AVS Electronics FOGGY 30 User manual

- 31 -
IST0787V3.0
Curtarolo (Padova) Italy
www.avselectronics.com
CERTIFIED QUALITY
SYSTEM
UNI EN ISO 9001:2008
E
N
G
FOG GENERAFOG GENERA
FOG GENERAFOG GENERA
FOG GENERATT
TT
TOROR
OROR
OR
FOGGY 30FOGGY 30
FOGGY 30FOGGY 30
FOGGY 30
FOGGY 50FOGGY 50
FOGGY 50FOGGY 50
FOGGY 50

- 32 -
NOTE: WHERE NOT EXPRESSLY INDICATED, THESE INSTRUCTIONS ARE REFERRED TO ALL MODELS
General information
In a few seconds Foggy is able to create a fog effect that makes it impossible to move within rooms, forcing the ill-
intentionedpersontoimmediatelysearchanescaperoute.Combinedwithanintrusiondetectionsystem,itcompletes
effectiveness of the detection through and “active” protection of the area.
Thecontinual system monitoring alwayskeeps liquid level, boilertemperature, battery status andnetwork presence
under control; Foggy is also equipped with a safety thermostat that deactivates the system in case of overheating.
Harmless to persons and property
The fog created by Foggy is completely harmless and suitable for use in residential, commercial, industrial and
military field of application. It is ideal for protecting property that is sensitive and valuable such as what is found at
jewellers, electronics ands computer stores and warehouses.
Thefog disperses without leavinganyresidue. Intense verifications, carried out atspecialised analysis laboratories,
guarantee the non toxicity of this effect that is also used bylaw enforcement agencies for fire simulations.
Duration of the fog effect
Within at least 10 seconds, Foggy 30 is able to saturate a 100 m³ environment, while Foggy 50, in at least 20
seconds, is able to saturate a 200m³ environment;it will take approximately 20 / 30 minutes to recuperate complete
visibility. In order to obtain a fog effect that lasts over time, it is possible to enable a particular function that activates
a maintenance deployment impulse.
Connections
Foggy can be the natural completion of any installed intrusion detection system. It is pre-set with a series of free
inputs that allow interfacing with any control unit.
Foggyhas an available equippinginput that allows following theon/off status of thecontrol unit in order toguarantee
that it cannot be activated while the system is shut off. Besides this, there is also a double consent that acts as a
guarantee against accidental activation of the fog generator. For example, it is possible to activate the pre-alarm
usingthe relay fromthe intrusion detection controlunit and connectthe actual alarm inputto an autonomous sensor
in the environment protected by Foggy.
Besides these inputs, Foggy includes free contact control outputs dedicated to:
Anti-removal alarm, Liquid level, System disbursing, Technical malfunction with an indication on the display for No
network, Battery level, Battery failure, Pump malfunctioning, Board temperature, Boiler temperature.
FOGGY Fog generator
FOGGY Dimensions
E
N
G
480 mm
165 mm 354 mm
356
264
163
264 mm163 mm
358 mm
165 mm
480 mm
FOGGY 30 FOGGY 50
354 mm

- 33 -
Technical features
The products must be used according to the intended use and in compliance with the rules applicable
to the various plant engineering types.
However,before commissioning theinstalledproducts, the systemmustbe tested inorder to verify its
functioningand compliance withthesafety rules accordingto that indicated byLaw n. 46 dated05/03/
90 and by Standard CEI 79-3.
The equipment must not be exposed to dripping or water sprays and no object full of liquid must be
placed on it.
03YGGOF 05YGGOF
semulovgnirevoC •
•
•
•
³m001:noitavitcafo’’01 ³m002:noitavitcafo’’02 ³m003:noitavitcafo’’03 ³m004otpu:noitavitcaeslupmi+’’01
•
•
•
•
³m002:noitavitcafo’’02 ³m004:noitavitcafo’’04 ³m006:noitavitcafo’’06 ³m0031otpu:noitavitcaeslupmi+’’06
yticapacknaT • ertil1 •ertil5.1
snoitavitcaforebmuN •
•hcae'’01fosnoitavitca05 hcae'’03fosnoitavitca61 •
•hcae'’02fosnoitavitca53 hcae'’02fosnoitavitca53
noitcnuflaicepS • hguorhtnoitavitcaeDdnanoitavitcAtnemeganaM slortnocetomer •hguorhtnoitavitcaeDdnanoitavitcAtnemeganaM slortnocetomer
sresnepsidelbaliavA •
•tejahtiwtnet°09:1.oN )lanoitpo(stnemyolpeddnaselgnatnereffidhtiw3.oN •
•tejahtiwtnet°09:1.oN )lanoitpo(stnemyolpeddnaselgnatnereffidhtiw3.oN
ylppusrewoP • ~V022 •~V022
noitpmusnocgnitaeH • ttaW006 •ttaW0001
noitpmusnocecnanetniaM • ttaW021 •ttaW002
yrettabreffuB • seY •seY
emitgnitaehlaitinI • setunim21 •setunim02
noitavitcanaretfaemitgnitaeH • setunim5fomumixaM •setunim5fomumixaM
CA022tuohtiwnoitarepO krowten •).ces02tnemyolped(gnittesBhtiwruoh1tsaeltA •).ces02tnemyolped(gnittesBhtiwruoh1tsaeltA
)DxHxW(mmnisnoisnemiD • 361x462x853 •561x453x084
thgieW • gK41 •gK22
snoitidnoclatnemnorivnE • lareneg-edisni-IIssalclatnemnorivne •lareneg-edisni-IIssalclatnemnorivne
ytidimuHdnaerutarepmeT • tuobafoytidimuhegarevahtiwC°04+otC°01-morf noitasnednocottcejbustondna%57 •tuobafoytidimuhegarevahtiwC°04+otC°01-morf noitasnednocottcejbustondna%57
rotacidnisutatS • yalpsiddnadelhguorhT •yalpsiddnadelhguorhT
stupnI •
•
•
•
•
·ffo/nometsysmralaswollof:gnimrametsyS ·mrala-erp:mralAyramirP noitavitcatej;mrala:mralayradnoceS kcolblatoT erifoteudkcolB
•
•
•
•
•
·ffo/nometsysmralaswollof:gnimrametsyS ·mrala-erp:mralAyramirP noitavitcatej;mrala:mralayradnoceS kcolblatoT erifoteudkcolB
stuptuO •
•
•
•
ssergorpnitnemyolpeD gnirepmaT leveLdiuqiL :noitcnuflamlacinhceT –levelyrettaB–krowtenoN erutarepmetdraoB-gninoitcnuflampmuP-tluafyrettaB erutarepmetrelioB-
•
•
•
•
ssergorpnitnemyolpeD gnirepmaT leveLdiuqiL :noitcnuflamlacinhceT –levelyrettaB–krowtenoN erutarepmetdraoB-gninoitcnuflampmuP-tluafyrettaB erutarepmetrelioB-
tuptuo=tlov21 • Am05deussitnerrucmumixam,seY •Am05deussitnerrucmumixam,seY
snoitcennoC •
•·sdradnatslasrevinU smetsysSVAotdetacided584SRlaireS •
•·sdradnatslasrevinU smetsysSVAotdetacided584SRlaireS
yromemstnevE • emitdnaetadhtiwdesiromemebnacstneve0001°n •emitdnaetadhtiwdesiromemebnacstneve0001°n
gnimmargorPdnasutatSkcehC •
•noitcennocBSUlacoL )lanoitpoMSGX.domhtiw(pu-laidMSG •
•noitcennocBSUlacoL )lanoitpoMSGX.domhtiw(pu-laidMSG
etadpuerawmriF • CPyb-seY •CPyb-seY
INSTALLATION AND MAINTENANCE MUST BE EXECUTED BY QUALIFIED PERSONNEL
E
N
G

- 34 -
Installation
Foggy can be installed both on the wall and on the ceiling. Its installation is simplified thanks to a support bracket
that the central block of the fog generator is attached to and a pulley (optional KIT MOD.LFT)
that makes a ceiling installation easier.
In order to lessen the aesthetic impact, Foggy can also be installed inside drop ceilings or wall cupboards, as long
assufficient aeration is guaranteedin order todisbursethe heat andasmall opening isleft in correspondence ofthe
nozzle in order to allow the fog spray to come out. In order to achieve this, if necessary, it is possible to use the
extension (optional KIT MOD. PRL10).
In order to achieve optimal per-
formance, it is recommended to
keep FOGGY at a minimum
distance from the objects to be
protected.
min. 35 cm
2.50 m
2.50 m
NO
!!! ATTENTION !!!
For horizontal wall
installation, the nozzle must
bepositionedontheleftside
while for vertical wall must
be positioned on top side.
Based on the type of
installation,keepaminimum
distance of at least 10 cm
from the wall or ceiling.
!!! ATTENTION !!!
Due to the high temperature at which
the fog is disbursed, it is necessary to
respectaminimumsafetydistancefrom
persons or equipment in order to avoid
buns or damage.
YES
min. 10 cm
min. 10 cm
CEILING
WALL
E
N
G

- 35 -
Warnings
For a correct deployment, make sure that there are no obstacles between the FOGGY and the area to protect
FOGGY must be installed installed in a way that guarantees minimum covering of the object to be protected
Install FOGGY in positions where they cannot be reached in order to avoid possible tampering.
During deployment, FOGGY must keep the escape routes visible.
NO
NO
NO
YES
NO
NO
YES
YES
YES Wall
installation
Ceiling
installation
E
N
G

- 36 -
E
N
G
Mounting FOGGY 30
Once the equipment is
unpacked remove the two
M6x10 screws and remove
front cover
Verify that package has been
positioned in the correct direction
before opening the package.
For correct positioning of FOGGY 30 either
atwalloratroof,usethedrillingplansupplied.
Mark the holes according to preferred
installation,keepingas reference the position
of the two big holes for cables passing
Disconnect the cable of the Liquid Sensor from the F. SENSOR in
the management board.
Remove 4 screws M4x6 holding the fluid tank
Remove the tank in order to avoid liquid leakage during the
installations phases.
IST0811V1.1 PIANO FORATURA FOGGY 30
Dimensioni: 358 x 264 mm
ALTO (installazione verticale a parete)
LATO SINISTRO (installazione orizzontale a parete)
PARETE / SOFFITTO/CONTROSOFFITTO : (A)
(A)
(A) (A)
(A) (A)
ASOLE PER GANCI CON OCCHIOLO APERTO
(per ausilio durante installazione - vedi Manuale Installatore) : (B)
(B) (B)
(C)
(C)
FORI PREDISPOSTI PER PASSAGGIO CAVI: (C)
FORARE QUI FORARE QUI
ALTO (installazione verticale a parete)
LATO SINISTRO (installazione orizzontale a parete)
PARETE / SOFFITTO/CONTROSOFFITTO : (A)
(A)
(A) (A)
(B) (B)
FORARE QUI FORARE QUI
To ease the roof installation it is
recommended to plug on the roof
proper hanging hooks to hang the
FOGGY30 by the two special eyelets
indicated in the figure. This simplifies
the wiring and connections before
fixing the device to the roof.

- 37 -
E
N
G
Fixing points
Use fixing plugs rated for 75Kg or more
To made easy the cabling and roof mounting it is possible,
usingappropriate eyelets, to hang theFoggy30 on two hook
fixing plugs
After fixing the equipment to the roof with proper plugs,
rotate the two hooks in order to enhance the placement of
the front cover.

- 38 -
Outdoor connections FOGGY 30
Insert an omnipolar network switch having a minimum distance between the contacts of at least 3 mm in the
electrical installation of the building.
For electric network power supply input, use double insulation cables.
Passing control and
signal cables
Block the cables to
the predefined
fastening points
usingsuitablestrips
Connections to the security system
Network connection
Passing power
supply cables
(1 L - Phase 220V ~
(2) Earthing - Input for
earthing
(3) N - Neutral 220V ~
Block the power supply cable to
the predefined fastening point
using the supplied cable gland
LN
F 3
Input for network power
supplyconnection
Input for connecting to the
activation system
E
N
G

- 39 -
Installation FOGGY 50
Disconnect the cable of the Liquid
Sensor from the F. SENSOR in the ma-
nagement board.
Unhookthe fastening clamp ofthe tank.
Removethe tank inorder to avoidliquid
leakageduring the installations phases.
Use the supplied drilling template for positioning the plate, both on the wall and on the
ceiling. Mark the holes based on the predefined type of installation (wall/ceiling or
drop ceiling).
Whenfasteningthe bracket, use anchors capable ofsupportingaweight
of at least 75 Kg.
Check that the pipes are inserted in the pre-set holes.
The hanging hooks are represented by two couples of screws with
blocking nuts.
Hook the upper pivot and the lower pivot of the Foggy to the specific
plate guide by sliding it sideways.
Both when fixing to the wall and the ceiling, rotate the equipment on the
pivotsinordertoeasilyaccesstheinsideoftheFoggywith the various cables.
1
2
Once the Foggy has
beenremoved from the
packaging, remove the
4 M4x6 type fixing
screwsand remove the
cover.
Verify that package has been
positioned in the correct direction
before opening the package.
The screws are factory mounted and
blocked against their respective nuts
using a special blocking glue.
The installer must carefully
check that these screws and
corresponding nuts are
perfectly blocked before
mounting the equipment
E
N
G

- 40 -
Fixthe equipment to theplate using the
two supplied M5x10 screws
Input for network power
supplyconnection
Input for connecting to the
activation system
Outdoor connections
Insert an omnipolar network switch having a minimum distance between the contacts of at least 3 mm in the
electrical installation of the building.
For electric network power supply input, use double insulation cables.
Network connection
LN
F 3
Passing power
supply cables
(1 L - Phase 220V ~
(2) Earthing - Input for earthing
(3) N - Neutral 220V ~
Block the power supply cable to the predefined
fastening point using the supplied cable gland
Passing control and
signal cables
Block the cables to the predefined fastening
points using suitable strips
This hook is intended to help the installer when mounting the equipment
at roof.The fog generator can temporarily hang from it to easily place
and block the lateral screws.
N.B. never leave the fog generator hanging from the
hook B without blocking it with the lateral screws.
E
N
G

- 41 -
Connection layout
The control contacts ARM, PRIM and SEC can be NC or NO type (configurable using DIP SWITCHES 4, 5 and 6.
The example layout shown in figure refers to stand by functioning with NC control contacts (normally closed, DIP 4,
5 and 6 in ON).
+ A
12 V ARM
T- A + P - P
PRIM + S - S + D - D
SEC DISABLE + F - F
FIRE DA DB
RS485 NO C
FAULT
NC NC CNO NC CNO NC CNO
FLUID SMOKE TAMPER
+-
USCITA
ON / OFF
IMPIANTO +-
USCITA
ALLARME
GENERALE +-
USCITA
ALLARME
DI ZONA
FOGGY
BLOCCO
GENERALE
CENTRALE
D'ALLARME CENTRALE
ANTINCENDIO
+-
ALLARME
GENERALE
INGRESSO
ZONA
TAMPER
TAMPER
4700 ohm 4700 ohm
+-
Adhesive labels
As recommended in the example figure, in proximity of access points to rooms protected by Foggy, locate the ideal
position where the adhesive warning label (supplied), as obliged by European Directive 92/58/EEC, at a minimum
visual distance of 9 metres.
E
N
G
SYSTEM
ON/OFF
OUTPUT
TAMPER
ZONE
INPUT
GENERAL
ALARM
OUTPUT
ZONE
ALARM
OUTPUT ALARM CONTROL
UNIT
FIRE PROTECTION
CONTROL UNIT
GENERAL
ALARM
GENERAL
BLOCK

- 42 -
Board
-BDAD+ .esuerutufrofdevreseR.desutoN
ONCN
C
TLUAF :TLUAFgnillangistuptuoyrailixuA ytefasevitisop ahtiwegatlovfoeerfyaleregnahcxe etavitcatahtseilamonA.ylamonametsysfoesacnietatssegnahctaht,cdV21tayticapacA2 tnaemeraspmalcrofsnoitacidnI.elbat"langisrorrE"ehtnidedulcniesohteratuptuosiht yllamron)CN(egnahcxenommoc)C(:gnitarepoyltcerrocdnaderewopsitahttnempiuqerof tahwsanoossacitamotuasiteserehT.egnahcxenepoyllamron)ON(egnahcxedesolc .sdnetidetavitca
CNON
C
DIULF :LEVELDIULFgnillangistuptuoyrailixuA yticapacahtiwegatlovfoeerfyaleregnahcxe ehtfonoitcennocoN"dna"tuogninnurdiulF"langisotetatssegnahctaht,cdV21taA2fo lanoitarepoyltcerrocdnaderewoproftnaemeraspmalcnosnoitcurtsnI."rosnesleveldiulf nepoyllamron)ON(egnahcxedesolcyllamron)CN(egnahcxenommoc)C(:tnempiuqe .sdneetavitcaottidesuactahwsanoossayllacitamotuasruccoteserehT.egnahcxe
CNON
C
EKOMS :GNISNEPSIDGOFgnillangistuptuoyrailixuA nocinoisnetadorebiloibmacsaèler e
safnièarutaihccerappa'lehceralangesrepotatsidaibmacehc,cdV21aA2idatatrop .aibbeNenoizagorE"id yltcerrocdnaderewoproftnaemeraspmalcnosnoitcurtsnI )ON(egnahcxedesolcyllamron)CN(egnahcxenommoc)C(:tnempiuqelanoitarepo .egnahcxenepoyllamron .enoizagore'lledenimretlaocitamotuanieneivvaonitsirpirlI
CNON
C
R
EPMAT :REPMATgnillangistuptuoyrailixuA A2foyticapachtiwegatlovfoeerfyaleregnahcxe snoitacidnI.tupni"repmaT"ehtfotesffolangisotredronisutatssegnahchcihw,cdV21ta nommoc)C(:lanoitarepoyltcerrocdnaderewopsitahttnempiuqeroftnaemeraspmalcrof siteserehT.egnahcxenepoyllamron)ON(egnahcxedesolcyllamron)CN(egnahcxe sdneetavitcaottidesuactahwsanoossacitamotua .
-
+.SNES.T gniriwyrotcaF.tupnieborperutarepmeT
+
-V21 .Am05tnerrucdesrubsidxaM.esufgnitteser-flesybdetcetorptuptuO .daolrewopwollanretxeelbissopafoesacnirewopsedivorP
Terminal board
RESET
ON
1 2 3 4 5 6 7 8
FAN LED USB
- T.SENS. +
F. SENSORLN
+ A
12 V ARM
T- A + P - P
PRIM + S - S + D - D
SEC DISABLE + F - F
FIRE DA DB
RS485 NO C
FAULT
NC NC CNO NC CNO NC CNO
FLUID SMOKE TAMPER
F 1 F 2
BUZZER
E
N
G

- 43 -
T tupnirepmaT nehwdelbasidsiti;ecnereferevitagenhtiwmhO0074ahtiwdecnalabebtsum ,sesacrehtollani;evitcasiELBASIDlangisehtnehwro,FFOmetsysslangistupniMRAeht .noitavitcaenihcamgofsesuacpmalcsihtgnittesffo etiuq,tuptuoyalerREPMATehtsreggirtsyawlatupnisihtfoecnalabnuehT:ETON .stupnirehtoehtfoetatsdnanoitarugifnocehtmorftrapa
-evitageN
A+A- MRA :metsySFFO/NO ehtsesingocerrewopcdV21fotonroecneserpehthguorht,tahttupnI gnisU.metsysmralaehtfosutatsFFO/NO 4PID rewopehttahterugifnocotelbissopsiti :sutatsFFOmetsysroNOmetsysslangisspmalcehttatneserp :NOmetsyS eht CES,MIRP dna)derugifnocfi( ERIF otderotinomyltnatsnocerastupni
tnemesrubsidgofelbissopehteganam FFOmetsyS stupnifosutatsehtmorfyltnednepednitnemesrubsidgofskcolbti: CES,MIRP
dna ERIF
P+P- MIRP :mralayramirP larenegehtsesingocerrewopcdV21fotonroecneserpehthguorht,tahttupnI ehtfotahtotetanidrobussinoitcnufstI.metsysmralaehtfosutatsmrala MRA dna CES .stupni
gnisU.tinulortnoctfeht-itnaaotdetcennocsituptuomralaehtyllacipyT 5PID otelbissopsiti ehtfosutatsyb-dnatsehtrospmalclangismralalarenegehttarewopfoecneserperugifnoc .metsysmrala
S+S- CES :mralayradnoceS ehtsesingocertirewopcdV21fotonroecneserpehthguorht,tahttupnI .rosnesdetacidedehtfosutatsmrala :)FFO9PID(mralA ehtfotahtotetanidrobussinoitcnufsti MRA dna MIRP yllamron;stupni ybdetseretniaeraehtnidenoitisopsitahtrosnescirtemulovdetacidedaotdetcennocsiti noitavitcaenihcambof )NO9PID(cinaP ehtmorftnednepednisinoitcnufsti: MRA dna MIRP yllacipytsiti;stupni
gnisU.ecivedyrebbor-itnanaotdetcennoc 6PID foecneserpehterugifnocotelbissopsiti .rosnessetacidedehtfosutatsyb-dnatsrospmalclangismralaehttarewop
D+D- ELBASID :kcolblatoT .ecivedehtfokcolbetelpmocehtsesuac,tneserprewopcdV21htiw,tahttupnI yltnednepedni,degagneylsuoiverpfI.ecnanetniamtuogniyrracrofelpmaxerofdesueboT ,elihwdetavitcatonsitnemesrubsidgof,stupnisuoiravehtfosutatsdnanoitarugifnocehtmorf .tnemyolpedskcolbyletaidemmiti,ssergorpnisitnemesrubsidfi
F+F- ERIF :eriffoesacnikcolB ebottnempiuqeehtsesuac,tneserprewopcdV21htiw,tahttupnI
ehtsselnudekcolb REPMAT htiwtesffosi MRA ehtfidnadetavitca CES sidnammoc
saderugifnocfidecnalabnu .cinaP masehtsruccotnemyolpedsesachtobnI .e foesacnilangismralaehteviecerotredronitinulortnocnoitcetorperifaotdetcennoceboT .erif
.ROSNES.F gniriwyrotcaF.rosneSdiulFehtfonoitcennoC
NAF esuerutuF
DEL .gniriwyrotcaF.draobdelotnoitcennoC
BSU .erawmrifehtetadpuro/dnayggoFehtmargorpotnoitcennocCP
V052Am005T-1F yramirpremrofsnartehtfonoitcetorP
V052A5F-2F seirettabreffubehtfotuptuoevitisopehtfonoitcetorP
V052A01F-3F tupnikrowtenV022gnitcetorpesuF
TESER rossecorporcimehtteserotesaelerdnasserP
Connectors
Fuses
Buttons
Terminal board
E
N
G

- 44 -
E
N
G
PID HCTIWS NOITPIRCSED TLUAFED
3-2-1 .elbatdetalereeS.emittnemyolpedgofehtgnirugifnocroF FFO
4FFO fotnemeganaM MRA metsysslangissitneserprewophtiw:tupni NO sutatS FFO
NO fotnemeganaM MRA sutatSFFOmetsysslangissitneserprewophtiw:tupni
5FFO fotnemeganaM MIRP :tupni evitca tneserprewophtiw FFO
NO fotnemeganaM MIRP :tupni evitcaton tneserprewophtiw
6FFO fotnemeganaM CES :tupni evitca tneserprewophtiw FFO
NO fotnemeganaM CES :tupni evitcaton tneserprewophtiw
7FFO demratonsimetsysehtnehwdelbasidkcolgnitaehrelioB FFO
NO demratonsimetsysehtnehwdelbanekcolgnitaehrelioB
8FFO noitarepolamroN FFO
NO .noitpircseddetalereeS.etadpuerawmriF
9FFO fotnemeganaM CES mralAyradnoceS:tupni FFO
NO fotnemeganaM CES cinaP:tupni
01 FFO delbasidrezzuB FFO
NO delbanerezzuB
Dip Switch
Firmware update
It is possible to update equipment firmware carrying out the following procedure:
1) Bring DIP 10 to ON to activate buzzer operation
2) Bring DIP 8 to ON
3) Press the RESET button, the buzzer goes off for a few seconds and then shuts off
4) After about ten seconds, as soon as the buzzer goes off again, bring DIP 8 to OFF
5) After approximately 5 seconds press the RESET button again
6) Bring DIP 10 to OFF to silence the buzzer
7) Connect the USB cable between the board and the PC; update using the FWIN software installed on the PC
8) At the end of the update, disconnect the USB cable and press the RESET button
9) Bring DIP 10 to ON to enable buzzer operation
EMITTNEMYOLPEDGOF
03YGGOF 05YGGOF
-ITTES GN PID emittnemyolpeD egarevoC 3mni
mumixaM forebmun stnemyolped emittnemyolpeD egarevoC ³mni
mumixaM forebmun stnemyolped
1 2 3
A FFO FFO FFO tesersitinehwtnemomehtotdetavitcasimralaehttahttnemomehtmorfylsuounitnocsruccotnemyolped:OMED roflufesumuminimehtwolebsllaferutarepmetrelioblitnudetavitcasimralaehtnehwtnemomehtmorfro .gofehtgnitareneg
BFFO FFO NO SDNOCESLAUNITNOC01 ³m001 05tuoba SDNOCESLAUNITNOC02 ³m002 53tuoba
C FFO NO FFO SDNOCESLAUNITNOC02 ³m002 52tuoba SDNOCESLAUNITNOC04 ³m004 71tuoba
D FFO NO NO SDNOCESLAUNITNOC03 ³m003 61tuoba SDNOCESLAUNITNOC06 ³m006 11tuoba
E NO FFO FFO +SDNOCESLAUNITNOC01 ETUNIMDESLUP1 ³m052 02tuoba +SDNOCESLAUNITNOC06 ETUNIMDESLUP1 ³m007 9tuoba
FNO FFO NO +SDNOCESLAUNITNOC01 SETUNIMDESLUP5,2 ³m004 21tuoba
+SDNOCESLAUNITNOC06 SETUNIMDESLUP3 ³m0001 6tuoba
GNO NO FFO +SDNOCESLAUNITNOC06 SETUNIMDESLUP5 ³m0031 5tuoba
HNO NO NO
+SDNOCESLAUNITNOC01 SETUNIMDESLUP5,2 noitammargorpstimrepdnA erawtfosNIWFhtiw
³m004 21tuoba
+SDNOCESLAUNITNOC06 SETUNIMDESLUP7 noitammargorpstimrepdnA erawtfosNIWFhtiw
³m0061 3tuoba
:litnuyB-dnatSnisniameryggoF,elcyctnemyolpedehtfodneehttA levelotnrutertonseoderutarepmeteht-
- tesertonseodtnemyolpeddetarenegtahtmralaeht sreggatstierehwecneuqesdeslupastratsyggoF,emittes-erpehtrofylsuounitnocgofehtgnitarenegretfa,HdnaG,F,EsgnittesnI sdnoces02tuobafosesuapotsdnoces5tuobafostnemyolped

- 45 -
12
3 4
5
Remote controls
Foggy handles a maximum of 16 remote controls and for each remote control it is possible to singularly enable the
4 combined functions described below:
Key 1: Activates smoke dispensation (with system entered by Key 2 or by ARM inlet).
•Functioning in demo mode (the activation lasts 60")
•Functioning in normal mode (impulsive control).
Key 2: Deactivates smoke dispensation (impulsive control)
Key 3: System insertion (impulsive control), as by ARM inlet imbalance.
Ifthe system results to bealreadyactivated by the imbalance oftheARM inlet, the commands
sum up, in this case, to deactivate the system, it is necessary to balance the ARM inlet and
deactivate throughkey4of theremotecontrol. Incase of lack orpowersupply or board reset,
the eventual previous activation through Key 3 is maintained.
Key 4: Deactivate the activation executed by Key 3 of the remote control (impulsive control).
Operation:
During normal system operation, the reception of a command executed by the remote control is signaled on the
display through a symbol made of three horizontal dashes followed by the number of the pressed key.
Only the acquired key can control the associated function and be seen on the display.
The function is carried out in the same moment of the reception of the command, while the display view happens in
sequence to the other eventually already present messages.
Remote controls acquisition:
1. Bring DIP 10 to ON to activate the buzzer and bring DIP 8 to ON to activate remote controls programming mode
2. For each remote control to acquire, configure the address through the dip switches on board and press the keys
relative to the functions one wishes to activate in sequence.
3. The successful acquisition is shown on the display through two horizontal dashes followed by the remote control
number, 0 to 9 for the first ten and A, B,C,D,E,F for remote controls 10 to 16.
4. Repeat step 2 for all the remote controls to acquire
5. Bring DIP 8 to OFF to exit programming mode and act on DIP 10 according to buzzer operation needs.
NOTE: Single keys of the remote control may also be acquired at different times.
Deletion:
1. Bring DIP 10 to ON to activate the buzzer and bring DIP 8 to ON to activate remote controls programming mode
2. Press key 5 and keep it pressed, in sequence press key 4. The buzzer will emit a brief confirmation sound.
3. Release keys 4 and 5.
4. As soon as the buzzer begins to sound again, press key 5 and keep it pressed, press key 4 in sequence. The
buzzer will deactivate and the display will show two horizontal dashes as confirmation of successful deletion.
5. If the procedure described in the previous step is not executed, the buzzer will nevertheless stop sounding after
a few seconds and deletion will not occur. In this case repeat the operation from step 2.
6. Bring DIP 8 to OFF to exit programming mode and act on DIP 10 according to buzzer operation needs.
NOTE: It is not possible to delete the single remote control nor the enabling of a single key.
ATTENTION: DIP 8 in ON also enables the firmware update procedure, therefore avoid executing a board reset
while in remote controls programming mode.
E
N
G

- 46 -
XGSM
Using the XGSM module (optional) it is possible to send commends and receive status information from the FOGGY via SMS
messages (from version 2.0), in addition it is possible to remotely interact with the equipment to monitor the status and to
change some functionning parameters
Technical characteristics
Installation
a) Remove power from FOGGY equipment, mains and battery
b) Place the plastic holders into the square holes of the PCB with the rails to the inner side
c) Insert the XGSM module in the connector sliding it inside the two rails all the way long
d) Open the antenna hole in the enclosure
e) Pass the antenna cable through the hole
f) Insert the antenna and block the nut
g) Connect the antenna cable to the XGSM module connector
h) Power up the FOGGY
SIM card inclusion / Antenna connector
To place the SIM card:
1. Open the SIM card holder
2. Insert the SIM card in the correct position following the mark on the receptacle
3. Click close the SIM card holder
Events transmission with SMS messages
FOGGY can be programmed to transmit specific SMS messages corresponding to events occurring in the system
Control via SMS messages
It is possible to cause the execution of commands in FOGGY sending opportune SMS messages.
The command messages are accepted if the following conditions are fulfilled:
•The originating telephone number is recognized and enabled
•The syntax is correct
NOTE: The System status request returns also the prepaid credit of the
SIM card still available
The sending of a command is followed by a text message of state relating to
thecontrolled,even ifthe telephone numberis not associatedwith thereception
events
snoitcennoclanretxE • rotcennoceludomMSG
srebmunenohpeleT • 6
egatlovylppuS • =V21lanimoN
noitpmusnoctnerruC •
•Am05ybdnatS Am004noissimsnarT
snoitidnoclatnemnorivnE • %59ytidimuh-C°55+/C°01-:erutarepmeT
snoisnemiD • mm06x51x39
noitaralceD • saevitceridCE/50/99ETT&RehtotmrofnocsidesueludommSGehT rerutcafunamehtybderalced
Sim Card
position
Antenna
Connector
Input
Disable the PIN code of the SIM card
Disable all the call transferring functions
Disable autoanswering service
Erase all the SMS messages from the SIM
Before placing or removing the SIM card
please remove power completely
STNEVEDEMROFNI
PUORG TNEVE
GNIMRA • )enohpeletMSGaiv(CTRrobofyeketomer,tupnilanimretmorfgnimrasiddnagnimrA
STLUAF • ,erutarepmetBCPhgih,tluafpmup,detcennocnuyrettab,yrettabwol,rorretnemtsujdalortnocerutarepmeT knatdiulf,rednilycgnitaehfoerutarepmetwol,rednilycgnitaehfoerutarepmethgih,erutarepmetBCPwol detcennoctonBCP
REPMAT • repmatmetsyS
MSG • gniripxeytidilavMIS,tiderctrohS
DIULF • gniripxeytidilavdiulf,diulffolevelwoL
TNEMYOLPED • dnetnemyolpedekoms,tratstnemyolpedekomS
SNIAM • erotser,tluafCAV032sniaM
EPYTEGASSEM XATNYS
gnimra #mra#
gnimrasid #mrasid#
sutatsmetsyS #sutats#
sutatsgnimrA #sutatsgnimra#
sutatstnemyolpeD #sutatsnoissime#
tnemyolpedtratS #noissimenigeb#
tnemyolpedpotS #noissimepots#
The short credit WARNING message is issued when
prepaid credit of the SIM card goes below 8 euros
E
N
G

- 47 -
E
N
G
Signals
DEL
DER -
-:DEMRASID demratonmetsyS
:DEMRA demrametsyS
NEERG -
-
-
:DEMRASID mralafoesacniylppusotelbissopmi-diuqildloc
:GNIHSALF ydaerlasahtifiylnoelbissopsinoitasnepsid,langissihthtiw-erutarepmetdiuqilwol erutarepmetetairporppanidiuqilehthtiwdetrats :DEMRA erutarepmetgnitarepotasireliobehtdnaylralugergnitareposiyggoF
nodaetsnidelangis,ytivitcagnitaehreliobehttondnaerutarepmetehtsetacidnidelehT Hrettelehthtiwyalpsideht
WOLLEY -
-
-
:DEMRASID ylamonaon
:GNIHSALF )trahcseilamonametsySees(seilamonasuoiresnon
:DEMRA )trahcseilamonametsySees(REPMATroseilamonasuoiresroflangis
tnatropmitsomehtsetacidnidelwolleyeht,slangissuoenatlumiseromfoesacnI
YALPSIDDEL
-segassemneewtebdecalpsilobmyssiht,slangissuoenatlumiselpitlumeraerehtfi:rotarapeS
SUTATSTUPMI
A MRA .degagnemetsysmralA-evitcatupni
P MIRP evitcatupni evitcamralalareneG-
S CES evitcamralAcinaPromralaenoZ-evitcatupni
d ELBASID evitcakcolbmetsyslatoT-evitcatupni
F ERIF evitcamralAnoitcetorPeriF-evitcatupni
t REPMAT evitcarepmatmetsyS-evitcatupni
SUTATSRELIOB
H ssergorpnignitaehrelioB:gnitaeH
r tnemylpedekomstratsotydaermetsyS:ydaeR
LANGISRORRE
wolleYdeL
0E ydaetsnO gnissimylppusrewopkrowtenV022
1E ydaetsnO .noitarbilaclortnocerutarepmetnirorrE .dekcolbeblliwgnitaehreliob,langissihtfoecneserpehtnI
2E gnihsalF gnissimrowolyrettaB
3E ydaetsnO gninoitcnuflaMPMUP
4E ydaetsnO tcerroctonerutarepmetBCP
5E ydaetsnO tluafeludomMSG
6E ydaetsnO erutarepmetRELIOBevissecxE
7E ydaetsnO aretfaroylppusrewoptsrifehttadelangissinoitacidnisihT.wolooterutarepmetrelioB roemitdehsilbatse-erpniatrecanihtiwlamronotnrutertonseoderutarepmetehtfinoitasnepsid erutarepmetgnikrowmuminimehtwolebsporderutarepmetreliobehtnehwnoitcnuflamrongnirud .dlohserht .ruccotonlliwnoitasnepsid,langissihtfoecneserpnI
8E gnihsalF detsuahxerowoldiuqiL
9E ydaetsnO detcennoctonsiknatdraC
t repmaT
Battery
During the first installation the 2 12V - 1,2Ah batteries supplied are disconnected.
FOGGY 50
In order to change
the batteries,
remove the
support ring nut
fastenedwiththe4
screws indicated
in figure.
+
FOGGY 30
To replace
the battery
losen the
fastener
indicated in
the figure
Connectthecabletothe
availablepositivepoleof
the battery indicated in
figure.
From this moment
Foggy is powered with
the exception of the
boiler.
FIXING
SCREWS
FASTENING
CLAMP
--
+

- 48 -
E
N
G
ER 190 (1 x 90°) Supplied: this nozzle is the one installed by the manufacturer, it
has a straight spray, uniform and long range.
Dispensers
ER160 (1x60°) Optional: it has a jet tilted 60°, long range; this type of dispenser
nozzle makes it possible to install Foggy in different positions.
ER390 (3x90°) Optional: allows short range dispensing in 3 different directions; it
dividesthe jet intotwo tilted at 30° and one tilted90°. This typeof dispenser allows
installingFoggy and creatinga tent effect protection,for example forprotecting full
length windows.
ER360 (3x60°) Optional: allows dispensing a short range triple jet with the
characteristic of spreading the fog effect uniformly.
Tank
The 1.5 litre tank guarantees autonomy for multiple activations; it is made in steel
and allows recharging the fog fluid (to be carried out by the manufacturer). The
fluid is not under pressure, but it is kept under vacuum, this in order to safeguard
its duration over time, avoiding alteration of chemical characteristics.
Fluidlevelis constantly monitored thanks to adedicatedsensorthatcommunicates
with the electronic board and warns if the level is low.
Installation
a. Connect the tank to the specific coupling.
b. Fix the tankx the tank:
- FOGGY 30: with screws included
- FOGGY 50: with supplied reusable strap
c. Connect the cable of the Liquid Sensor on
the F. SENSOR in the management board.
After carrying out operational tests, it is recommended to replace the tank with one that has not yet
been used in order to guarantee the maximum number of deployments based on the selected type
of operation.
The tank must be regenerated exclusively by AVS Electronics therefore, in order to avoid having an
environment unprotected by Foggy while waiting for a recharge, it is recommended to keep an
emergency tank.
To replace the dispenser, proceed as follows:
• Remove the white Teflon insulating that protects the dispenser
• Remove the nozzle to be replaced with an 11-mm wrench (optional
accessory item KEY ER, code PM11-00004-76)
• Carefully clean the threaded seat in the boiler
•Carefully cover the threadof the dispenserwith high-temperature sealant
to ensure the seal and prevent the nozzle from moving
• Slowly screw the nozzle to be used until it is positioned at the nominal
height (see picture to the right)
• Replace the white Teflon insulating plate
•Testthe dispenser to check the correct directionofthe(Note:ifnecessary,
make small height adjustments without compromising the seal).
Foggy is supplied with dispenser Mod. ER 190 but it is possible to replace it with one of the other models (optional)
described here below:
FOGGY 50
FOGGY 30
2
1

- 49 -
Initial power-up precautions
Check that:
wthe DIP SWITCHES are positioned according to the chosen operational mode.
wconnections related to control inputs keep the equipment in standby status.
wafter connecting the batteries the display must signal “H” (Heating in progress).
wabout 20 minutes after supplying power from the network, the display must signal “r” (Operational).
Note: the alternate “H” and “r” signal on the display occurs in the period when the boiler is heated in order to maintain
operating temperature.
Precautions for the installer
The installer must:
winstall Foggy out of the range of children and animals and in an area that is not accessible to unauthorised persons.
winstall Foggy making sure that escape routes are not blocked while dispensing the fog.
wdo not install Foggy outside or in humid environments.
wcheck Foggy using adeguate controls is there is a fire extinguishing system present in the protected area.
wbefore installing Foggy make sure that there are no local regulations or standards that prohibit its use.
wtrain personnel in charge before hand regarding precautions to be used during regular use and on how to assist, in case of
accidental deployment, other persons that may be in the rooms.
wmust communicate with competent agencies that the device was installed.
wbefore any maintenance intervention on connected safety systems, activate the general block of the Foggy.
wbefore each maintenance intervention on the device, disconnect form the power mains.
wAVS Electronics is not liable for damage caused by an incorrect installation or by improper use of the equipment.
General precautions
wAvoid stopping for long periods of time in fog saturated environments, this may cause an irritation of the mucous membranes
of airways and eyes.
wDo not touch and do not come too close to the dispenser as long as the equipment is in operation in order to avoid burns.
wAvoid positioning flammable material at less than 35 centimetres from the dispenser.
wExclusively use a damp cloth when cleaning the Foggy externally. Do not use water or other liquids.
wIn order to avoid condensation, air out the rooms for a long time after dispensing the fog.
First-aid measures:
wGeneral indications: replace soaked clothing.
wContact with skin: wash thoroughly immediately using water and soap.
wContact with eyes: rinse thoroughly for 15 minutes under running water keeping eyelids open.
wSwallowing: do not swallow the fluid and keep it away from children and animals, if swallowed, rinse mouth immediately and
drink abundant water.
Fire prevention measures:
wSuitable fire extinguishers: nebulised water, dry extinguisher, foam, carbon dioxide.
Note: Water used to for fighting the fire must be disposed of according to local legislation.
Measures in case of accidental leakage:
wPrecautionary measures: one must observe the usual precautionary measures when manipulating chemical substances.
wPrecautional measures: if fluid leaks from the tank onto the ground, it is necessary to remove it immediately form the floor
because, due to its slipperiness, it may cause falls.
wEcological information: do not pour residue into the sewer, more in general, do not disperse into the environment.
wCleaning and collection systems: use absorbent materials such as sand, infusorial earth, acid binders, universal binders,
sawdust. Dispose of according to current local regulations.
E
N
G
Close the cover using the 4 supplied
screws.
Supply power to the network only
after closing the cover.
Before testing or using Foggy, it is
necessarytowaitatleast20minutestoallow
the boiler to reach operating temperature.
Commissioning
FOGGY30 FOGGY50

- 50 -
Special functions
Thanks to the FWIN software, the potential of digital technology can be best exploited from PC.
-FWIN permits:
- Checking:
- system state
- input state
- boiler state
- liquid state
- faults found
- boiler features
- SIM credit
- historical record with 1000 memorized data complete with date and time
- Management:
- setting the test parameters
- programming SIM credit management
- programming liquid management
- programming telephone parameters
- programming remote-control functions
- upgrading firmware (not active in GSM)
Thesefunctionsareactivewithlocal USB connection, i.e.,connecteddirectlyonFOGGYorinGSM phone connection.
Once the management software has been installed, a “New numerical code” must be created in “Client Records”
with indication that this is FOG SYSTEM (FOGGY).
Activation of USB /Telephone connection for viewing and managing the FOGGY
settings
Activation of the USB /Telephone connection for viewing and managing the FOGGY
events record
ActivationoftheUSB/Telephoneconnection for the personalization of the parameters
programmable in FOGGY
To exit the connection
Activation of the FOGGY firmware update procedure
Return to initial display page
To access the connection
Access code: numerical password consisting of 6 figures
Programming code: numerical password consisting of 6 figures
The “Access Code” and the “Programming Code” are automatically transferred at every FOGGY connection via
USB and are then used in the remote connections on GSM line.
E
N
G
Other manuals for FOGGY 30
1
This manual suits for next models
1
Table of contents
Languages:
Other AVS Electronics Portable Generator manuals