IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
WARNING: Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes
and standards.
WARNING: When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
CAUTION: The installation of a Big Ass Fan must be in accordance with the requirements specied in this installation manual
and with any additional requirements set forth by the national electric code (NEC), ANSI/NFPA 70-2011, and all local codes.
Code compliance is ultimately YOUR responsibility!
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect. Wait
3 minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death. NOTE:
Darkened display LEDs are not an indication of safe voltage levels.
CAUTION: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous
power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans if you have any
questions regarding the electrical installation of this fan.
WARNING: To reduce the risk of re, electric shock, and injury to persons, Big Ass Fans must be installed with Big Ass
Fan supplied controllers that are marked (on their cartons) to indicate the suitability with this model. Other parts cannot be
substituted.
CAUTION: When service or replacement of a component in the fan requires the removal or disconnection of a safety device,
the safety device is to be reinstalled or remounted as previously installed.
WARNING: Risk of re, electric shock, or injury to persons during cleaning and user-maintenance! Disconnect the appliance
from the power supply before servicing.
WARNING: Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
WARNING: Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten
a prominent warning device, such as a tag, to the service panel.
CAUTION: Do not bend the airfoils when installing, adjusting, or cleaning the fan. Do not insert foreign objects between
rotating airfoils.
WARNING: Stay alert and use common sense when installing fans. Do not install fans if tired or under the inuence of drugs,
alcohol, or medication. A moment of inattention while installing fans may result in serious personal injury.
CAUTION: The installation of this fan requires the use of some power tools. Follow the safety procedures found in the owner’s
manual for each of these tools and do not use them for purposes other than those intended by the manufacturer.
CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure caused by improper installation.
Leave this installation guide with the owner of the fan after installation is complete.
WARNING: This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of
the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the
appliance.
ATTENTION: If installing the fan in the United States, the fan must be installed per the following National Fire Protection
Association (NFPA) guidelines:
• The fan must be centered approximately between four adjacent sprinklers.
• The vertical distance from the fan to the sprinkler deector must be at least 3 ft (91.4 cm).
• The fan must be interlocked to shut down immediately upon receiving a waterow signal from the alarm system.