Bard WL7013B User manual

Manual 2100-428A
Page 1 of 18
WALL MOUNTED
PACKAGE AIR CONDITIONERS
Model
WL7013B
WL7023A
INSTALLATION INSTRUCTIONS
Manual : 2100-428A
Supersedes: 2100-428
File: Volume III Tab 16
Date: 07-25-06
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.

Manual 2100-428A
Page 2 of 18
CONTENTS
Figures
Figure 1 Unit Dimensions...................................... 5
Figure 2 Mounting Instructions.............................. 9
Figure 3 Electric Heat Clearance ........................ 10
Figure 4 Wall Mounting Instructions.....................11
Figure 5 Wall Mounting Instructions.....................11
Figure 6 Common Wall Mounting Installations.... 12
Figure 7 Unit 24V Terminal Board ....................... 14
Figure 8 Fan Blade Setting ................................. 17
Tables
Table 1 Electric Heat Table .................................. 4
Table 2 Electrical Specifications .......................... 6
Table 3 Thermostat Wire Size ........................... 13
Table 4 Wall Thermostat.................................... 13
Table 5 Fan Blade Dimensions.......................... 17
Table 6 Indoor Blower Performance .................. 17
Table 7 Refrigerant Charge ............................... 17
Table 8 Rated CFM and Rated ESP.................. 17
Table 9 Maximum ESP of Operation
Electric Heat Only ................................. 17
Table 10 Pressure Table ...................................... 18
Getting Other Information and Publications 3
Wall Mount General Information
Air Conditioning Wall Mount Model Nomenclature .. 4
Shipping Damage .................................................... 6
General ................................................................ 6
Duct Work.......................................................... 6 & 7
Condensate Drain.................................................... 7
Installation Instructions
Wall Mounting Information....................................... 8
Mounting the Unit .................................................... 8
Wiring – Main Power ............................................. 13
Wiring – Low Voltage Wiring ................................. 13
Start Up
Important Installer Note ......................................... 15
Crankcase Heaters................................................ 15
High Pressure Switch ............................................ 15
Three Phase Scroll Compressor Start Up.............. 15
Service Hints ......................................................... 15
Sequence of Operation.......................................... 15
Compressor Control Module.......................... 15 & 16
Adjustments ........................................................... 16
Phase Monitor ....................................................... 16
Pressure Service Ports.......................................... 16
Troubleshooting
Fan Blade Setting Dimensions .............................. 17
Removal of Fan Shroud......................................... 17
Refrigerant Charge ................................................ 17
Pressure Table....................................................... 18

Manual 2100-428A
Page 3 of 18
Getting Other Information and Publications
These publications can help you install the air conditioner
or heat pump. You can usually find these at your local
library or purchase them directly from the publisher. Be
sure to consult current edition of each standard.
National Electrical Code........................ ANSI/NFPA 70
Standard for the Installation...................
ANSI/NFPA90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ..........................
ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for .............................. ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential................... ACCAManual
D Winter and Summer Air Conditioning and Equipment
Selection
For more information, contact these
publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057

Manual 2100-428A
Page 4 of 18
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE
WL 70 2 3 A 10 B N X X X A
TABLE 1
ELECTRIC HEAT TABLE
sledoM
WK
YLNOA3207LWYLNOB3107LW
1-V0421-V8021-V0421-V802
SPMAHUTBSPMAHUTBSPMAHUTBSPMAHUTB
0.9------------7.12006,037.81030,32
0.016.14031,432.63006,52------------
MODEL NUMBER CONTROL
MODULES
CAPACITY
70 - 6 Ton
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
REVISIONS KW
VENTILATIONOPTIONS
B - Blank-off Plate
FILTEROPTIONS
N - No Filter
COLOROPTIONS
X - Beige(Standard)
1 - White
2 - MesaTan
4 - BuckeyeGray
COILOPTIONS
X - Standard
1 - PhenolicCoated Evaporator
2 - PhenolicCoated Condenser
3 - PhenolicCoated Evaporator
andCondenser
OUTLETOPTIONS
X - Front(Standard)
FEATURE CODE
3 - 3 ton air openings
on 5 ton cabinet

Manual 2100-428A
Page 5 of 18
FIGURE 1
UNITDIMENSIONS

Manual 2100-428A
Page 6 of 18
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
1Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2Based on 75° C copper wire. All Wiring must conform to NEC and all local codes.
3These “minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the
National Electric Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors
must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment
Factors when more than 3 conductors are in a raceway.
TABLE 2
ELECTRICALSPECIFICATIONS
ledoM
TIUCRICELGNIS
detaR &stloV esahP
.oN dleiF rewoP stiucriC
3
muminiM tiucriC yticapmA
1
mumixaM lanretxE roesuF .tkC rekaerB
2
dleiF rewoP eriW eziS
2
dnuorG eriW eziS
Z0A3207LW 01A 1-802/032 1
18495 0606 8
60101
Z0B3107LW 90B 3-802/032 1
16363 0505 8
80101
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
DUCT WORK
All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.
These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.

Manual 2100-428A
Page 7 of 18
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation. Use
insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures 2,
4 & 5 for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wallcavity.
Some installations may not require any return air duct. A
metallic return air grille is required with installations not
requiring a return air duct. The spacing between louvers
on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria may be
used. It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used. Contact distributor or
factory for ordering information. If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base. There are openings in
the unit base for the drain hose to pass through. In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.

Manual 2100-428A
Page 8 of 18
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 1.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight
of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance, but
the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material. If a combustible
wall use a minimum of 30½" x 10½" dimensions for
sizing. However, it is generally recommended that a
1-inch clearance is used for ease of installation and
maintaining the required clearance to combustible
material. The supply air opening would then be
32" x 12". See Figures 2 and 3 for details.
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figure 2.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top
rain flashing is shipped secured to the right side of
the back.
6. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter flat washers on the lag
bolts.
7. Secure rain flashing to wall and caulk across entire
length of top. See Figure 2.
8. For additional mounting rigidity, the return air and
supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum
of 20 inches clearance on left side to allow access to
control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
WARNING
Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained. See Figure 2.

Manual 2100-428A
Page 9 of 18
FIGURE 2
MOUNTINGINSTRUCTIONS

Manual 2100-428A
Page 10 of 18
FIGURE 3
ELECTRICHEATCLEARANCE
WARNING
A minimum of 1/4 inch clearance must be maintained between the
supply air duct and combustible materials. This is required for the
first 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible
material and may result in a fire causing damage, injury or death.
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT
SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.

Manual 2100-428A
Page 11 of 18
SEE UNIT DIMENSIONS, FIGURE 1,
FOR ACTUAL DIMENSIONS
FIGURE 4
WALLMOUNTINGINSTRUCTIONS
FIGURE 5
WALLMOUNTINGINSTRUCTIONS

Manual 2100-428A
Page 12 of 18
FIGURE 6
COMMONWALL MOUNTINGINSTALLATIONS

Manual 2100-428A
Page 13 of 18
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size. Each outdoor unit is marked with a “Minimum
Circuit Ampacity”. This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring muse
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab locate in
the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out. This tab
will now line up with the slot in the door. When shut, a
padlock may be placed through the hole in the tab
preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers. All equipment leaves the
factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
TAP RANGE
240 253 – 216
208 220 – 187
NOTE: The voltage should be measured at the field power
connection point in the unit and while the unit is
operating at full load (maximum amperage
operatingcondition).
Five (5) wires should be run from thermostat subbase to
the 24V terminal board in the unit. A five conductor, 18
gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in
Figure 7:
TABLE 3
THERMOSTAT WIRE SIZE
remrofsnarT AVALFeguaGeriW
mumixaM ecnatsiD teeFnI
553.2
eguag02 eguag81 eguag61 egaug41 egaug21
5406 001 061 052
TABLE 4
WALLTHERMOSTAT
tatsomrehTserutaeFetanimoderP
750-3048 )3511D0225HT(
taeHegats1;looCegats1 elbammargorP-noNcinortcelE revoegnahclaunaMrootuA
850-3048 )1511D0225HT(
taeHegats2;looCegats2 elbammargorP-noNcinortcelE revoegnahclaunaMrootuA
940-3048 )083-39F1(
taeHegats2;looCegats2 cinortcelEelbammargorP revoegnahclaunaMrootuA

Manual 2100-428A
Page 14 of 18
FIGURE 7
UNIT 24V TERMINAL BOARD

Manual 2100-428A
Page 15 of 18
START UP
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil
with a dish washing detergent.
CRANKCASE HEATERS
These units are not provided with crankcase heat. These
units utilize scroll compressors which do not require
crankcase heat in this application.
HIGH PRESSURE SWITCH
The models are supplied with a remote reset high
pressure switch. If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power. Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the
time the equipment is put into service. If improper
rotation is corrected at this time there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse rotation
for several minutes, the compressor’s internal
protector will trip.
All three phase ZR3 compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at
all times. Also, not to needlessly close off supply
and return air registers. This reduces airflow through
the system, which shortens equipment service life as
well as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside
temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.
3. Check all power fuses or circuit breakers to be sure
they are the correct rating.
4. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling
in compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase of constant air circulation. On all 230 volt units
there is a one minute off delay on the blower motor. 460
volt models do not have an off delay.
COMPRESSOR CONTROL MODULE
The compressor control module is standard on the
models covered by this manual. The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.
Adjustable Delay On Make And Break Timer
On initial power up or any time power is interrupted to
the unit, the delay on make period begins, which will be
2 minutes plus 10% of the delay on break setting. When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized. Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.
During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Manual 2100-428A
Page 16 of 18
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor
contactor will de-energize immediately. The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired. If the high pressure switch
opens again in this same operating cycle, the unit will
go into manual lockout condition and the alarm relay
circuit will energize. Recycling the wall thermostat
resets the manual lockout.
Low Pressure Switch, Bypass, and Lockout
Sequence
If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout. Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired. If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.
Alarm Relay Output
Alarm terminal is output connection for applications
where alarm relay is employed. This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.
NOTE: Both high and low pressure switch controls are
inherently automatic reset devices. The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model. The
lockout features, both soft and manual, are a
function of the Compressor Control Module.
ADJUSTMENTS
Adjustable Delay on Make and Delay on Break
Timer
The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes. Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.
Typical Settings for Dual Unit Installation:
Unit 1: DOB set at 2 minutes, and DOM is 132 seconds.
Unit 2: DOB set at 4 minutes, and DOM is 144 seconds.
PHASE MONITOR
All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor
and phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. A pressure table can be found later in the
manual covering all models. It is imperative to match
the correct pressure table to the unit by model number.

Manual 2100-428A
Page 17 of 18
The suction line temperatures in table above are based
upon 80° F dry bulb / 67° F wet bulb (50% R.H.)
temperature and rated airflow across the evaporator
during cooling cycle.
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and
bottom. Nine (9) screws.
4. Unwire condenser fan motor.
FIGURE 8
FAN BLADE SETTING
TROUBLESHOOTING
5. Slide complete motor, fan blade, and shroud assembly
out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit
rating plate. Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6" from compressor) as shown in Table 7.
TABLE 5
ledoM noisnemiD A
07LW52.1
TABLE 6
INDOORBLOWERPERFORMANCE
CFM
@
230V
.P.S.E HnI
2
O
07LW
deepShgiH
lioCyrDlioCteW
0.1.2.
5771 5761 5751
0061 5251 5241
TABLE 8
RATED CFM AND ESP
ledoM detaR MFC detaR PSE dednemmoceR egnaRwolfriA
07LW524102.05241-5771 1
TABLE 9
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Values shown are for units equipped with standard 1"
throwaway filters or 1" washable filters. Derate ESP by
.15 for 2" pleated filters.
SLEDOMPSE
07LW 01A 90B 3.3.
1Rated CFM & ESP on High Speed tap with 14 x 28 return air
filter grille
FAN BLADE SETTING DIMENSIONS
Shown in Figure 8 is the correct fan blade setting
dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.
TABLE 7
REFRIGERANTCHARGE
ledoMwolfriA DO59 erutarepmeT DO28 erutarepmeT
07LW007106-8585-65

Manual 2100-428A
Page 18 of 18
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operating charge being in the system, the charge should be removed, system evacuated and recharged to
serial plate instructions.
COOLING
TABLE 10
PRESSURETABLE
Air Temperature Entering Outdoor Coil °F
ledoM riAnruteR erutarepmeTerusserP5708580959001501011511
A3207LW
BD.ged57 BW.ged26 ediSwoL ediShgiH 86512 86822 96242 07652 17272 27982 37503 47423 57343
BD.ged08 BW.ged76 ediSwoL ediShgiH 37022 37432 47842 57362 67972 77692 87313 97233 08253
BD.ged58 BW.ged27 ediSwoL ediShgiH 67822 67242 77752 87272 97982 08603 18423 28443 38463
B3107LW
BD.ged57 BW.ged26 ediSwoL ediShgiH 26412 36032 46742 56562 66082 76992 86613 96333 07153
BD.ged08 BW.ged76 ediSwoL ediShgiH 76022 86632 96452 07172 17782 27603 37603 37423 57063
BD.ged58 BW.ged27 ediSwoL ediShgiH 27522 37342 47162 57972 67792 77613 87533 97353 08273
This manual suits for next models
1
Table of contents
Other Bard Air Conditioner manuals

Bard
Bard MULTI-TEC W24AAPA User manual

Bard
Bard YA302 User manual

Bard
Bard MULTI-TEC W18AAPA Operating instructions

Bard
Bard Q24A2-A User manual

Bard
Bard WA423 User manual

Bard
Bard H24AA-A User manual

Bard
Bard W3SAC-A User manual

Bard
Bard EHWH02A-A04 User manual

Bard
Bard Q-TEC Q A4D Series User manual

Bard
Bard 11EER WA W18AB-A User guide
Popular Air Conditioner manuals by other brands

Carrier
Carrier 40GJB owner's manual

EcoNet
EcoNet A2024AJVCA installation instructions

Friedrich
Friedrich Chill CP18 Installation and operation manual

Technibel
Technibel MTA8FIA0R5I operating instructions

GE
GE AGE07 Owner's manual and installation instructions

Cruisair
Cruisair Zephyr Installation and operation manual