Note

Autronica Autroprime Service manual

Autronica

Autronica Autroprime Service manual

Autronica AutroSafe BS-3 User manual

Autronica

Autronica AutroSafe BS-3 User manual

Autronica BS-310 System manual

Autronica

Autronica BS-310 System manual

Autronica AutroSafe Self Verify BSL-336 User manual

Autronica

Autronica AutroSafe Self Verify BSL-336 User manual

Autronica BS-310 Service manual

Autronica

Autronica BS-310 Service manual

Autronica BS-200 User manual

Autronica

Autronica BS-200 User manual

Autronica BS-310 System manual

Autronica

Autronica BS-310 System manual

Autronica BSL-330 User manual

Autronica

Autronica BSL-330 User manual

Autronica Autroprime System manual

Autronica

Autronica Autroprime System manual

Popular Fire Alarm manuals by other brands

Apollo 45681-265 installation guide

Apollo

Apollo 45681-265 installation guide

pivotal CurrentLeak Whole Home installation instructions

pivotal

pivotal CurrentLeak Whole Home installation instructions

Simplex 4007ES Panels User & installation manual

Simplex

Simplex 4007ES Panels User & installation manual

Mircom FA-1000 SERIES installation instructions

Mircom

Mircom FA-1000 SERIES installation instructions

DSC PC1500RK installation manual

DSC

DSC PC1500RK installation manual

Global Fire Equipment VALKYRIE AS manual

Global Fire Equipment

Global Fire Equipment VALKYRIE AS manual

hyfire HY5000 Series install guide

hyfire

hyfire HY5000 Series install guide

Siemens MH-5 Series Installation instructions manual

Siemens

Siemens MH-5 Series Installation instructions manual

Myalarm D1256 user guide

Myalarm

Myalarm D1256 user guide

Schrack Seconet Integral MAP Quick user manual

Schrack Seconet

Schrack Seconet Integral MAP Quick user manual

Jade Bird JBE-2100 manual

Jade Bird

Jade Bird JBE-2100 manual

SL SECURI4 Installation, operating,  & maintenance instructions

SL

SL SECURI4 Installation, operating, & maintenance instructions

Honeywell ESSER 804950 Installation instruction

Honeywell

Honeywell ESSER 804950 Installation instruction

Global Fire Equipment ORION EX MINI-REP installation manual

Global Fire Equipment

Global Fire Equipment ORION EX MINI-REP installation manual

Evacuator Defender Wireless Alarm instructions

Evacuator

Evacuator Defender Wireless Alarm instructions

Notifier AFP-300 Programming manual

Notifier

Notifier AFP-300 Programming manual

bolid ShPS-12 Operation manual

bolid

bolid ShPS-12 Operation manual

Wheelock NS4-2415W installation instructions

Wheelock

Wheelock NS4-2415W installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.