www.belimo.com CRA24-... • en-gb • 2013-05-15 • Subject to changes 7 / 24
Technical data sheet CRA24-..
Technical data
Electrical data Nominal voltage AC 24V 50/60 Hz
Dimensioning 3 VA, without actuators
Power supply range AC 19.2 … 28.8V
Connections Terminal block 1 … 3: 2.5 mm2
Terminal block 4 … 12: 1.5 mm2
Functional data Control characteristics P
– P-Band Selectable: 1.5 K or 3.0 K
External temperature sensor (ai1) Type NTC, 5 k�, power supply range 10 … 45°C
e.g. Belimo Type TFK
Setpoint Adjustment range 15 … 36°C (Default 21°C)
– Energy hold off (EHO) Heating –2 K
Room temperature (frost protection) 14°C
Max. room temperature monitoring 28°C
Operation
– Mode switch and status display (LED) COMF (green) – MIN (orange) – MAX (red)
– Rotary knob for setpoint adjustment 30 … 70% air / ±3 K temperature
Communication connection for field devices 2 x PP (for PC-Tool, ZTH-GEN, etc.)
Inputs 1 x analogue, 3 x digital
– External temperature sensor (ai1) Type NTC, 5 k�, power supply range 10 … 45°C
– Digital inputs (di1, di2, di3) Contact load 10 mA
Output 3 x analogue or digital
– Supply air VAV system output (ao1) 2 … 10V, max. 5 mA
– Exhaust air VAV system output (ao2) 2 … 10V, max. 5 mA
– Heating output (ao3) 2-point / 3-point, AC 24V, source current max. 0.5 A
/ 10 VA (optimised for actuators with approx. 150 s
running time)
Norms and Standards Protection class III Safety extra-low voltage
Degree of protection IP30 (EN 60529)
Mode of operation Type 1 (EN60730-1)
Software class A (EN 60730-1)
EMC CE according to 2004/108/EC
Ambient conditions
– Operation 0 … +50°C / 20 … 90% r.h. (non-condensing)
– Transport and storage –25 … +70°C / 20 … 90% r.h. (non-condensing)
Dimensions / weight Dimensions (H x W x D) 99 x 84 x 32 mm
Weight 105 g
Housing colours Baseplate NCS2005-R80B light grey (corresponds approximately
to RAL 7035)
Cover RAL 9003 Signal white
Room controllers for controlled apartment
ventilation with three outputs:
• Analogue output ao1: Supply air device
– VAV unit or damper actuator
• Analogue output ao2: Exhaust air
device
– VAV unit or damper actuator
• Output ao3: 2-point (on/off) or 3-point
signal for a heating valve
Safety notes
• The controller is not allowed to be used outside the specified field of application, especially
not in aircraft or in any other airborne means of transport.
• It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
• The device does not contain any parts that can be replaced or repaired by the user.
• The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
Device variant
Type CRA24-B3P, same functions as the CRA24-B3,
but with a hidden user interface.
Technical data sheet CRA24-B3(P)