Installing your thermostat
4. Setting the system mode
Press Mto change the system mode HEATING,
COOLING and VENTILATION. In the mode of
VENTILATION, the valve is off but the fan runs.
5. Setting the Sleeping
Press and Hold Mto set the sleeping. Press
to confirm, to cancel.
6.Selecting manual and programmable
Press and hold Mto change manual and weekly
programmable. MANUAL means
non-programmable. will display in the right
corner of screen. Press to select Manual and
press to select weekly programmable.
The order is sleeping -- manual/weekly
programmable -- period and temperature setting.
7. Adjusting the weekly programmable
Press and hold Mto change into weekly
programmable. Then press Mto change the
different items.
The order is Minute adjusting→ Hour adjusting
→ Week adjusting→ Minute timing-on → Hour
timing-on→ Minute timing-off→ Hour timing-off→
Temperature adjusting ( Three periods,
“12345”,”6”,”7”, is “5+1+1” programmable mode,
every mode has two times zones and a time
temperature setting)
Week
First Period Second Period
Turn-on
me
Turn-off
me
Set
temp.
Turn-on
me
Turn-off
me
Set
temp.
Mon. to Fri. 1 2 3 4 5 6
Sat. 7 8 9 10 11 12
Sun. 13 14 15 16 17 18
8. Setting functions and options
During power off, press and hold at the same
time for 5 sec. to system functions. Then press M
to change the different items. All the settings will
confirm automatically when power is on. Press
to confirm, to cancel.
No Func on Se ng & Op ons Default
1 Temp.
Calibra on
-9℃to 9℃0℃
2 Lock 0:All the bu ons are locked
except POWER
1 :All the bu ons are locked
1
3 Fan Control 0:When room temp. reaches
the setpoint, the fan will turn
off.
1:When room temp. reaches
the setpoint, the fan will turn
to low speed.
0
4 Heat/Cool 0:Cool only 1:Heat/Cool 1
5 Min. Set Temp. 5-15℃,default is 10℃10℃
6 Max. Set Temp. 5-35℃,default is 30℃30℃
7 Time Display 0:12 hours 1:24 hours 0
8 Display mode 0:display set temp. only
1:display both set temp. and
room temp.
1
9 Keycard mode 0: When keycard is pulled off,
room thermosat enter into
energy saving mode.
1: When keycard is pulled off,
room thermostat is off.
0
10 Set temp.
for keycard
For hea ng:10-20℃15℃
11 Set temp.
for keycard
For cooling:25-35℃30℃
This product is suitable for standard 86mm wall
box or european 60mm round box.
Wiring your thermostat
2
1
3
7
6
5
4
BAC1000APK (Two pipe)
110-240VAC 50~60HZ
L
N
FAN
HIGH
MED
LOW
VALVE
ON
OFF
1. Connect the line of power and valve into the terminals.
Fix the wall plate into the wall box by a screwdriver.
2. Connect the lines with the LCD board.
3. Connect the LCD board into the wall plate.
4. Finished.
(Fig 1)
(Fig 2) (Fig 3)
(Fig 4)
9
8
keycard
WARNING: Please arrange the professional technician
to install this product according to installation drawing and
instruction.
RISK OF ELECTRICAL SHOCK. Disconnect power supply
before making electrical connection. Contact with components
carrying hazardous voltage can cause electrical shock and may
result in severe personal injury or death.instruction.
BECA ENERGY CONTROLS CO.,LTD
www.becavalve.com