1
MOUNTING INSTRUCTION
ZIP Economizer™Base Module
Dimensions in Inches [mm]
ECON-ZIP-BASE
Technical Data
Type Name Description Electrical Specification
Input R Supply Hot 24 VAC, ± 20%, 50/60Hz
Input G Fan Signal (occupied) On/Off, 24 VAC, ± 20%, 50/60Hz
Input C Supply Common Common
Input Y1 Cooling requirement
Stage 1
On/Off, 24 VAC, ± 20%, 50/60Hz
Input Y2 Cooling requirement
Stage 2
On/Off, 24 VAC, ± 20%, 50/60Hz
Input W1 Heating requirement
Stage 1
On/Off, 24 VAC, ± 20%, 50/60Hz
Input SAT ± Supply Air Temperature
Sensor
Type: 10K NTC (Type II thermistor)
Input OAT ± Outdoor Air Temperature Type: 10K NTC (Type II thermistor)
Input OAH ± Outdoor Air Humidity 0-10 VDC
Auto Detection: Sensor present if
voltage 0.5V-10V
Input RAT ± Return Air Temperature Type: 10K NTC (Type II thermistor)
Input RAH ± Return Air Humidity 0-10 VDC
Auto Detection: Sensor present if
voltage 0.5V-10V
Output CC1 Compressor 1
RTU Stage 1
Mechanical Cooling
Circuitry
100'000 cycles @ inrush current
of 3A, normal current 1.5A
Impedance for Auto detection
@ 24 V:
<60O W@ 60Hz
<80O W@ 50Hz
Output CC2 Compressor 2
RTU Stage 2
Mechanical Cooling
Circuitry
100'000 cycles @ inrush current
of 3A, normal current 1.5A
Impedance for Auto detection
@ 24 V:
<60O W@ 60Hz
<80O W@ 50Hz
Output Act 1 Actuator supply common Common
Output Act 2 Actuator supply hot 24 VAC, 50/60Hz
Output Act 3 Actuator control output 2-10 VDC
Input Act 5 Actuator feedback signal 2-10 VDC
2.35” [59.7]
2.42” [61.6]
6.63” [168.5]
2” [50.8]
6.04” [153.4]
1.61” [40.9]
7.12” [181]
0.34”
[8.7]
1.25” [31.8]
5.64” [143.2]
5.50” [139.7]
2.35” [59.7]
2.42” [61.6]
6.63” [168.5]
2” [50.8]
6.04” [153.4]
1.61” [40.9]
7.12” [181]
0.34”
[8.7]
1.25” [31.8]
5.64” [143.2]
5.50” [139.7]
Installation
You can mount the ZIP Economizer in any orientation; it is
recommended that you mount it in a position that will allow
full utilization of the LCD and key pad and proper clearance for
installation, servicing, wiring, and removal.
Take the overall dimensions of 6.63" [168.5] x 7.12" [181] x 2"
[50.8]and mount in the interior of the RTU in a convenient location
that you can access. Secure the ZIP utilizing #8 self-tapping screws
(included). A minumum of two tabs need to be secured, one which is
a top tab. Ideally secure all four tabs. Wire the electrical connection
using ¼” female insulated spade connectors to prevent corrosion.
08/14 - Subject to change. © Belimo Aircontrols (USA), Inc.
71413-00001_E
WIRING DIAGRAM
ZIP Economizer™Base Module
2
08/14 - Subject to change. © Belimo Aircontrols (USA), Inc.
R
C
G
OCC
W1
O/B
Y1
Y2
ACT1 ACT2 ACT3
ACT5
R
C
R
C
GW1
Y1
Y2
CC1
CC2
OAT+
OAT-
OAH+
OAH-
SAT+
SAT-
RAT+
RAT-
RAH+
RAH-
-SR
1 -Common
2 + Hot
3 Y Input, 2 to 10V
5 U Output, 2 to 10V
ACT 1
ACT 2
ACT 3
ACT 5
R
C
Y1
Y2
ECON-ZIP-10K
Supply Air Temp
SAT +
SAT -
OAT +
OAT -
CC1
CC2
OCC
W1
RTU Stage 1
Mechanical Cooling
Circuitry
RTU Stage 2
Mechanical Cooling
Circuitry
ECON-ZIP-TH
Outside Air Enthalpy
ECON-ZIP-TH
Return Air Enthalpy
RAT+
T (+)
T (-)
24 V (R)
RH (+)
RH (-)
RAT-
RAH+
RAH-
R
T (+)
T (-)
24 V (R)
RH (+)
RH (-)
OAH +
OAH -
R
ECON-ZIP-BASE
THERMOSTAT RTU TERMINAL
1 3 6 46
50
52
51
53
50
Differential Dry Bulb
Differential Enthalpy
R
C
G
OCC
W1
O/B
Y1
Y2
ACT1 ACT2 ACT3
ACT5
R
C
R
C
GW1
Y1
Y2
CC1
CC2
OAT+
OAT-
OAH+
OAH-
SAT+
SAT-
RAT+
RAT-
RAH+
RAH-
-SR
1 -Common
2 + Hot
3 Y Input, 2 to 10V
5 U Output, 2 to 10V
ACT 1
ACT 2
ACT 3
ACT 5
R
C
Y1
Y2
ECON-ZIP-10K
Supply Air Temp
SAT +
SAT -
OAT +
OAT -
THERMOSTAT RTU TERMINAL
CC1
CC2
OCC
W1
RTU Stage 1
Mechanical Cooling
Circuitry
RTU Stage 2
Mechanical Cooling
Circuitry
ECON-ZIP-10K
Outside Air Temp
ECON-ZIP-10K
Return Air Temp
RAT
ECON-ZIP-BASE
1 3 6 46
52
51
53
Actuators Hot wire must be connected to the control board common.
Actuators may be controlled in parallel. Current draw and input impedance must be observed.
6
46
Power source should be the same as ECON-ZIP-BASE.
50
When the thermostat is not equipped with occupancy control, "Fan On" output "G" shall be wired to the ECON-ZIP-BASE.
W1 must be wired to ECON-ZIP-BASE when unit is a Heat Pump, using 2 speed fan (VFD), and/or when it is desired to record operational hours in heating.
Existing refrigeration safety devices may exist, consult RTU wiring diagram
51
52
53
Actuators Hot wire must be connected to the control board common.
Actuators may be controlled in parallel. Current draw and input impedance must be observed.
6
46
Power source should be the same as ECON-ZIP-BASE.
50
When the thermostat is not equipped with occupancy control, "Fan On" output "G" shall be wired to the ECON-ZIP-BASE.
W1 must be wired to ECON-ZIP-BASE when unit is a Heat Pump, using 2 speed fan (VFD), and/or when it is desired to record operational hours in heating.
Existing refrigeration safety devices may exist, consult RTU wiring diagram
51
52
53
QUICK SETUP
ZIP Economizer Base Module
3
08/14 - Subject to change. © Belimo Aircontrols (USA), Inc.
MMI Keypad
Moves up through the
menu on the same level.
Will increase values by
one increment at a time.
When setting values
holding key down will
fast scroll
Moves down through the
menu on the same level.
Will decrease values by
one increment at a time.
When setting values
holding key down will fast
scroll.
Enter sub menu level.
Start editing a setting.
Store an entered
value.
esc
Escape sub menu to
next higher level.
Cancel current actions.
i
Show additional
information on the
current menu Item
when “i” appears in
lower right of display.
Moves up through the
menu on the same level.
Will increase values by
one increment at a time.
When setting values
holding key down will
fast scroll
Moves down through the
menu on the same level.
Will decrease values by
one increment at a time.
When setting values
holding key down will fast
scroll.
Enter sub menu level.
Start editing a setting.
Store an entered
value.
esc
Escape sub menu to
next higher level.
Cancel current actions.
i
Show additional
information on the
current menu Item
when “i” appears in
lower right of display.
Functions
1. “Monitor Live Conditions” is used to display settings and live values.
2. “Settings” is used to parameterize the ZIP Economizer. Unless otherwise
prompted; default entry is “Auto” or “Off”. (Note: Devices 1 is for CC1,
CC2, EF, IF; Devices 2 is for OAH, RAH)
3. “Present Devices” is used to verify that the ZIP Economizer's Auto Detected
connections are terminated properly. If established I/O is not shown,
verify wiring. If wiring has continuity and device is verified operational
re-enter “Settings” and enable missing device by changing from “Auto” to
“Available” or “Installed”.
4. “Alarms” is used to view current and historical alarms and delete
inadvertently caused alarms.
5. “Service and Commissioning” submenu is used to operate the RTU in
“Manual Mode” or to perform “Acceptance Test”. “Settings” must to be
completed to access.
6. “Status” is a display of the current operating mode. It can be accessed
by pressing ”esc”. The action of pressing any key will drop the user down
from Status to the next level, so repeatedly pressing “esc” will toggle the
display between Status and Monitor Live Conditions. (Note: If status
“Setup Incomplete” is displayed the RTU cooling operation will be
disabled.)
Installation
1. Shut off power to RTU before beginning installation.
2. Note orientation, opening rotation, and spring return rotation of damper
assembly. Mount Actuator to Outside Air and Return Damper assembly.
To ensure tight outside air shutoff; while tightening actuator clamp push
damper closed.
3. Terminate required Inputs and Outputs(I/O): For the ZIP Economizer to
function correctly, the following I/O, at a minimum, are required to be
terminated, wired, and functioning (R, C, Y1, Y2, G, CC1, OAT, SAT, ACT1,
ACT2, ACT3, ACT5). See diagram above.
4. Sensor configuation: The ZIP Economizer automatically detects sensors
attached and automatically configures for single dry bulb, single enthalpy,
differential dry bulb and differential enthalpy.
Settings
“Settings” is the menu displayed when the ZIP Economizer is first powered.
Press “OK” to parameterize required settings. Reference above Keypad Key
definition instructions and navigate as needed.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a quali-
fied licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
QUICK SETUP
ZIP Economizer Base Module
Required "Settings" Parameters for All Configurations
1. ZIP Code US or Canada (sets the free cooling changeover high limit and
temperature units F/C)
a. When the Zip Code submenu is displayed enter “OK” to begin “US” Zip
Code parameterization. If “Canada” Postal Code is desired press the up/
down arrow to access.
i. Press OK to access digit 1 (flashing) then use the up/down arrow
to parameterize; enter OK when complete. Repeat until all digits
are complete. If a mistake is made press “esc” and repeat from
beginning
ii. When all Zip Code or Postal Code digits are parameterized press
“esc” to move up a level then press the up/down arrow to access
next settings parameter.
2. Vent Min Pos (Outdoor Air Damper Ventilation Minimum Position)
a. When the “Vent Min Pos” submenu is displayed press “OK” to
parameterize (flashing).
b. Use the up/down arrow to parameterize, press “OK” when complete.
The actuator will immediately drive the damper to the minimum position.
3. Additional Parameters may require setting. The ZIP Economizer will auto-
detect added Devices such as a CO2 sensor etc. When the ZIP Economizer
detects a new device, it will prompt the user in the Status level; navigate to
Settings and parameterize blank fields. If the devices are connected upon
first start up their settings will require parameterization then.
4. When all parameters have been set, the ZIP Economizer will show “Setup
Complete” if there are still parameters to set, there will be no action. You
can verify by pushing esc until status level is reached and it will display
“Setup Incomplete”. If this is the case, re-enter settings menu and use up
down arrows to find the parameter with blank fields and parameterize as
described above.
Note: you may enter parametersin any order - eg: Vent min Pos before ZIP
Code - If the RTU is a heat pumpor uses a 2 speed indoor fan, these
paramaters should be enabled first, otherwise the logic may go to Setup
Complete prematurely.
Service and Commissioning (Acceptance Test & Manual Mode)
Setup Complete - Initializing Automatic Mode
1. The ZIP Economizer has built in commissioning processes found in
Acceptance Test. Use “Economizer Test” to verify RTU Integrated
Economizer operation and also if it is known that the actuator stroke is
mechanically limited to less than 90 degree rotation. The test will re-
scale the control signal range to maximum resolution (0-100%) over the
calibrated (reduced) angle.
a. Navigate to the “Service and Commissioning” menu, press “OK”; press
the down arrow to access “Acceptance Test”. Press OK again when
“Economizer Test” appears. Press “OK” again to confirm running test.
Follow prompts during test. This test will open damper to 100% (re-
scale control signal if needed), enable power exhaust fan (if connected),
enable 1st stage of Mechanical Cooling, reverse this process and then
drive to Vent Min Position. When used with a Belimo actuator, the
actuator will speed up to reduce test time. (Note: failure to identify
obstructions or improper setup of damper assembly may result
in an improper scaling and operation of the damper.)
b. This can be done by pressing “OK”... displayed or is automatically
done after 8hrs has passed.
2. Manual Mode is used to override outputs after entering a “Timeout”
duration.
1. When all entries have been completed, the ZIP Economizer will switch to
Status display and show “Setup Complete”, and will immediately show a
“Damper scaling starts in 10secs” and will countdown to 0 (be aware,
at 0 the damper will start to move at high speed) . A message will scroll
saying “Damper scaling for better operation if obstruction is present
rescale damper in commissioning menu”. (For detailed instructions on
this – please see the section “Service and Commissioning” below. This will
open damper to 100% (re-scale control signal if needed). (Note: failure to
identify obstructions or improper setup of damper assembly may result in
an improper scaling and operation of the damper.)
Once scaling is complete, a message will appear saying “Damper scaling
successful”. The ZIP will then show “maximum at 80° = 100%” That
message will show maximum rotation of the damper. This process ensures
the damper is always operating and displayed from 0-100%.
2. Once the message has appeared, the actuator immediately closes the
damper and a countdown begins, until the unit starts to operate in
Automatic Mode (be aware, when countdown complete, the RTU
will respond to thermostat calls which may enable mechanical
cooling).
Belimo Americas
USA, Latin America, and the Caribbean: www.belimo.us
Canada: www.belimo.ca
Brazil: www.belimo.com.br
Belimo Worldwide: www.belimo.com
08/14 - Subject to change. © Belimo Aircontrols (USA), Inc.

Other Belimo Audio & Video Accessories manuals

Belimo ECON-ZIP-BASE User manual

Belimo

Belimo ECON-ZIP-BASE User manual

Belimo ZIP Economizer User manual

Belimo

Belimo ZIP Economizer User manual

Belimo ZIP Economizer User manual

Belimo

Belimo ZIP Economizer User manual

Popular Audio & Video Accessories manuals by other brands

Koyoe KY HYBIRD Series user manual

Koyoe

Koyoe KY HYBIRD Series user manual

Kramer DS Vision Digital user manual

Kramer

Kramer DS Vision Digital user manual

ENSA ENSA-MS3 instruction manual

ENSA

ENSA ENSA-MS3 instruction manual

TED 5000 Series user manual

TED

TED 5000 Series user manual

RGBlink CP 3072S quick start guide

RGBlink

RGBlink CP 3072S quick start guide

Delta TR-1B P2 Series user manual

Delta

Delta TR-1B P2 Series user manual

Smappee Infinity installation manual

Smappee

Smappee Infinity installation manual

Rainforest Automation EMU-2 Technical manual

Rainforest Automation

Rainforest Automation EMU-2 Technical manual

CAD Audio Live DA4090 user guide

CAD Audio

CAD Audio Live DA4090 user guide

Adax BT Instructions for use

Adax

Adax BT Instructions for use

Efergy Elite IR instruction manual

Efergy

Efergy Elite IR instruction manual

Barnfind Stagebox manual

Barnfind

Barnfind Stagebox manual

Roberts Gorden nRG Control Installation, operation and service manual

Roberts Gorden

Roberts Gorden nRG Control Installation, operation and service manual

Oregon Scientific ESD200 user manual

Oregon Scientific

Oregon Scientific ESD200 user manual

Panoramic Power Energy Insight Installation and configuration guide

Panoramic Power

Panoramic Power Energy Insight Installation and configuration guide

Herz ETKF 1 8250 02 datasheet

Herz

Herz ETKF 1 8250 02 datasheet

FSR BMS 1032 Installation and operating manual

FSR

FSR BMS 1032 Installation and operating manual

MuxLab 500056-PRO Quick installation guide

MuxLab

MuxLab 500056-PRO Quick installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.