BERG BME461 User manual

Berg GmbH
Frauenhoferstraße 22
82152 Martinsried, Germany
Phone +49 379 160 - 0
Fax +49 379 160 - 199
E-Mail [email protected]
www.berg-energie.de
Operating Instructions
3-349-868-74
3/8.18
Edited in Germany • Subject to change without notice • PDF version available on the Internet
Electronic
Energy Meters
Efficio Certified
Direct Meter BME
Transformer Meter BME
1ScopeofDelivery
1Energymeter
2 Operating instructions (German and English)
Operating instructions can be found at www.berg-energie.de
2 Safety Precautions – Symbols
– Check the specified nominal voltage on the serial
plate before placing the instrument into service.
– Observe maximum pulse output voltage.
– When wiring the instrument, make sure the connec-
tor cables are not damaged, and that they are volt-
age-free.
– If it can be assumed that safe operation is no longer
possible, the instrument must be immediately
removed from service (disconnect input voltage!).
Safe operation can no longer be relied upon if the
instrument demonstrates visible damage.
The device may not be placed back into operation
until troubleshooting and repair have been per-
formed, and calibration and dielectric strength have
been tested and approved at our factory or an autho-
rized service center.
– Voltage conducting parts may be exposed if the
cover is opened.
If balancing, maintenance or repair of a live open
instrument is required, this may only be carried out by
trained personnel who are familiar with the dangers
involved.
– When connecting measuring current, it is important
to provide for low-ohmic contact and to select an
appropriate conductor diameter.
Meanings of Symbols on the Instrument
DE MTP 18 B 004 MI-003 (Direct Meter)
DE MTP 18 B 005 MI-003 (Transformer Meter)
Prototype test certificate
Total insulation,
protection class II device
Warning concerning a point of danger
(attention, observe documentation!)
This device may not be disposed of with the
trash. Further information can be accessed on
the Internet at www.berg-energie.de.
Metrology mark
with indication of year (M18) and register
no. of the notified body for module D,
country-specific calibration validity period
Marking with stamp of the federally approved
test laboratory
(for recalibration only)
Tamper-Proof Sealing – Opening the Meter / Repairs
Tamper-Proof Calibration Sealing
with Manufacturer’s Seal
(at the side)
If the manufacturer’s seal is damaged or removed, all
guarantee claims are rendered null and void.
The meter may only be opened by authorized, trained per-
sonnel in order to ensure flawless operation and to assure
that the guarantee is not rendered null and void.
If it can be ascertained that the
meter
has been opened
by unauthorized personnel, no guarantee claims can be
honored by the manufacturer with regard to personal
safety, measuring accuracy, compliance with applicable
safety measures or any consequential damages.
Tamper-proof sealing for the terminal cover may be
attached either to the left or the right of the terminal
cover.
3 Rating Plate Entries
4 Connector Pin Assignments and Wire Gauge
Note: Observe the wiring diagrams in the top and bot-
tom terminal covers.
Meas. Inputs, Direct Meter (top & bottom terminals)
Meas. Inputs, Transformer Meter (bottom terminals)
Connections (top terminals)
5 Pulse Output
Default setting: active energy
Terminal 23 (S01) import, terminal 25 (S02) export
* Type of energy can also be selected with feature Impuls.
Underlined values are default values.
* Pulse rates are based on secondary side
!
M18
1948
EBY
8
18
Connections Direct Meter Transformer Meter
Current input Solid wire ≤ 16 sq. mm
Fine wire ≤ 25 mm2or
≤
16 mm
2
with wire end ferrule
Tightening torque:
3-4 Nm
Solid wire ≤ 4 sq. mm
Tightening torque:
0,5-0,6 Nm
Voltage input
N: solid wire
≤
2.5 sq. mm
Tightening torque:
0,4 Nm
Solid wire ≤ 4 sq. mm
Tightening torque:
0,5-0,6 Nm
SØ pulse output
Bus output, tariff input
(power utility pulse)
Solid wire ≤ 2.5 sq. mm
Tightening torque:
0,4 Nm
Solid wire ≤ 2.5 sq. mm
Tightening torque:
0,4 Nm
TCP/IP
RJ45 (8P8C)
Prototype test certificate
Accuracy class / operating temperature
← Energy export / → energy import
Nominal voltage
Imin - In (Imax.) / nominal frequency
Warning
Protective insulation
Symbol for system type
Yea r o f ma n uf a ct u re
Metrology mark
LED constant
2D code
EBY
8
18
Serial number
Up key
Enter key
Anti-reversing for
the registers in both
energy directions
Bidirectional meter
L2
L1
L3
Voltage Voltage
Current Current Current
Voltage
CurrentCurrent Current
N
Voltage Voltage Voltage
Current Current Current
L3
L2L1 N
Current
CurrentCurrent
Tar if f
Connections
W1: LON
W2: M-Bus
W4: TCP/IP
W7: Modbus RTU
V1 ... 9: SØ pulse output Tb Tn Ta
TCP/IP
Pulse Rates programmable V2
Direct Meter
1 …1000 Imp/kWh
Transformer *
CT, VT progr.
1
...
1000
...
50000Imp/kWh
RL
+
24
23/25
U
t
Energy type*
Max. 40 V
24 V DC
I = max. 27 mA
U
External Voltage Source
Standard pulse duration: 30 ms + 5%, interpulse period: > 30 ms
V7/V8 pulse duration: 130 ms + 5%, interpulse period: > 130 ms
6 Display and Control Panel
6.1 Test LEDs
The
test LEDs
are located above the control keys. The left-
hand LED indicates energy export, and the right-hand LED
energy import. LED blinking frequency increases along
with measured power. If all currents are smaller than start-
ing current, both LEDs light up continuously.
LED Constant
Direct Meter: 10,000 pls/kWh
Transformer Meter: 100,000 pls/kWh
6.2 Resolution, Main Display (large characters) Energy Import
Intern wird mit erhöhter Auflösung gezählt. Hierdurch kann bei
Mehrtarifnutzung das Gesamtregister in der letzten Stelle
einige Digit über der Summe der Einzelregister liegen.
* An additional place to the right of the decimal point is included
for the calibration display in the case of a main display which
can be calibrated. And thus the leading digit is eliminated in
the case of an 8-place display.
** Due to programmable CT, VT only the secondary display can be
calibrated. Therefore, display overflow is based on the secondary
display. The normal display is shifted one place to the left if neces-
sary.
6.3 Meanings of Symbols at the LCD
uMain display
, not calibrated
(programmable CT/VT, see section 6.2).
T1 ... T8: active tariff
Display of instantaneous power in 4 quad-
rants: positive or negative active power P,
positive or negative reactive power Q.
Correct connection:
Continuous illumination of the phase symbols
where P
≥
0
Phase failure:
Symbol for affected phase is cleared from the display.
Incorrect phase sequence:
Phase symbols blink in following order: 3 - 2 - 1.
Negative power:
Respective phase symbol blinks.
For bus connection: appears when
the meter transmits a data packet.
Key symbols for parameters configuration
(see next column)
Key Symbols for Parameters Configuration
for Feature Q1 and V2:
Key and 2nd key bit blanked:
Parameter CT, VT and SØ configurable according
to features, disabling with enable key.
Key displayed with one bit:
Parameter CT, VT and SØ disabled,
change after activating the enable key.
6.4 LCD Background Illumination
Background illumination is activated each time a key is
activated. Background illumination goes off after about
2 minutes.
Background illumination colors indicate various display
menus:
– White: query menus
– Red: display of firmware version
– Pink: parameters display and setting menu
– Blinking red: in case of error
6.5 Key Operation
Querying Parameter Values
In addition to the LCD test, the UP and ENTER keys also
make it possible to query currently set parameter val-
ues, as well as to change parameters for certain fea-
tures after first pressing the enable key (located behind
the top cover).
If no keys are pressed for a period of 1 minute, the
meter is returned automatically to its standard display.
Parameters can be changed for the following meters:
Parameters CT and VT for Transformer Meter,
Parameter SØ for Pulse Meter.
Further parameters in accordance with interface descri-
tion.
a) Enabling Parameter Changes
The enable key makes it possible to enable or disable
parameter changes. It’s located underneath the top ter-
minal cover between terminals 21 and 22 and is acti-
vated with a pointed object (e.g. a ballpoint pen).
Pressing the enable key activates the “change parame-
ters” operating mode (key off):
Pressing the enable key again disables the “change
parameters” operating mode (key on):
If no keys are pressed for a period of about 2 minutes,
the “change parameters” operating mode is exited auto-
matically and disabled (key on).
b) Changing Parameter Values
➭Briefly press the enabling key as described in point
a) above (this activates the “change parameters”
operating mode).
➭See the operating overview on the back with regard
to changing the parameters.
➭Press and hold the ENTER key until the firmware ver-
sion appears (red background).
➭Press the UP key. The display test appears.
Briefly press and hold the ENTER key in order to dis-
play two further test patterns.
➭Then repeatedly press the UP key until the parame-
ter to be changed appears at the display.
➭Briefly press the ENTER key in order to access the
setting menu.
➭The input cursor blinks at the leftmost entry posi-
tion. Each tine the ENTER key is pressed the cursor
is advanced to the next position to the right. The
value of the blinking digit can be increased by
pressing the UP key. When the rightmost digit is ac-
knowledged by pressing the ENTER key, the se-
lected value is accepted and SAVinG appears
briefly at auxiliary display 2. If no keys are pressed
for a period of about one minute, the setting menu
is exited.
➭Press and hold the ENTER key or wait for one minute
in order to change to the normal display.
➭Press the enable key once again. This disables the
“change parameters” operating mode.
Disabling takes place automatically after 2 minutes.
Meter CTxVT
min.
CTxVT
max.
Normal dis-
play
Calibration
display *
Unit
Direct
Meter — — 123456,78 23456,789 kWh
Tra ns
for-
mer
meter
Q1
**
1 4 u12345,67 ** kWh
5 40 u123456,7 ** kWh
41 400 u1234567 ** kWh
401 4000 u12345,67 ** MWh
4001 40000 u123456,7 ** MWh
40001 100000 u1234567 ** MWh
Main display
(active energy* in kWh or MWh)
Auxiliary display 1 (active power* in kW or MW)
* Transformer meter: CT and VT are taken into account
Auxiliary display 2 (e.g. IN, OUT for import or export)
In case of error: error code alternates with current display
(reactive energy* in kVArh or MVArh)
(reactive energy or power in kVAr(h) or MVAr(h)*)
Power: negative sign for export
Enable Key
→
→
Repair and Replacement Parts Service
Recalibration
Recalibration can be conducted at any time by our fed-
erally approved test laboratory.

7 Switching Amongst Tariffs
Hardware Controlled
Tariff inputs Ta and Tb are each connected with refer-
ence to Tn.
Level 0: < 12 V
Level 1: > 45 V (max. 265 V permissible!)
Software Controlled (not included in MID scope of approval)
In the case of meters with bus connection, four further
tariffs can be selected (software controlled).
8 Overview of Bus Systems
–
LON-Bus
–M-Bus
– TCP/IP (BacNet IP/Modbus TCP)
–ModbusRTU
Interface descriptions for energy meters with bus connection
can be found on the Internet at www.berg-energie.de.
9 Error Messages – Reset
Display
If an error occurs, the respective error code and active
energy or instantaneous power are displayed alter-
nately.
LOVoLt error
In case of LOVoLt error (phase voltages too low), back-
ground illumination, and if applicable the bus connec-
tion, are deactivated. The load profile (feature load pro-
file) cannot be viewed as long as the error is pending.
10 Repair and Recalibration
Note for Test Laboratories
Direct measuring meter: Testing is only possible with
source which supply currents superimposed on volt-
ages.
Calibration Display
Display of energy values with increased resolution can
be selected for testing or calibration purposes.
➭Press and hold the ENTER key once to this end. The
firmware version is displayed with a red back-
ground.
➭Press the UP key twice. The calibration display ap-
pears with a pink background.
Resolution depending on display, see section 6.2.
Recalibration can be conducted at any time by a feder-
ally approved test laboratory (e. g. EB-8) (see repair and
service address on the back of the folder).
Calibration capability is valid for 8 years in Germany.
11 Manufacturer’s Guarantee
The energy meters are guaranteed for a period of 3
years after shipment. The manufacturer’s guarantee
covers materials and workmanship. Damages resulting
from use for any other than the intended purpose or
operating errors, as well as any and all consequential
damages, are excluded.
12 Ambient Conditions
13 Return and Environmentally Sound Disposal
The BME meter is a category 9 product (monitoring and
control instrument) in accordance with ElektroG (Ger-
man electrical and electronic device law). This device is
subject to the RoHS directive.
We identify our electrical and electronic
devices in accordance with WEEE 2012/19/EU
and ElektroG using the symbol shown at the
right per DIN EN 50419.
These devices may not be disposed of with the trash.
Please contact our service department regarding the
return of old devices.
14 Declaration of Conformity, Direct Meter 15 Declaration of Conformity, Transformer Meter
Tariff Input Tb Ta
Tariff 1 0 0
Tariff 2 0 1
Tariff 3 1 0
Tariff 4 1 1
Error Code Meaning Cause / Remedy
0L0volt Phase voltage < 75% Check connection
0VHi1 Maximum value for U1
exceeded
Check connection
0 VHi 2Maximum value for U2
exceeded
Check connection
0 VHi3 Maximum value for U3
exceeded
Check connection
1Hi1 Maximum value for I1
exceeded
Check connection
1Hi2 Maximum value for I2
exceeded
Check connection
1Hi3 Maximum value for I3
exceeded
Check connection
0SYnc Frequency measuring
error
Meter connected to direct
voltage
0C0m Interface error
Check connection
EnErgY Meter defective
Send device to
repair service
0cALib Balancing required
0
AnALog
DC offset too high
!
!
!
!
!
!
!
!
!
!
!
!
Operating temperature range –25 ... +55 °C
Storage temperature range –25 ... +70 °C
Relative humidity < 75% annual average
Elevation to 2000 m
Deployment Indoors
mechanical classification M1
electromagnetical classification E2
Protection (built-in device) front panel: IP 51
Protection terminal area IP20
12345.678
4567
kWh
W
1na
Calibration
Firmware
Normal display
Pulse rate
Pulse Duration
Feature V2/V4
Feature V2/V4
12345.678
678
kVArh
VAr
1
nR
CT
VT
112345
.
6
7
8
4567
kWh
W
0uta-
12345
.
6
7
8
678
kVArh
VAr
0utR-
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
1n
Reactive energy import, total
1123
4
21
234
W
31
234
Active power / phase
1230
.
0
2
230
.
4
V
3230
.
4
Phase voltages
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
0ut
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 0ut
Export, total
Active energy import, total
Tariff (T1)
Tariff (T1)
Power displays
11234
2
1234
VAr
31234
11234
2
1234
VA
31234
1234
1234
VA
VAr
1234
Reactive power / phase
Apparent power / phase
Total power
Mains monitor
12 400
.
4
23 400
.
4
V
31 : 400
.
4
Line-to-line voltage
Switching Between Active and Reactive Energy – Display Tests – Calibration Display – Setting Transformer and S0 Interface Parameters Switching Amongst Tariffs, Active and Reactive Energy, as well as Power Displays and Mains Monitor, Optional Display of the Load Profile
1Total active power (kW) appears at auxiliary display 2
2Not approved for billing purposes in Switzerland
Measuring Function Feature
Measured Quantity Accuracy M3 2
Active energy (kWh)
1
EP1...EP8, EPtot ±1% •
Reactive energy (kVArh)
EQ1...EQ8, EQtot
±2% •
Star voltage (V) U1N, U2N, U3N0.5% ±1 d •
Delta voltage (V) U12, U23, U13 0.5% ±1 d •
Current per phase (A) I1, I2, I3 0.5% ±1 d •
N conductor current (A) IN
1%
±
1 d, typ.
•
Active power (kW) P1, P2, P3, Ptot 1% ±1 d •
Reactive energy (kVAr) Q1, Q2, Q3, Qtot 1% ±1 d •
Apparent power (kVA) S1, S2, S3, Stot 1% ±1 d •
Power factor
(cos phi)
PF1, PF2, PF3,
PFtot
1% ±1 d •
Frequency (Hz) f0.05% ±1 d •
RMS distortion value THD U1, U2, U3 •
THD I1, I2, I3 •
Blinking cursor
Identifies the current entry position. Position
selection via ENTER.
The value at the cursor position can be
changed with the UP key (upward arrow).
Abbreviations
ct Transformation ratio, current
INN conductor current (calculated)
SØ SØ pulse output
THD Distortion component (for voltage and current)
vt Transformation ratio, voltage
Features
M3 Multifunctional variant:
measurement of U, I, P, Q, S, PF, f, THD, In, reactive energy
Q1 Programmable transformation ratios
V2 Programmable SØ
W1 ... 7 Bus connections
Keys
ENTER key (press briefly)
ENTER key (press and hold)
UP key (press briefly)
long
Pulse source
4 pulse sources for pulse outputs SØ1 and SØ2:
– Active energy import (+) kWh or export – kWh
– Reactive energy import (+) kVAr or export – kVAr
2 states: SØ switch “Closed” or “0pen”
Operating Overview
W
Feature V2/V4
Transformation ratios (Transformer Meter only)
Feature bus connection: T5 ... T8
Active energy import
Active energy export
Fixed display and illumination – live values
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
1n
Active energy import, total
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
0ut
Active energy export, total
2 additional
Display test
Pulse rate
Number of pulses to be
read out per kWh
Pulse duration
Duration of the pulse for the on state or the high
value: at least 30 ms, e.g. 70 ms in case of
processing problems
version
1.00
2345.6789
1234.5678
kWh
kWh
1234 W
2345.6789
1234.5678
kWh
kWh
hold
10000
ct
10000
ct
set
1000
ut
1000
ut
set
50 1000
per kWh
50 1000
per kWh
set
50 0.100
sec
50 0
.
100
sec
set
50 srC1/2
+ / –kWh
50 srC1/2
+ / –kWh
set
SØ pulse output**
test patterns
8888:88:88
8888:88:88
kWh
kWh
88:88:88
Information for manufacturing
All Tariffs *
Active tariff (here T1)
Reactive energy import, total Reactive energy export, total
Reactive energy, capacitive
Reactive power, capacitive
Active energy export
Active power export
Reactive energy, inductive
Reactive power, inductive
Active energy import
Active power import
* Max. 4 tariffs with S0
or 8 tariffs with bus
T1 T1 T1 T1 T1T3 T1T3
T2T4 T2T4
long
** See corresponding interface description for additional menus in case of bus connections.
Transformer Meter: Programmable CT, VT
T1T3
T1T3
T1
T1
pf1: 1
.
00
2
: 1
.
00
3: 1
.
00
Power factor / phase
pf : 1
.
00
50
.
00
H
z
Power factor
T1
T1
T1
T1
T1
T1
11
.
234
2
1
.
234
A
31
.
234
1n1
.
234 A
50
.
00
h
z
kW
dv1: 0
.
120
2
: 0
.
042
3: 0
.
050
THD U1, U2, U3
d11: 0
.
476
2
: 0
.
120
3: 0
.
092
THD I1, I2, I3
T1
T1
T1
T1
T1
T1
Phase currents
Line frequency
4-wire only4-wire only
4-wire only4-wire only4-wire only4-wire only
Active Tariff (here T1)
3/4-wire
2-wire
1234
1234
VA
VAr
1234
Apparent/reactive/active power
W
pf : 1
.
00
50
.
00
H
z
Power factor
T1
T1
123
.
4
1
.
234
V
A
50
.
00
H
z
Voltage/current/frequency
dv : 0
.
028
d1 : 0
.
082
THD U, I
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t2: 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t2: 0ut
Tariff (T2)
Tariff (T2)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t3: 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t3: 0ut
Tariff (T3)
Tariff (T3)
T1
T1
long
→
→
→
→
→
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 1n
Reactive energy
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 0ut
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t2: 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t2: 0ut
Tariff (T1)
Active energy
Tariff (T2)
Tariff (T2)
Feature bus connection: T5 ... T8
T1
T1
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t3: 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t3: 0ut
Tariff (T3)
Tariff (T3)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t4: 1n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t4: 0ut
Tariff (T4)
Tariff (T4)
T1
T1
T2T4
T2T4
Q1: secondary calibrated
Tariff (T1)
N current (4-wire only)
display
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.4
3.8.4
2.8.4
4.8.4
OBIS
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.0
3.8.0
2.8.0
4.8.0
This manual suits for next models
7
Other BERG Measuring Instrument manuals