Blue Ridge Retrofit Kit 2 User manual

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 1
Hardware Installation and Setup Instructions
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 2
Table of Contents
Overview
Document
Component
Assembly
Dimensions
Preparation
Mounting
Connection
Controller Setup
Optional Equipment
RK Conguration Worksheet
Visit www.BRTint.com/tandc.html for Terms and Conditions of Sale
3
3
3
4
4
4
5
8
9
10
Attention
This section serves as a notice of the immediate or potential dangers involved when working with the equipment described throughout this manual. Any
person involved in installation, maintenance, or service of the equipment should rst carefully examine the equipment and read the instructions contained
in this manual to ensure that personal and/or equipment injury is avoided.
The following safety messages appear throughout this manual to alert of immediate or potential danger to life as well as property.
Disclaimer
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designated to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will
be required to correct the interference at his own expense.
Instructions contained in this user’s guide should be performed only by qualied persons in accordance with local and national codes. Blue Ridge
Technologies International, LLC and its afliates assume no responsibility for any consequences related to the improper use of this manual.
Note : Indicates an important note.
Tip : Indicates a helpful tip or trick.
Safety Reminder : Applicable safety instructions will be included with this symbol.
DANGER : Indicates an immediately hazardous situation which ,if not avoided, will result in serious injury or death.
WARNING : Indicates a potentially hazardous situation which ,if not avoided, may result in serious injury or death.
CAUTION : Indicates a potentially hazardous situation which ,if not avoided, may result in minor or moderate injury.
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 3
Overview : Document
This document provides mounting and connection instructions for the following Blue Ridge Technologies Retrot Kit (RK) products:
Retrot Kit 2 (RK2)
RK2 is compatible with Douglas Panels (WR-6221, 6161, 6162, 6172, 6321) and ILC Panels (2PC).
Sections of this Install Guide apply to optional equipment and may not be applicable. See the Optional Equipment section for details.
Siemens’ P1 and Automated Logic Corporation’s BACnet ARCnet protocols are only available to authorized integrators.
For RK integration with a Building Automation System (BAS) as well as software conguration refer to the Application Guide.
Overview : Component
The RK2 includes the following items :
1 - Controller
2 - Relay Interface Boards (RIB-A) with (16) Relay Outputs
2 - Relay Interface Boards (RIB-B) with (16) Relay Outputs
2 - 16-20pin Ribbon Cables
2 - 16pin Ribbon Cables
1 - BT485 BAS Network Terminator (BT485 Terminator)
Overview : Assembly
1. Mounting Fastener Point
2. Mounting Plate
3. Controller
4. RIB
RIB Identication
5. RIB-A (Outside Ribbon Cable Socket)
6. RIB-B (Inside Ribbon Cable Socket)
(Figure 1)
Disconnect line voltage power before performing RK installation.
All circuits must be tested for wiring errors and shorts prior to RK installation.
Before handling any RK components, the technician should be grounded to prevent
circuit board damage.
DO NOT apply control power to the RK Relay Outputs. Remove any power source
from the control side of the relays prior to RK installation.
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 4
Overview : Dimensions
Preparation
Remove the existing control system.
1. Disconnect power from the panel.
2. Label all low voltage leads.
3. Unfasten or cut existing low voltage leads. Do not cut existing leads too short.
4. Unfasten and remove existing controller electronics. Remove any power source from the control side of the relays.
5. Remove any dust or debris from low voltage bay of the panel.
Mounting
Grouping Strategy
Retrot Kits permit soft-wiring Inputs to Relay Outputs. This allows relays to be connected to any Relay Output terminal on the RIB while maintaining the
original system conguration. Soft-wiring is achieved by a software based Grouping method. The Input (switches, occupancy sensors, etc) is assigned
control of a Group. Each Group contains Relay Outputs (relays and related lighting circuits). Therefore, an Input commands its assigned Group and all
the Relay Outputs contained within that Group. These Group assignments may be congured to suit any application ensuring maximum exibility during
physical installation. Connections may be recorded utilizing the RK Conguration Worksheet. (See page 10)
Example:
Original Conguration
• Input 1 controls Relay 1
Retrot Conguration
• Due to panel arrangement Relay 1 is in close proximity to Relay Output 17 on RIB-B
• Therefore Relay 1 is connected to Relay Output 17.
• During software conguration Input 1 is assigned control of Group 1 and Relay Output 17 is placed in Group 1.
• The original conguration is maintained. Input 1 controls Relay 1 through Group 1.
Determine position of all components prior to installation. Consider these factors during this process.
• Ensure the all RIB’s are near the relays with which they will interface.
• RIB position should minimize cross-board wiring (relay control leads lying across boards).
• Ensure Controller is near the power, input, and network leads.
• Conrm the distance between the Controller, RIB’s, and Optional Equipment does not exceed the length of the ribbon cables.
• Allow a minimum of 0.75” (20mm) clearance between component mounting plates for ease of wiring.
The Retrot Kit may now be mounted in the low voltage bay.
1. Conrm power is disconnected from the panel.
2. Fasten the Controller in position utilizing self-tapping screws. Drive a screw through each Mounting Fastener Point. Keep the board clear of any metal
shavings. (Figure 1)
3. Repeat fastening procedure for each component required in the application.
4. Remove any metal shavings from the panel.
(Figure 2)
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 5
Connection
All low voltage leads are terminated on the Controller and RIB’s. These screw terminals accept a 0.4 x 2.5mm slot head screw driver. (Figure 3)
1. Conrm power is disconnected from the panel.
2. Complete ribbon cable terminations to connect Controller, RIB’s, and Optional Equipment. Disconnect power to the Controller before installing or
removing ribbon cables. Failure to do so could result in damage to the electronics.
a. Route cables in a neat fashion to prevent interference during remaining installation.
b. Connect the 16-20pin Ribbon Cables to the Controller.
c. Connect the 16pin Ribbon Cables to the 16-20pin Ribbon Cables.
d. Connect one RIB-A and one RIB-B per 16pin Ribbon Cable. Do not combine like RIB styles on a ribbon cable. The sequence of RIB-A and RIB-B
per ribbon cable is not specic.
3. Connect the relay control leads to the RIB’s Relay Output terminal blocks. DO NOT apply control power to the RK Relay Outputs. Remove any power
source from the control side of the relays.
a. Route leads.
b. Cut to length and strip as appropriate.
c. Insert stripped lead into screw terminal and tighten screw. Conrm the connection’s orientation. (Figure 4)
d. Repeat procedure for each relay.
4. Connect existing power, input, and network leads to the Controller.
a. Route leads.
b. Cut to length and strip as appropriate.
c. Insert stripped lead into screw terminal and tighten screw.
d. Repeat for each lead.
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
(Figure 3)
(Figure 4)
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 6
Connection
Power Specications (Figure 5)
Power In: 24VAC +/-10%, 30VA, 50-60 Hz
Auxiliary Out: 24VAC Full Wave Rectied
Digital Input Specications (Figure 6)
Digital Input: 24 two-wire inputs
Software Conguration: Maintained, state change, momentary on/off,
momentary on, or momentary off
Jumper Conguration: 8 input segments, dry contact (N) or 24VDC
externally powered (R)
Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry
Contact 500’(152m) or externally powered 1,000’(304m)
Analog Input Specications (Figure 8)
Analog Input: 6 three-wire 0-5VDC inputs
Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / 250’(76m)
Digital Input Special Case (Figure 7)
Douglas WR8501-88 and equivalent switches may be congured to
operate with RK2. This conguration eliminates the external power
supply and green LED while maintaining the red LED as a pilot light.
(Figure 5)
(Figure 6)
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
(Figure 7)
(Figure 8)
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 7
(Figure 9)
(Figure 10)
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Terminations : Low Voltage
BAS Network Specications
Topology: RS-485, 3 conductor (+, -, and shield), daisy chain wiring (no stars or t-taps)
Wire Requirement / Maximum Length: Belden 8760 / 4000’(1216m)
BACnet MS/TP
Baud Rate: DIP switch selectable 9.6K, 19.2K, 38.4K, or 76.8K
Device Prole: BACnet Advance Application Controller (AAC)
Address Range: 1 – 99 selectable with rotary dials
Unit Load: Full unit load, 32 devices per MS/TP segment
Points: See Application Guide and PIC Statement
N2
Baud Rate: DIP switch selectable 9.6K
Address Range: 1 – 255 selectable with rotary dials and DIP switch
P1
Baud Rate: DIP switch selectable 4.8K, 9.6K, 19.2K, or 38.4K
Address Range: 1 – 99 selectable with rotary dials
See Automated Logic Corporation’s ARC156 Wiring Technical Instructions for the latest BACnet ARCnet specications.
Install BT485 Terminator if RP is operated as end of line device(rst or last device on network). BT485 Terminator requires no specic orientation in relation
to the terminal.
See Controller Setup for Address and Protocol settings.
DDN Network Specications
Protocol: Digital Device Network (DDN)
Address Range: 1-60, DIP switch selectable
Topology: Daisy Chain Wiring (no stars or t-taps)
Wire Requirement: CL3P, 22AWG, 4 conductor, Unsheilded
Maximum Stations (w/o external power): 10 CTS-DDN
Maximum Length (w/o external power): 500’(152m)
Maximum Stations (w/ external power): 60 one-button, 30 two-button, or a combination for 60 buttons total
Maximum Length (w/ external power): 2,000’(610m)
Power / Draw: 24VDC / 15mA per CTS-DDN
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 8
Controller Setup
Controller conguration and RK testing are the nal steps of installation.
(Figure 11)
Setup
1. Conrm power is disconnected from the Controller and the Power /
Run LED’s are not illuminated.
2. Set the DDN Network Terminator Jumper if utilizing DDN Network.
Two devices on the DDN Network should be set for network
termination. If the Controller is the end-of-line, terminate the Controller
and the device at the opposite end of the network. If the Controller is
positioned at a mid-point on the network, terminate devices at the
opposite ends of the network either side of the Controller.
3. Set the Digital Input (DI) Jumpers.
4. Set the Baud Rate / Protocol Dip Switch for protocol and baud rate.
5. Set the Network Address.
Testing
1. Connect power to the Controller. Wait 10 seconds for power up.
2. Conrm normal LED operation.
Power LED: Solid illumination
Run LED: Continuous blinking
3. Press and release the Over Button. Conrm the Relays change state
On/Off.
4. Press and release the Over Button again. Conrm the Relays change
state On/Off.
5. Press and release the Auto Button to exit override mode.
6. Test procedure complete.
(Figure 11)
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 9
Optional Equipment
LEXP Specications (Figure 12)
Description: Digital Input Expansion Card
Digital Input: 32 two-wire inputs
Software Conguration: Maintained, state change, momentary on/off,
momentary on, or momentary off
Jumper Conguration: 8 input segments, dry contact (N) or 24VDC
externally powered (R)
Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry
Contact 500’(152m) or externally powered 1,000’(304m)
Dimensions: 6.00”(152mm)H x 4.50”(113mm)W x1.13”(29mm)D
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
(Figure 12)
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 10
RK Conguration Worksheet
RIB-A (1)
RIB-B (1)
RIB Terminal Number (Relay Output) Original Relay Number Area Controlled Original Input Number
1(1)
2(2)
3(3)
4(4)
5(5)
6(6)
7(7)
8(8)
9(9)
10(10)
11(11)
12(12)
13(13)
14(14)
15(15)
16(16)
RIB Terminal Number (Relay Output) Original Relay Number Area Controlled Original Input Number
1(17)
2(18)
3(19)
4(20)
5(21)
6(22)
7(23)
8(24)
9(25)
10(26)
11(27)
12(28)
13(29)
14(30)
15(31)
16(32)
Obsolete

B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 11
RK Conguration Worksheet
RIB-A (2)
RIB-B (2)
RIB Terminal Number (Relay Output) Original Relay Number Area Controlled Original Input Number
1(33)
2(34)
3(35)
4(36)
5(37)
6(38)
7(39)
8(40)
9(41)
10(42)
11(43)
12(44)
13(45)
14(46)
15(47)
16(48)
RIB Terminal Number (Relay Output) Original Relay Number Area Controlled Original Input Number
1(49)
2(50)
3(51)
4(52)
5(53)
6(54)
7(55)
8(56)
9(57)
10(58)
11(59)
12(60)
Obsolete