manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. BEA
  6. •
  7. Remote Control
  8. •
  9. BEA DK-12 User manual

BEA DK-12 User manual

Other manuals for DK-12

2

Popular Remote Control manuals by other brands

Bircher Reglomat RC Duo 2 user guide

Bircher Reglomat

Bircher Reglomat RC Duo 2 user guide

Emerson RCBT100 owner's manual

Emerson

Emerson RCBT100 owner's manual

BILDA Element-6 user manual

BILDA

BILDA Element-6 user manual

Absima CR7P manual

Absima

Absima CR7P manual

Mitsubishi Electric PAR-32MAAG Instruction book

Mitsubishi Electric

Mitsubishi Electric PAR-32MAAG Instruction book

RCA RCRTBL08BE1 quick start guide

RCA

RCA RCRTBL08BE1 quick start guide

US Electronics NOVARI user guide

US Electronics

US Electronics NOVARI user guide

Panasonic EUR7622KB0 Operation guide

Panasonic

Panasonic EUR7622KB0 Operation guide

Bang & Olufsen Beo4 user manual

Bang & Olufsen

Bang & Olufsen Beo4 user manual

Marantz RC101 user guide

Marantz

Marantz RC101 user guide

FUTABA 9ZAP - PART2 manual

FUTABA

FUTABA 9ZAP - PART2 manual

HR Matic HR MULTI 3 quick start guide

HR Matic

HR Matic HR MULTI 3 quick start guide

Anritsu MP1777A Operation manual

Anritsu

Anritsu MP1777A Operation manual

Niles WVC100 Installation & operating guide

Niles

Niles WVC100 Installation & operating guide

Bang & Olufsen BEO6 Getting started

Bang & Olufsen

Bang & Olufsen BEO6 Getting started

GE 94901 instruction manual

GE

GE 94901 instruction manual

FUTABA R7108SB Full manual

FUTABA

FUTABA R7108SB Full manual

Invacare G91S user manual

Invacare

Invacare G91S user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

?
?
?
?
?
?
Universal
Remote
Control Guide
RIDC Park West
100 Enterprise Drive
Pittsburgh, PA 15275
Phone: 1 412.249.4100
FAX: 1 888.523.2462
Toll Free: 1 800.523.2462
75.0180.05 2008102
1
* Active output (Fail-Secure):
NC-COM circuit is closed and
NO-COM circuit is open.
** Passive output (Fail-Safe):
NO-COM circuit is closed and
NC-COM circuit is open.
WIZARD
Microwave Sensitivity(0-9)
Default = 7
F1 Safety Output (0-1)
0. No Redirection (6 wires)
1. All Relay Output (4 wires)
Relay Output (1-4)
Motion Out Presence Out
1. Active NO Passive NC
2. Passive NC Active NO
3. Passive NC Passive NC
4. Active NO Active NO
Detection Mode (1-4)
1.Bidirectional 2.Unidirectional
3.Unidirectional with MTF
4. Unidirectional Reverse
Microwave Immunity(1-9)
1. Reduced 2. Normal
3. Increased 4-9 Enhanced
Infrared Immunity (1-3)
1. Low 2. Medium 3. High
Set-Up (0 or 9)
0. Setup 9. Factory Defaults
FALCON
Sensitivity (0-9)
Default = 7
Hold Time (0-9)
(0.5 sec - 9 sec)
Relay Output (1-2)
1. Active Output*
2. Passive Output**
Detection Mode (1-3)
1.Bidirectional
2.Unidirectional Approach
3.Unidirectional Depart
Rejection Mode(1-5)
1. Detects all traffic: Pedestrian
& Vehicle
2. Detects All Traffic +Interference
Immunity
3. Low Pedestrian/Parallel Traffic
Rejection
4. Mid Pedestrian/Parallel Traffic
Rejection
5. High Pedestrian/Parallel Traffic
Rejection
Restore Default
Settings (1)
Auto Learn Time(0-6 or 9)
0 - 30 sec 3 - 5 min 6 - 60 min
1 - 1 min 4 - 10 min 9 - Infinity
2 - 2 min 5 - 20 min (no learn)
EAGLE
Sensitivity (0-9)
Default = 8
Hold Time (0-9)
(0.5 sec - 9 sec)
Relay Output (1-2)
1. NO Relay* 2. NC Relay**
Detection Mode (1-3)
1. Bidirectional 2. Unidirectional
3. Unidirectional with MTF
Immunity (1-9)
1. Reduced 3. Increased
2. Normal 4-9. Enhanced
Default Settings(1-2 or 9)
1.Normal 2.Boost 9.Restore
F2 Door Control (1-3)
1. Normal
2. Permanent Detection
3. Permanent Non-Detection
75.0180.05_RC_Guide_20080915_BW.indd 175.0180.05_RC_Guide_20080915_BW.indd 1 10/21/2008 3:05:59 PM10/21/2008 3:05:59 PM
UNIVERSAL OPTIONS
Lock
Note: Not used on DK-12
Unlock
Note: Not used on DK-12
Inquiry
?
For any product application specified
herein, compliance to the ANSI A1
56.10-2005 standard is strictly
performance driven. Therefore,
following each installation and/or
adjustment, it is necessary to
properly walk-test and document
the performance of all sensors to
ultimately help aide in the
determination of compliance.
Testing and final determination of
ANSI compliance should be
performed by inspectors that have
been certified by the American
Association of Automatic Door
Manufacturers (AAADM).
DISCLAIMER
* Active output (Fail-Secure):
NC-COM circuit is closed and
NO-COM circuit is open.
** Passive output (Fail-Safe):
NO-COM circuit is closed and
NC-COM circuit is open.
75.0180.05 200809
15
BODYGUARD
Sensitivity (0-9)
Default = 6 Closed, 7 Open
Hold Time (0-9)
0 (0.5 sec.) to 9 (9.0 sec.)
Relay Output (1-2)
1. NO Relay* 2. NC Relay**
Auto Learn Time (0-9)
0 - 30 sec 4 - 5 min 8 - 10 sec
1 - 1 min 5 - 7 min 9 - Infinity
2 - 2 min 6 - 10 min (no learn)
3 - 3 min 7 - 15 min
Pattern Width (1-9)
1. Wide (Door Closed)
2. Middle (Door Open)
3. Asymmetrical Left Narrow
4. Asymmetrical Right Narrow
5. Narrow Left
6. Narrow Right
7. Asymmetrical Left Wide
8. Asymmetrical Right Wide
9. Center Narrow
Pattern Depth (1-6)
1. Deep - Threshold On
2. Medium - Threshold On (Open)
3. Limited - Threshold On
4. Deep - Threshold Off
5. Medium - Threshold (Closed)
6. Limited - Threshold Off
Immunity (1-3)
1. Low 2. Medium 3. High
Set-Up (1-2 or 9)
1. Door Closed 2. Door Open
9. Restore Factory Defaults
Infrared Frequency (1-4)
1. Normal/Low 3. Quiet/Low
2. Normal/High 4. Quiet/ High
DK-12
Pattern Width (1-6)
1. Wide (open & closed) 4. Left Narrow
2. Left Wide 5. Center Narrow
3. Right Wide 6. Right Narrow
Frequency (1-2)
1. High Impulse 2. Low impulse
Relay Output (1-4)
1. Passive Output** 3. ON
2. Active Output* 4. OFF
Sensitivity (0-9)
Default = 8 Closed, 7 Open
Set-Up (1-2 or 9)
1. Door Closed 2. Door Open
9. Restore Factory Defaults
F2 Door Control (1-3)
1. Normal (LED Normal Mode)
2. Door Permanently Open (On)
3. Door Permanently Closed (Off)
BodyGuard & DK12 differences only