
ELECTRIC CONVECTION OVEN OPERATION MANUAL
3
INSTALLATION INSTRUCTIONS
2. CO11-2E: Installation / Mounting 6” Legs
a. After unpacking the unit, remove legs and any
other material from inside the oven.
b. Tilt the bottom oven onto its left side and attach
the two mounting plates to the right underside
using 1/2” bolts and washers and tighten firmly.
Screw the 6” legs into the center holes.
c. Use proper lifting equipment to raise the
unit, and while suspended attach the two left
mounting plates and legs in the same manner.
d. Use the lifting equipment to raise the top oven
to the proper height, and slide it on top of the
bottom oven. Line up the sides and front and
use the supplied stacking brackets, screws
and lock washers to fasten the two ovens in the
back.
3. CO11-E1: Assembly of an Open Rack Stand (see
Sketch “D”)
a. Slightly loosen the (12) 30” leg bolts.
b. Remove (4) inner bolts, (1) from each of the
four legs, place the top right angle underneath
as shown, and tighten these (4) bolts.
c. Insert Open Rack Shelf and tighten into place
with (8) 3/8”-16 screws, washers and nuts.
d. Position Rack Supports and tighten in place
using (4) 5/16”-18 hex nuts and flat washers.
4. COC-E / CO11-E1: Installation Of Casters (Optional)
a. (4) Casters (2) with wheel brakes and the
mounting hardware is packed and included in
the shipment if ordered.
b. Install casters with wheel brakes on the front of
the unit. Note: See sketch D.
c. Install rear legs with casters on the back of
the unit with the restraining plate affixed firmly
between the right rear leg & the bottom of the
appliance as shown on Sketch D.
d. Provide a suitable restraining chain or cable to
securely tether the appliance to the building
structure. The restraining chain or cable should
be of such length, that it will stop movement of
the appliance before there is any strain on the
power supply cable.
Electrical Connections
1. General Instructions
a. A licensed electrician must make electrical
connections.
b. When installed, unit must be electrically
grounded in accordance with the local codes
and/or the latest edition of the National
Electrical Code ANSI/NFPA No. 70 in USA or
Canadian Electrical Code, CSA Standard C22.1,
Part 1 in Canada.
c. Make sure electrical supply corresponds with
that specified on the rating plate.
d. For single phase 2-wire or three phase 3-wire
supplies, the controlling branch circuit is designed
to operate at 208-240 volts AC and is pre-wired at
the factory between L1 and L2 of the field wiring
terminal block (in North America).
e. For three phase 4-wire 230/400 Volts AC
50hz supplies, the controlling branch circuit is
designed to operate at 230 volts AC and is pre-
wired at the factory between L2 and N of the
field wiring terminal block.
f. Only use copper conductors rated at 90°C.
g. All pole disconnect must be provided by the
installer.
h. FOR CE UNITS: The appliance must be
connected by an earthing cable to all other
units in the complete installation and thence to
an independent earth connection in compliance
with EN 60335-1 and/or local codes. If flexible
line cordage is used to connect the equipment,
it should be a minimum of H07RN-F type
conforming to EN60335-1, EN60335-2-42 and/
or local codes.