
BAXI LUNA 310 Fi troubleshooting guide
Page 3
Fault Cause Suggested Solutions
Boiler short cycling. Heating output has not ▪Set the "Max R" on the control PCB to match the heating system requirements,
been set. see chart on page 25 in manual for settings.
Short cycling on a ▪In a smaller system make sure theT-Off Jumper on the PCB is set to the left,
short heating circuit. this will give a 3 min. delay when the burner turns off in the heating mode.
▪If zone valves are present in system, the internal bypass is not designed to
handle system flow, it is only used for boiler pump protection. Install a separate
pressure-activated bypass, a buffer tank or a low loss header.
Whistling noise from High fire when using ▪BAXI recommends that only25% inhibited propylene glycolsolutions which are
boiler. Glycol in system. specially formulated for hydronic systems be used in the LUNA boiler. Ethylene
glycol is toxic and can attack gaskets and seals used in hydronic systems.
Check that the glycol ratio is not more than the recommended amount yearly,
a higher ratio can affect the pump performance causing noise at high fire.
Note: Anti-freeze solutions expand more than water. For example a50% by volume
solution expands4.8% in volume for a temperature increase from32°F to 180°F,
while water expands3% with the same temperature rise. Allowances must be
made for this expansion in the system design. A30% mixture of glycol will result
in a BTU output loss of 15% with a 5% increase in head against the boiler pump.
A 50% mixture of glycol will result in a BTU outputloss of 30% with a 50% increase
in head against the boiler pump.
Fluctuating DHW Boiler cycles on and ▪Check that low fire is not set to high. Reset if required.
temperature at tap. off.
Erratic burner ▪Check burner pressure at gas valve test port with manometer while boiler
pressure. operating. If gas pressure fluctuates erratically suspect either primary sensor is
out of calibration or the DHW sensor is dirty. Replace one or both sensors.
Burner pressure ▪Check burner pressure at gas valve test port with manometer while boiler
fluctuates from high operating. If gas pressure fluctuates from high to low then back to high suspect
to low fire. that the DHW plate exchanger is dirty or scaled up. Remove and clean/ de-scale
with suitable cleaner, or replace heat exchanger.
▪If the boiler is being used with a well, make sure that the supply pressure is good.
If the pump setting is set for 40 Psi-on and 60 Psi-off try it at 50 Psi-on and 70 Psi-off.
Fluctuating ▪If previous checks are OK check the temperature of the hot water at a single
temperature at tap (not single lever tap). If the temperature is stable (within 3-5°f) at this tap
shower. suspect that the shower valve cartridge is dirty or faulty, clean or replace cartridge.
Note: taps that have internal plastic parts tend to cause fluctuations in water flow.
Plastic has a faster expansion rate than brass as the water heats it up it tends to
expand and slow the water flow. The tap then needs to be opened further to let the
water flow faster, which in turn increases the water flow through the boiler.
Hot water not hot Incorrect gas ▪Check that the boiler has the correct maximum gas pressure.
enough. pressure.
Faulty/Dirty NTC ▪Check that the DHW sensor is not dirty or scaled up. Check that sensor is not
sensor. out of calibration (10 K Ω@ 25°C). Replace if faulty.
▪If PCB has been changed has the boiler thermostat knob been fitted correctly?