Axxeron HESCH HE 5411 User manual

#340411 | Version 1.11
Differential pressure measuring transducer
with limit signal
HE 5411
Operating Instructions
(Translation of Original German version)

2
HE 5411 Operating Instructions
#340411 | version 1.11
Imprint
AXXERON HESCH electronics GmbH
Boschstraße 8
31535 NEUSTADT
GERMANY
Phone: +49 5032 9535-0
Internet: www.hesch-automation.com
Email: [email protected]
Hanover District Court
Commercial Register 111184
VAT.-Id. No. DE813919106
General Management
Werner Brandis
Editor:
AXXERON HESCH electronics GmbH, Documentation Department
Copyrights
© Copyright 2023 AXXERON HESCH electronics GmbH. All rights
reserved. The content including pictures and the design of these operating
instructions are subject to copyright protection and other laws for the
protection of intellectual property. The operating instructions may only be
distributed as a complete document and only with reference to the source.
The modification of the contents of this operating instructions is prohibited.
In addition, this content may not be copied, distributed, modified or made
available to third parties for commercial purposes.

HE 5411 Operating Instructions
#340411 | version 1.11
3
Document history
Date / Version
Description / Author
16.09.2019 / 1.0
First version / Bg
25.09.2019 / 1.1
Chapter 3: Basic accuracy and temperature drift removed for analogue
output; Chapter 8.1: Adaptation of heading; Chapter 8.3: Steps 9 and
10 supplemented; Chapter 9: Note removed / Bg
15.01.2020 / 1.2
Chapter 3: free from silicone, cable diameter and mean times (MTBF,
MTTF) added
Chapter 11: new article number for USB/TTL adapter added / Bg
03.04.2020 / 1.3
Chapter 3: technical data for relay contact added / Bg
14.04.2020 / 1.4
Chapter 3: technical data for relay contact adapted and service
interface added / Bg
12.05.2020 / 1.5
All 24 VDC devices can now be used in EX zone 2 as well, except for
the devices with a measuring range of ±1.25 mbar (Sensirion sensor).
Chapter 6.1 Electrical connections, Relay output (limit value): graphical
explanation
Chapter 8.5 Setting the measuring range: “mbar” changed to
“pressure”.
Bg
21.10.2020 / 1.6
Chapter 9.1 Parameter table: Damping and creep flow suppression
added after software modification
Chapter 10 Error messages: Error E.CAL,
E. Sen. and E.Par added after software modifications / Bg
08.12.2020 / 1.7
Chapter 3 Technical data: sensor with ± 350 mbar measuring range
added / Bg
08.06.2022 / 1.8
Optional electrical connections via M12 connector for 24 V DC devices:
chapter 6.1.1 added / Bg
22.11.2022 / 1.9
Chapter 7 Display and Operating elements, chapter 10 Error
messages: blinking green LED in case of wrong or faulty voltage
supply added / Bg
08.03.2023 / 1.10
Validity of operating instructions for ATEX and Non-ATEX devices. / Bg
14.04.2023 / 1.11
HE 5411 Premium 19…36 V DC not for EX zone 2 / Bg

4
HE 5411 Operating Instructions
#340411 | version 1.11
TABLE OF CONTENTS
1LEGAL PROVISIONS................................................................................................................................... 5
2SAFETY INFORMATION ............................................................................................................................. 6
2.1 SYMBOLS AND BASIC SAFETY INSTRUCTIONS...................................................................................................... 6
2.2 SIGNAL WORDS ........................................................................................................................................... 6
2.3 SAFETY IN THE INDIVIDUAL OPERATING PHASES................................................................................................... 7
2.4 SPECIAL REGULATIONS................................................................................................................................... 8
2.5 DEVICE IDENTIFICATION................................................................................................................................. 9
3TECHNICAL DATA.................................................................................................................................... 11
4MOUNTING ............................................................................................................................................ 14
4.1 DIMENSIONS ............................................................................................................................................. 14
4.2 OPENING THE DEVICE.................................................................................................................................. 15
4.3 MOUNTING THE DEVICE............................................................................................................................... 16
5DEVICE DESCRIPTION.............................................................................................................................. 17
5.1 OVERVIEW OF DEVICE VERSIONS.................................................................................................................... 17
5.1.1 HE 5411 Lite / Basic / Premium (with limit signal ).................................................................. 17
6ELECTRICAL COMMISSIONING ................................................................................................................ 19
6.1 ELECTRICAL CONNECTIONS ........................................................................................................................... 21
6.1.1 Option: electrical connection via M12 connector (for 24 V DC devices only!)............................... 22
6.2 MOUNTING MEASURING HOSE ONTO PRESSURE CONNECTION ............................................................................. 24
7DISPLAY AND OPERATING ELEMENTS ..................................................................................................... 25
7.1 LIMIT LED (PREMIUM ONLY)........................................................................................................................ 27
7.1.1 “Limit threshold” mode ................................................................................................................. 27
7.1.2 “Limit window” mode.................................................................................................................... 28
8OPERATION ............................................................................................................................................ 29
8.1 OFFSET FOR ZEROING.................................................................................................................................. 29
8.2 OFFSET FOR ZEROING WITH DEVICE KEYPAD (HE 5411 PREMIUM)....................................................................... 30
8.3 LIMIT VALUE PARAMETER SETTING WITH DEVICE KEYPAD (HE 5411 PREMIUM)...................................................... 31
8.4 ANALOGUE OUTPUT SETTING ....................................................................................................................... 32
8.5 SETTING THE MEASURING RANGE................................................................................................................... 32
8.6 TEST MODE .............................................................................................................................................. 33
9PARAMETER SETTING WITH SERVICE PC ................................................................................................. 34
9.1 PARAMETER TABLE..................................................................................................................................... 35
10 ERROR MESSAGES............................................................................................................................... 43
11 ACCESSORIES ...................................................................................................................................... 44
12 MAINTENANCE AND SERVICE.............................................................................................................. 46

HE 5411 Operating Instructions
#340411 | version 1.11
5
1 Legal Provisions
Manufacturer
AXXERON HESCH electronics GmbH, Boschstraße 8, 31535 NEUSTADT, GERMANY
Intended use
The HE 5411 differential pressure measuring transducer is a universal pressure
transducer, mainly used in dedusting industry. It can also be used for measuring
overpressure in clean rooms.
The device can be operated within the operating and environmental conditions
approved in these operating instructions without impairing its safety.
The manufacturer is not liable for improper use and any resulting personal injury or
material damage; the risk is borne solely by the user. Failure to comply with the above
criteria for intended use will result in the expiry of the warranty and liability for the
device.
Note!
The devices are available with as well as without ATEX approval.
Please refer to chapter 5 Device description, to find out which device
version (Lite, Basic, Premium) is approved for which EX zone.
Devices with a measuring range of ± 1.25 mbar, regardless of the
device version, are not ATEX approved!
If you have ordered an ATEX-approved device, you must necessarily
observe the safety instructions for explosion protection, the indication on
the name plate as well as the information in chapter 2.5 Device
Identification.
Personnel qualification
All work on the differential pressure measuring transducer may only be carried out by qualified
electricians with sufficient knowledge in the field of electrical engineering.
Device Safety
The device has been built and tested according to VDE 0411 EN 61010-1 and has left the factory
in a safety-related impeccable condition. The user must observe the mentioned instructions and
warnings in this manual to keep this condition and to ensure a safe operation.
Declaration of conformity
The valid declaration of conformity is available in the download centre of our website
https://www.hesch-automation.com/en/support/download-center/. Click on the tab
Declarations of Conformity to select your device.

6
HE 5411 Operating Instructions
#340411 | version 1.11
2 Safety Information
2.1 Symbols and Basic Safety Instructions
This chapter contains important safety regulations and notes. To protect against personal
injury and material damage, it is necessary to read this chapter carefully before working with
the device.
Symbols used
The following symbols are used in this manual. All safety instructions have a uniform structure.
Personal Injury Warning!
The severity of the danger is indicated by the respective signal word.
Explosive atmosphere warning sign!
High Voltage Warning!
Warning of material damage caused by electrostatic charge!
Property Damage Warning!
Note!
Identifies possible malfunctions and indicates optimum operating
conditions.
2.2 Signal Words
DANGER!
Indicates an imminently hazardous high risk situation, which, if not avoided, will result in death
or serious injury.
WARNING!
Indicates a potentially hazardous medium risk situation, which, if not avoided, could result in
death or serious injury.
CAUTION!
Indicates a hazardous low risk situation, which, if not avoided, could result in minor or
moderate injury.

HE 5411 Operating Instructions
#340411 | version 1.11
7
2.3 Safety in the individual operating phases
When installing the device and during operation, the following safety instructions must be
observed.
Danger of Electrocution!
Before working on the device, switch off all power supplies used. The
electrical cables must be laid according to the respective national
regulations (in Germany VDE 0100). The measuring lines must be laid
separately from the mains leads.
Attention!
The device must never be put into operation despite visible damage.
Warning!
Ensure protection against short-circuiting in the supply circuit.
Attention!
During installation, commissioning, maintenance and troubleshooting,
observe the accident prevention regulations applicable to your system,
e.g. DGUV Regulation 3 "Electrical installations and equipment".
Attention!
Clean dirty contacts with oil-free compressed air or with spirit and a lint-
free cloth.
Warning of material damage caused by electrostatic charge!
Observe the safety measures according to BS EN 61340-51/-3 to avoid
electrostatic discharge!
Power Connection!
The electrical cables must be laid according to the respective national
regulations (in Germany VDE 0100). The measuring lines must be laid
separately from the mains leads.
Attention!
Cables must be inserted professionally into the housing through the cable
glands.

8
HE 5411 Operating Instructions
#340411 | version 1.11
Explosion Prevention! (for ATEX approved devices only!)
HE 5411 Lite, Basic with a supply voltage of 19…36 V DC are suitable
for use in explosion zones 2 and 22, provided that the lid is closed.
HE 5411 Lite, Basic and Premium with a supply voltage of 100…240
V AC as well as Premium with 19…36 V DC are only suitable for use in
explosion zone 22, provided that the lid is closed.
Devices with a measuring range of ± 1.25 mbar (regardless of the
device version) do not have an ATEX certification and must not be used
in potentially explosive areas.
Before opening the device, e.g. for parameter setting, it is absolutely
necessary to ensure that no explosive environmental conditions, such as
formation of dust or gas, exist.
Troubleshooting!
At the beginning of troubleshooting, all possible sources of faults on
additional devices or supply lines (measuring lines, wiring, downstream
devices) should be taken into consideration. If the fault is not found after
checking these points, we recommend sending the device to the supplier.
Decommissioning!
Switch off the power supply on all poles if the device is to be
decommissioned. Secure the device against unintentional operation!
If the device is connected to other devices and / or equipment, the effects
must be considered and appropriate precautions taken before switching
off.
2.4 Special regulations
Note!
Sealing bolts must be applied professionally to cable ducts that are not
used.

HE 5411 Operating Instructions
#340411 | version 1.11
9
2.5 Device Identification
Note!
The HE 5411 is available in three different designs. The corresponding
device identification can be found on the name plate. Devices with a
measuring range of ± 1.25 mbar (regardless of the device version) do not
have an ATEX certification!
Note!
For the 24 V DC devices with M12 connector, the device identifications
below are identical (see chapter 6.1.1 Option: electrical connection via
M12 connector (for 24 V DC devices only!)
HE 5411 Lite
HE 5411 Basic
HE 5411 Premium
The devices are marked as follows:
HE 5411 Lite
19…36 V DC
HE 5411 Basic
19…36 V DC
HE 5411
Premium
19…36 V DC
HE 5411
measuring
range ± 1,25
mbar
With ATEX
__
__
__
Without ATEX
HE 5411 Lite
100…240 V AC
HE 5411 Basic
100…240 V AC
HE 5411
Premium
100…240 V AC
HE 5411
measuring
range ± 1,25
mbar
With ATEX
-
Without ATEX

10
HE 5411 Operating Instructions
#340411 | version 1.11
II3D
Device category:
Use in Zone 22 for dust during normal operation
Ex
Denotes electrical equipment.
Standards of the EN 60079-0ff. series have been applied.
tc
Type of ignition protection:
Protection by housing
IIIC
Explosion group:
conductive dusts
T135°C
Temperature class:
maximum permissible surface temperature
Dc
Device protection level:
Use in Zone 22 for dust
IP65
Protection type:
dust-tight and protected against water jets
II3G
Device category/
Ex. Atmosphere:
Use in Zone 2 for gas during normal operation
Ex
Denotes electrical equipment.
Standards of the EN 60079-0ff. series have been applied.
nR
Type of ignition protection:
Protection by restricted-breathing housing
IIC
Explosion group:
Certified for gases with an ignition power of <60µJ
(e.g. hydrogen)
T4
Temperature class:
maximum permissible surface temperature
(135°C)
Gc
Device protection level:
Use in zone 2 for gas

HE 5411 Operating Instructions
#340411 | version 1.11
11
3 Technical Data
Electric supply
Voltage
19…36 V DC or 100…240 V AC
Power consumption
Max. 2 W
Sensor system
Measuring range
(mbar)
± 1.25, ± 2.5, ± 5, ± 10, ± 25, ± 50, ± 100, ± 350, ± 1000
in accordance with the information on the name plate
Max. differential
pressure
Measuring
range
± 1.25 mbar
< 1 bar
± 2.5 mbar
< 0.35 bar
± 5 mbar
± 10 mbar
± 25 mbar
< 0.5 bar
± 50 mbar
< 1 bar
± 100 mbar
± 350 mbar
< 5 bar
± 1000 mbar
Medium
Air and dry, non-aggressive gases
Measuring system
Thermal
(Bypass
Technology)
Piezoresistive
Piezoresistive
Piezoresistive
Measuring ranges
(mbar)
± 1.25
± 2.5…± 10
± 25…± 100
± 350…± 1000
Basic accuracy
-
± 1.5 % FSO
T = 25 °C
± 1.0 % FSO
T = 25 °C
± 0.5 % FSO
T = 25 °C
Total error
± 3 % FSO
T = -20…85°C
± 2 % FSO
T = 0…60°C
± 1.5 % FSO
T = 0…60°C
± 1.0 % FSO
T = 0…60°C
Pressure connection
Push-in bulkhead fittings for 6 mm hose –outer diameter (4 mm
with reduction, see chapter 11 Accessories)
Input / Output
Analogue output:
0…10 V
0(4)…20 mA
Max. permissible
load
RL ≥1 kΩ
RA ≤500 Ω
Relay output
1 changeover contact 250 VAC, 5 A as limit value relay
Service interface
USB / TTL adapter HE 5851 required (see chapter 11 Accessories)
FSO = Full Scale Output

12
HE 5411 Operating Instructions
#340411 | version 1.11
Housing
Type
Dust-tight polycarbonate housing
Dimensions
113 × 80 × 60 (W × H × D)
113 × 110 × 60 (W × H × D) incl. connection
coupling
Protection type
IP 65
Mounting
Wall-mounted, vertical mounting position
Cable gland
1 × M20 × 1,5 N (for cable diameters 6-12 mm)
with multiple sealing insert for 2 x cables Ø 6
mm
Climatic environmental conditions
Storage
-20°…+60° C
Transport
-20°…+85° C
Operation
-20°…+55° C
In EX zone: -20 °C…+40 °C
Relative air humidity
75% rel. humidity, no condensation
Air and creepage distances
Pollution degree
2
Overvoltage category
II
Material group
IIIa
Rated voltage
< 150 V AC, ≤ 250 V AC
Test voltage (basic insulation):
1250 V AC, 1 min
Test voltage (added insulation):
3000 V AC, 1 min
Power connection
Connection type
-push-in-spring connection
-or optionally via M12 connector (for 24 V DC
devices only)
Wire size
0.2 mm²…1.5 mm²
Flexible wire size
0.2 mm²…1.5 mm²
AWG1wire size / kcmil2
24…16
Flexible wire size with ferrule without
plastic sleeve
0.2 mm²…1.5 mm²
Flexible wire size with ferrule with plastic
sleeve
0.2 mm²…0.75 mm²
Extras
Special characteristics
silicone free3
1
American Wire Gauge
2
Kilo Circular Mils
3
Silicone is not used in the production process.

HE 5411 Operating Instructions
#340411 | version 1.11
13
Mean Time Between Failures
MTBF [a4]
Power supply
19…36 V DC
without limit
signal
Power supply
100…240 V AC
without limit signal
Power supply
19…36 V DC
with limit signal
Power supply
100…240 V AC
with limit signal
Without
display
545
167
-
-
With
display
486
161
431
119
Mean Time to Dangerous Failure
MTTFd[a]
Power supply
19…36 V DC
without limit
signal
Power supply
100…240 V AC
without limit signal
Power supply
19…36 V DC
with limit signal
Power supply
100…240 V AC
with limit signal
Without
display
1090
334
-
-
With
display
972
322
862
238
4
anno

14
HE 5411 Operating Instructions
#340411 | version 1.11
4 Mounting
Note!
If you want to drill the device to the wall, Figure 1 can be used as a
drilling template.
The ambient temperature at the installation point must not exceed the
permissible temperature for nominal use specified in the technical data. The special regulations
for use in EX ATEX Zones must be observed (see chapter 2.3 Safety in the individual operating
phases).
4.1 Dimensions
Back of housing
Scope of Delivery
HE 5411 differential pressure measuring transducer
Operating Instructions
Note!
Upon receipt, check the delivery for completeness and visible defects. In
case of complaint, contact your responsible representative at AXXERON
HESCH electronics GmbH immediately.

HE 5411 Operating Instructions
#340411 | version 1.11
15
4.2 Opening the device
Opening and closing is performed by hinge technology without screws. A slit screwdriver is
required to open the device. The screwdriver must be positioned at the intended position at
the housing lid (see Figure 2).
Note!
Make sure to move the screwdriver to the right to open the hinge (see
Figure 2). If the screwdriver is moved to the left, the housing cover may
be damaged.
The housing lid can be opened to the left up to an angle of 105°.
Optionally, the housing lid can be closed with 4 additional screws (see chapter 11
Accessories) in order to protect it from unauthorised access. For further information, please
contact your service representative of AXXERON HESCH electronics GmbH.
Open the housing lid to the left (figure shows similar device)

16
HE 5411 Operating Instructions
#340411 | version 1.11
4.3 Mounting the device
Note!
If the device is to be drilled to the wall, Figure 1 can be used as drilling
template.
4 screws are required to fasten the device to the wall. (Not included in the scope of delivery!)
Housing bottom
Alternative: Fastening to the wall with wall brackets. (see chapter 11 Accessories)

HE 5411 Operating Instructions
#340411 | version 1.11
17
5 Device description
The differential pressure measuring transducer records the differential, over- and negative
pressure between two pressure inputs, and converts the measurement value into a linear or
square-rooted output signal of 0(4)…20 mA or 0…10 V.
The 4-digit 7-segment display of the Basic and Premium version allows the indication of
negative pressures.
5.1 Overview of device versions
5.1.1 HE 5411 Lite / Basic / Premium (with limit signal )
From left to right: HE 5411 Lite, HE 5411 Basic, HE 5411 Premium
Explosion Prevention! (for ATEX approved devices only!)
HE 5411 Lite, Basic with a supply voltage of 19…36 V DC are suitable
for use in explosion zones 2 and 22, provided that the lid is closed.
HE 5411 Lite, Basic and Premium with a supply voltage of 100…240
V AC as well as Premium with 19…36 V DC are only suitable for use in
explosion zone 22, provided that the lid is closed.
Devices with a measuring range of ± 1.25 mbar (regardless of the
device version) do not have an ATEX certification and must not be used
in potentially explosive areas.
Before opening the device, e.g. for parameter setting, it is absolutely
necessary to ensure that no explosive environmental conditions, such as
formation of dust or gas, exist.

18
HE 5411 Operating Instructions
#340411 | version 1.11
Device versions with 19…36 V DC:
HE 5411 Lite
HE 5411 Basic
HE 5411
Premium
HE 5411
measuring
range ± 1.25
mbar
With ATEX
Zone 2 + 22
Zone 2 + 22
Zone 22
-
Without ATEX
x
x
x
x
Device versions with 100…240 V AC:
HE 5411 Lite
HE 5411 Basic
HE 5411
Premium
HE 5411
measuring
range ± 1.25
mbar
With ATEX
Zone 22
Zone 22
Zone 22
-
Without ATEX
x
x
x
x
Note!
Optionally, all 24 V DC devices are available with an M12 connector
(see chapter 6.1.1 Option: electrical connection via M12 connector (for 24
V DC devices only!)).
The advantage of a device with M12 connector is that it is not necessary
to open the device for electrical commissioning.

HE 5411 Operating Instructions
#340411 | version 1.11
19
6 Electrical Commissioning
Danger of Electrocution!
Electrical installation must only be carried out when the power is
disconnected.
Warning of material damage caused by electrostatic charge!
Observe the safety measures according to DIN EN 61340-51/-3 to avoid
electrostatic discharge!
Property damage due to incorrect voltage supply!
The power supply must correspond to the voltage indicated on the
nameplate.
Explosion Prevention! (for ATEX approved devices only!)
HE 5411 Lite, Basic with a supply voltage of 19…36 V DC are suitable
for use in explosion zones 2 and 22, provided that the lid is closed.
HE 5411 Lite, Basic and Premium with a supply voltage of 100…240
V AC as well as Premium with 19…36 V DC are only suitable for use in
explosion zone 22, provided that the lid is closed.
Devices with a measuring range of ± 1.25 mbar (regardless of the
device version) do not have an ATEX certification and must not be used
in potentially explosive areas.
Before opening the device, e.g. for parameter setting, it is absolutely
necessary to ensure that no explosive environmental conditions, such as
formation of dust or gas, exist.
Note!
Before commissioning, please note the information on the nameplate!
Note!
The cables must be connected professionally to the cable glands.
Note!
The temperature limitations specified for the use of the device must be
complied with before and during operation.

20
HE 5411 Operating Instructions
#340411 | version 1.11
Electrical connections HE 5411 with cable glands
.
A
B
C
+ -
D
Table of contents
Popular Transducer manuals by other brands

MKS
MKS 392 Series User instruction manual

Automationdirect.com
Automationdirect.com AcuAMP ACTS050 Series installation instructions

KEPO
KEPO SMT-9640A specification

Camille Bauer
Camille Bauer 136590 operating instructions

TorqSense
TorqSense SGR530 Series user manual

Thyracont
Thyracont VSP62 operating instructions