Baxi Solo WM 30/4 PF User manual

This manual suits for next models

3

Other Baxi Boiler manuals

Baxi Bermuda 553 User guide

Baxi

Baxi Bermuda 553 User guide

Baxi COMBI 424 Manual

Baxi

Baxi COMBI 424 Manual

Baxi Power HT User manual

Baxi

Baxi Power HT User manual

Baxi UB SC 120 Operating and maintenance manual

Baxi

Baxi UB SC 120 Operating and maintenance manual

Baxi Bermuda 45/3 M User guide

Baxi

Baxi Bermuda 45/3 M User guide

Baxi ECOGEN 24/1.0 Release note

Baxi

Baxi ECOGEN 24/1.0 Release note

Baxi Combi 130 HE Operation instructions

Baxi

Baxi Combi 130 HE Operation instructions

Baxi COMBI 424 User manual

Baxi

Baxi COMBI 424 User manual

Baxi 47 075 35 Release note

Baxi

Baxi 47 075 35 Release note

Baxi Maxflow Combi WM User guide

Baxi

Baxi Maxflow Combi WM User guide

Baxi 600 Combi 2 Manual

Baxi

Baxi 600 Combi 2 Manual

Baxi Roca LIDIA GT EM Series User manual

Baxi

Baxi Roca LIDIA GT EM Series User manual

Baxi EcoBlue Advance Heat 13 Manual

Baxi

Baxi EcoBlue Advance Heat 13 Manual

Baxi Sirius FS 90-105-130-160 Instruction manual

Baxi

Baxi Sirius FS 90-105-130-160 Instruction manual

Baxi Maxflow Combi WM Operation instructions

Baxi

Baxi Maxflow Combi WM Operation instructions

Baxi Bioflo Release note

Baxi

Baxi Bioflo Release note

Baxi MainEco Combi 24 Manual

Baxi

Baxi MainEco Combi 24 Manual

Baxi Boston 2 80 OF User guide

Baxi

Baxi Boston 2 80 OF User guide

Baxi Combi 130 HE User guide

Baxi

Baxi Combi 130 HE User guide

Baxi Luna 3 Silver Space 250 FI User manual

Baxi

Baxi Luna 3 Silver Space 250 FI User manual

Baxi Luna 310 Fi User guide

Baxi

Baxi Luna 310 Fi User guide

Baxi 100 He Operation instructions

Baxi

Baxi 100 He Operation instructions

Baxi Nuvola 3 Comfort User manual

Baxi

Baxi Nuvola 3 Comfort User manual

Baxi Fourtech Series User manual

Baxi

Baxi Fourtech Series User manual

Popular Boiler manuals by other brands

IDEAL IMAX XTRA EL 320 user guide

IDEAL

IDEAL IMAX XTRA EL 320 user guide

UTICA BOILERS BC3D Installation, operation & maintenance manual

UTICA BOILERS

UTICA BOILERS BC3D Installation, operation & maintenance manual

Lochinvar SOLUTION 260000 Installation & service manual

Lochinvar

Lochinvar SOLUTION 260000 Installation & service manual

Weil-McLain EG 6 Series manual

Weil-McLain

Weil-McLain EG 6 Series manual

RBI LCD Series Installation & operation manual

RBI

RBI LCD Series Installation & operation manual

Unical ALKON R 24 Installation and Servicing Manual

Unical

Unical ALKON R 24 Installation and Servicing Manual

Automatic Heating Gasogen Installation and Servicing Manual

Automatic Heating

Automatic Heating Gasogen Installation and Servicing Manual

Viessmann VITORADIAL 300-T Type VR3 Service instructions for contractors

Viessmann

Viessmann VITORADIAL 300-T Type VR3 Service instructions for contractors

Alpha GasSaver GS-1 Installation and servicing instructions

Alpha

Alpha GasSaver GS-1 Installation and servicing instructions

Vaillant uniSTOR VIH SW GB 500 BES operating instructions

Vaillant

Vaillant uniSTOR VIH SW GB 500 BES operating instructions

Kärcher HWE 4000 Gas manual

Kärcher

Kärcher HWE 4000 Gas manual

Radijator BIO max 23.1 instruction manual

Radijator

Radijator BIO max 23.1 instruction manual

Granby BKC Installation, operation and maintenance manual

Granby

Granby BKC Installation, operation and maintenance manual

Brunner BSV 20 Instructions for use

Brunner

Brunner BSV 20 Instructions for use

Potterton 50e Installation and Servicing Manual

Potterton

Potterton 50e Installation and Servicing Manual

UTICA BOILERS TriFire Assembly instructions

UTICA BOILERS

UTICA BOILERS TriFire Assembly instructions

ECR International UB90-125 Installation, operation & maintenance manual

ECR International

ECR International UB90-125 Installation, operation & maintenance manual

Froling P4 Pellet 8 - 105 installation instructions

Froling

Froling P4 Pellet 8 - 105 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Supplied by freeboilermanuals.com
BS 5258

BS 6332
Safety & Performance
Baxi heating is one of the leading manufacturers of
.tdomestic heating products in the U.K
Our first priority is to give a high quality service to
our customers. Quality is built into every Baxi
, product - products which fulfil the demands
and needs of modern consumers, offering
choice, efficiency and reliability.
To keep ahead of changing trends, we have
made a commitment to develop new ideas using
the latest technology - with the aim to continue
making the products that customers want to buy.
Baxi is also the largest manufacturing partnership
•
in the country. Everyone who works at the
company has a commitment to quality because, as
•
shareholders, we know that satisfied customers
- mean continued success.
We hope you get a satisfactory service from
Baxi. If not, please let us know.
BS 5750 Company
1:91.(e-
CONTENTS
Introduction
Technical Data
System Details
Site Requirements
Installation
Water Circulation Systems
Pipework
System Controls
Low Head Installation
Sealed Systems
Location
Clearances
Flue Position
Rue Dimensions
Ventilation
of
Compartments
Gas Supply
Electrical Supply
Initial PreparationPreparation
Rear Flue
Flue Preparation
Assembly
of
Flue
Fitting the Back Plate
Left or Right Flue
Flue Preparation
Assembly
of
Flue
Fitting the Back Plate
Terminal Guard
Fining a Terminal Guard
Internal Fitting Kit
Electrical Connections
Fining the Combustion Box
Water Connections
Pipe Routes
Gas Connection
Commissioning the Appliance
Fitting the Outer Case
Overheat Cut-Off Device
Annual Servicing
Changing Components
^<1-t..
4
1;14

g ,-trreiirgsivircitalemtro
Cleaning the Combustion Box
Cleaning the Burner/Injector
Cleaning the Pilot

AIEBEEIZZIEZZE
Pilot Injector
Ignition Electrode
Fan
Pressure Switch
Boiler Thermostat
Control Board/Electrode Lead
Overheat Thermostat
Insulation Panel Door
Burner and Injector
Insulation Panel Combustion Box
Gas Valve
Fault Finding
Short Parts List
7
,1
4
‘
z
l
e

4--I.W.7:41-
4
INTRODUCTION
The Baxi Solo is a gas fired room sealed fan
assisted central heating boiler with range rated
outputs as shown in the table below.
L
.:.:7.,
.i:1,3saTtlir
^
g
"
?.
M
-;-..-1•.•,,a
• -
..
i,
,
..
VA
r.,..?,15::41]lfrrii.;.;.,:).,t1.,
6.15kW(21 000 Btu/h)
8 79kW(30 000 Btu/h)
-:
I
I
0
9.08kW(31 000 Btu/h)
11.72kW(40 000 Btu/h)
..
c
a
-

.
12.02kW(41 000 Btu/h)
14.65kW(50 000 Btu/h)
15.00kW(51 000 Btu/h)
20.5kW(70 000 Btu/h)
Each appliance is prese at its MAXIMUM
hea input rating and is designed for use on
NATURAL GAS only.
...AB boilers are suitable for fully pumped open
vented central heating and domestic hot water
•
systems and sealed, systems, or where
additional control protection
is
required.
The standard flue is adjustable in length between
100mm (4in) and 610mm (24in) to the left or rear
but the maximum length to the right is reduced to
533mm (21in)(70/4 only-483mm (19in)). Flue
extension kits are available which increase these
maximum dimensions to 2 metres (78
3
/
4
in) for left
or rear and 1.92 metres (75
9
/
16
in) (70/4 only-1.873
metres (73
3
/
4
in)) for right.
NOTE: All above dimensions are taken from the
respective faces of the outercase/backplate.
The appliance data badge is fitted to the combustion
box door.
:Inpitallation;
.4 • A,
The installation must be carried out by a competent
person and be in accordance with the relevant
requirements of the GAS SAFETY (Installation and
Use) REGULATIONS 1984, the BUILDING
REGULATIONS (Scotland)(Consolidation), the LOCAL
BUILDING REGULATIONS, the CURRENT I.E.E.
WIRING REGULATIONS and the bye laws of the
LOCAL WATER UNDERTAKING. It should also be in
accordance with the relevant BRITSH STANDARD
CODES OF PRACTICE.
13;Sfiebeles,of,Praadtid:e
STANDARDaSCOPai
85 6891:1988

Gas Installation.
BS 5546

Installation of hot water
supplies for domestic
purposes.
88 5449 Part 1

Forced cirulation hot
water systems.
BS 6798

Installation of gas fired
hot water boilers.
BS 5440 Part 1

Rues.
855440 Part 2

Air Supply.
Internal Fuse
F2A 250V to BS 4256
situated on control board
(spare fuse also located
on control board)
Connections
2 x 22mm
compression adaptors
Gas Rate
(after 10 mins)
Outerease
Dimensions
1.08m3/h
(38.05113/h)
Height

600mm
Width

400mm
Depth

300mm
Flue Terminal
Dimensions
Diameter 100mm
Depth

65mm
Heat Input
Max
Min
Lifting Weight
•

kW
11.56
8.32
Water Content
Btu/h 39500
28 400
Static Head
Heat Output
Max
Min
metres
kW
8.79 6.15
feet
Btuth
SO 000
21 000
Low Head
Burner Pressure

Max
Min
System Design
mbar
15.8±0.5
7.7 ±0.5
in wg
6.3
=
0.2
3.1 =0.2
Gas Connection
RC7
2
('/in BSPT)
Electrical Supply 240V-50H2 fused 3A
- 32W
Controls

on/off boiler thermostat /
pump over-run with pilot
and electronic flame
sensing
Heat Exchanger cast iron monobloc
I 1
0
C Drop 8.79 kW Output
c
rn-
(4)
ID
20°F Drop 30 000 131u/h Output
max Flow
11.45 litres/mm
2
(2) 5
12.52 gal/min)
C.
o

4.5

9

13.5
(
1
)

RI

131
Water Flow litres/mm
n (gal/min)
Hydraulic Resistance Chart
27.5 kg (60.6 lbs)
1.85 litres (0.407 gals)
Max

Min
30

1
100

3.25
Min 0.2m (8 in)
fully pumped open
vented and sealed
systems.
Max
15
51 200
Min
11.94
40 700
Heat Input
kW
Btu/h
Max
11.72
40 000
Min
9.08
31 000
Heat Output
kW
Btu/h
Min
10.2 =0.5
4.1

0.2
Burner Pressure Max
mbar

.

16.6 ± 0.6
in wg

6.6 0.2
Internal Fuse
F2A 250V to BS
4256
situated
on control board
(spare fuse also located
on control board)
Gas Connection
RC'/
2
(
I
/
2
in BSPT)
Electrical Supply 240V-50Hz fused 3A
- 32W
Controls on/off boiler thermostat /
pump over-run with pilot
and electronic flame
sensing

•
Connections
Gas Rate
(after
10
mins)
Flue Terminal
Dimensions
2 x 22mm
compression
1.40m3/h
(49.33t13/h)
Height
Width
Depth
Diameter
Depth
adaptors
-1
max Flow
a
(4)
10
15.27 Mres/rnin
(3.36 gal/min)
2
0
600mm
(2)
5
400mm
300mm
o

4.5

9

13.5

•

18
.

.
100mm
(1)

(2)

PI

(4)
65mm
Water Flow litres/min tgailmin)
Hydraulic Resistance Chart
-
Outerease
Dimensions
Lifting Weight
27.5 kg (60.6 lbs)
Water Content

1.85 litres (0.407 gals)
Static Head
Max

Min
metres
30
1
Clearances
feet
100
3.25
System Design
fully pumped open
vented and sealed
systems.
X50
Heat Exchanger cast iron monobloc
11
0
0 Drop 11.72 kW Output
ggoc Drop 40 000 BW/h Output
rth (6) 15
Low Head
MM 0.2m (8 in)
TECHNICAL DATA
P9):V4
(4)
10
(2) 5
Lifting Weight
27.5 kg (60.6 lbs)
Water Content

1.85 litres (0.407 gals)
Static Head
metres
MM 0.25m (10 in)
fully pumped open
vented and sealed
systems.
Heat Exchanger cast iron monobloc
2
x
22mm
compression adaptors
1.77m3/h
(62.5583/h)
Height

600mm
Width

400mm
Depth

300mm
Flue Terminal

Diameter 100mm
Dimensions

Depth

65mm
Clearances
11
0
0 Drop 14.65 kW Output
20°F Drop 50 CO0 Btuth Output
max
Flow
19 litres/min
(4.2 gal/min)
0

4.5

9

13.5

18
(1)
(2)

(3)

(4)
Water Flow litres/min (gal/mln)
Hydraulic Resistance Chart
Max
30
Min
1
Low Head
System Design
Connections
Gas Rate
(after
10
mins)
Outercase
Dimensions
feet
100
3.25
Max
26.6
90 900
Min
20.2
68 900:
Heat Input
kW
Btu/h
Lifting Weight
32.8 kg (72.3 lbs)
MM 0.2m (8 in)
Low Head
Diameter
Depth
Flue Terminal
Dimensions
Internal Fuse
F2A 250V to BS 4256
situated on control board
(spare fuse also located
on control board)
Controls
on/off boiler thermostat /
pump over-run with pilot
and electronic flame
sensing
Height
Width
Depth
600mm
470mm
300mm
100mm
65mm
Static Head
Max

Min
Max
Min
Heat Output
kW
Blu/h
metres
30

1
Clearances
20.5
15
feet
100

3.25
70 000
51 000
Burner Pressure
mbar
in wg
Max
13 = 0.5
5.2 = 0.2
Min
7-±a5 •
2.8 = 0.2
System Design
fully pumped open
vented and sealed
systems.
Gas Connection RC
1
/
2
('/
2
in BSPT)
Electrical Supply 240V-50Hz fused 3A
- 32W
2 x 28mm
compression adaptors
2.48m3/h
(87.5783/h)
11°C Drop 20.5 kW Output
20°F Drop 70 000 Btu/h Output
r,
(6) l5
a
(4) 10-
0
(2) 5 -
max Flow
26.8 litres/min
(5.9 gal/min),
1
0

9 13.5
18
22.5 27
(2)
(
3
)

99

(
5
)

(8)
Water Flow litres/min (gal/min)
Hydraulic Resistance Chart
Water Content

2.76 litres (0.61 gals)
Heat Exchanger cast iron monobloc
Connections
Gas Rate
(after 10 mins)
Outercase
Dimensions
Heat Input

Max

Min
kW

19
Btu/h

65 000

54 600
Heat Output Max

Min
kW

14E5

12.02
Btu/h

50 000

41 000
Burner Pressure Max

Min
mbar

15.3 = 0.5 107
in wg

6.1 = 0.2 4.3 = 0.2
Gas Connection RC'/
2
(
I
/
2
in BSPT)
Electrical Supply 240V-50Hz fused 3A
- 32W
Internal Fuse F2A 250V to BS 4256
situated on control board
(spare fuse also located
on control board)
Controls on/off boiler thermostat /
pump over-run with pilot
and electronic flame
sensing
k
f
k
te
i
t
i
r
treS6Y9N
t

System Drains at
All Low Points 15mm By-pass
if required
SYSTEM DETAILS
The appliance is suitable for use with open vent fully
pumped systems, sealed systems and where
additional control protection is required.
•
The following conditions should be observed on all
systems:
()The static head must not exceed 30 m
(100ft) of water.
•The boiler must not be used with a
direct cylinder.
0The boiler is fitted with a pump
overrun thermostat and where the
system design does not result in a
permanent open circuit between boiler
flow and return, a 15mm by-pass loop,
fitted with a lockshield valve, must be
incorporated to maintain a minimum
flow rate through the boiler of
7
1/min
(1.54 gal/min).
•
Drain cocks should be fitted to all
system low points.
Ptp,

cteta
"Y
Pumped SI-
OPosition isolating valves as close to circulating pump
as possible.
S
System additives - where used, corrosion inhibitors
and flushing agents/descalers should be suitable for
all system metals. They should be acceptable to major
users i.e. British Gas and Water Council approved. Non
acidity or alkalinity is desirable.
The sizes of flow and return pipes from the boiler
should be determined by normal methods, according
to the requirements of the system.
It Is recommended that the system is designed for an
11°C (20°F) drop in temperature across the system.
22mm Open Vent
15mm
Cold
Feed
Air Vent
-gt
Radiator
Circuit
0 All gas and water pipes and electrical wiring
must be installed in a way which would not restrict
the servicing of the boiler.
Indirect
Cylinder
360mm Min
(50/4 only)
125mm
xk
r
kt
ri').
;;;;O
Viltgl
ks
For optimum operating conditions, the heating system
'into which the boiler is installed should include a
-
control system.
Such a system will comprise of timer control and a
'
,
separate room or cylinder thermostat as appropriate.
The boiler should be controlled so that it operates on
demand only.
Operation of the system under control of the boiler
thermostat only, does not produce the best results.
Where necessary a frost thermostat should be fitted to
protect the boiler and if necessary the system.
Reference should be made to the control equipment
manufacturer's literature for information e.g. wiring
•
diagrams, etc.
175mrn Min
(225mm Min
50/4 only)
For Minimum
Operating Head
See Pump
Manufacturers
Instructions
538mm Min
150mm Max
22mm Open Vent
(30-40/4 only)
28mm Open Vent
(50-70/4 only)
100mm Min
I
Return
Row '1 I
CD
C
to

0(t
Iv
Head Insta
%
lla
•
A guide to a fully pumped low head installation is
shown, subject to: The correct gas input and the pump
being adjusted to give the design flow rate, (i.e. 11°C
(20°F) Drop). It is important to ensure a route back to
the boiler for the cold feed via the system, a bypass or
3 port valve control system would satisfy this
requirement.
The diagram shows a method of installation where the
static head between the boiler and feed/expansion
tank is restricted e.g. between ceiling level and a
•
kitchen work top.
It is important that the open vent pipe is taken off the
flow pipe in the manner illustrated i.e. by means of a
tee in a horizontal section of the flow pipe.
An alternative approach would involve the use of the
boiler, which is fitted with an overheat thermostat, in
conjunction with a combined feed and vent
arrangement.
Pressure
Gauge
Filling
Point
Pump
0
V I
Expansion
Vessel
Radiator
Circuit
Safety
Valve
Al
Vent
3 Litre
Top Up Bottle
(If Required)
A safety valve complying with the requirements of
BS 6750 Part 1 must be fitted close to the boiler on the
flow pipe by means of a horizontal or vertically upward
connection with no intervening valve or restrictions and
should be positioned to facilitate testing. The valve
should be pre-set and non-adjustable to operate at a
pressure of 3 bar (45 lbf/In9. It must be arranged to
discharge any water or steam through a pipe to a
safe outlet position.
,

--
IUSERMIESEMBEEMES
A pressure gauge of minimum range 0-4 bar
(0-60 lbf/In
2
) with a fill pressure indicator
must be fitted to the system, preferably at the
same point as the expansion vessel in an
easily visible position.
An expansion vessel complying with the
requirements of BS 4814 must be fitted to the
system by means of a connection close to the
inlet side of the circulating pump in accordance
with the manufacturers instructions, the
connecting pipe being unrestricted and not less
than 15mm
(
V
2
in) nominal size. The volume of the
vessel should be suitable for the system water content
and the nitrogen or air charge pressure should not be
less than the system static head. Further details of
sealed system design can be obtained from BS 5449:
Part 1 and the British Gas publication entitled
'Specifications for Domestic Wet Central Heating
Systems'.
I*4111.101W4.13/4.

-
System Drains
at Low Points
Max Boiler Flow
Temp = 82°C
Pr
cot
miciiii
el
*volytiikurn
_
c,

•
;C
oll
-
4
5
-"icsin
"
4713a4 %-f-9--r-e-44
.7-
-it2-9,,terP
'co..
,

0
7 --Pe;
ko
.4115.09'ie
404.-k
4
'

I--
Vessel Charge
Pressure (Bar)
1
Initial System
Pressure (Bar)
Multiply Total
Water Content
Of System by
(Litres)
0.5 -'
'

0.5
1.0
1.5
2.0
0.067
0.112
0.207
0.441
1.0
1.5
2.0
0.087
0.152
0.330
1.5
2.0
0.125
0.265
Vetherohardtplessure
nitialljjlein-preicute
5
Ekpans
yatem_volume
0' 5

raire
/
r
o
t
-
t
e n
,
41,6
'Op Oa
Pe

NOTE
w
of the calce‘
a
e
2
7
0
-1
0‘
e
-9
e,
ta
ble
se
siz
e
e
then the neXt
-nould be used.
- 0 10,i-
A filling point and an approved stop valve to BS 1010
must be fitted at low level and the method used for
fillingthe system should be approved by the local
Water undertaking. For further details see BS 6798.
afAXEMEISYSIEMEMENZEMES
A method of replacin9 water lost from the system
should be provided either by means of a make up
vessel of not more than 3 litres (5 pints) capacity,
mounted above the highest point of the system, or by
pre-pressurisation of the system.
A method of venting the system during filling and
commissioning must be provided by fitting automatic
air vents or by venting manually.
-Worn
,
Am; .
0
tom
The hot water storage vessel must be of the indirect
coil type. All components used in the system must be
suitable for operation at 110°C (230°F) and at the
pressure allowed by the safety valve.
SITE REQUIREMENTS
.0
-
he appliance maY be fitted to any suitable wall with
the flue passing through .an outside wall and
.discharging to atmosphere in a position permitting
7 "[Satisfactory removal of combustion products and
.:
.
fProviding an adequate air
.
supply. The appliance
:.should be fitted within the building unless otherwise
::protected by a suitable enclosure ie. garage or
'.:.cauthouse.
lithe appliance is to be fitted into a building of timber
::frarne construction then reference must be made to
.:British Gas document DM2.
RecornmendatiOnS for flues are given in BS 5440 Pt. 1.
'SS
.
A flat vertical area
le
required for the installation of the
'boiler measuring aS shown in the table below for each
Height

Width
Model
mm (in) mm (in)
30/4
800 (31
1
/
2
)
410 (161/)
40/4
800(311/2)
410 (161/8)
50/4
800(3172)
410(15h/)
70/4
850 (337
2
)
480 (1874)
obstructions such as joists running
parallel to the front face of the appliance.
clearances to the side of the installation equal to the
length of the flue reqUired including the terminal (ie flue
length + 65mm (2V2in)).
Model:
These dimensions include the
'necessary clearances around the
appliance for case removal, spanner
access, air movement:
Additional clearances may be required
for the passage of pipes around local
Installations flued to the left or right require extra
(SNP
An internal fitting kit is provided with the appliance for
installations where the flue terminal is inaccessible
from the outside.
The following guide lines indicate the general
.requirements for siting balanced flue terminals.
If the terminal is fitted within-1 metre (39in) of a plastic
gutter, within 500mm (197
2
in) of a painted eave or a
painted gutter, an aluminium shield of at least 1 metre
(39in) long should be fitted to the underside of the
gutter or painted surface. An air space of 5mm (116in)
should be left between shield and gutter.
If the terminal discharges onto a pathway or
passageway, check that combustion products will not
cause a nuisance and that the terminal will not obstruct
the passageway.
If the outer surface of an outside wall is of combustible
material, it should be protected by fitting a non-
combustible plate so that it extends not less than
50mm (2in) around the terminal.