bolid S2000-OST User manual

ADDRESSABLE LED EMERGENCY SIGN BOARD
S2000-OST
INSTRUCTION MANUAL
mod. 00 “FIRE” mod. 04 “GAS KEEP OUT” mod. 08 Arrow Right Sign
mod. 01 “EXIT” mod. 05 “POWDER ESCAPE” mod. 09 Man / Arrow Left Down
mod. 02 “AUTO OFF” mod. 06 “POWDER KEEP OUT” mod. 10 Man / Arrow Right Down
mod. 03 “GAS ESCAPE” mod. 07 Arrow Left Sign mod. 11 “ESCAPE EXIT”
1TECHNICAL DATA
1.1 General
S2000-OST Addressable LED Emergency Sign Board (hereinafter referred to as the S2000-OST) is used to display alarm
messages of fire alarm systems, to identify escape routes and to display information.
The S2000-OST operates under a polling loop controller S2000-KDL (of version 2.15 and higher) or S2000-KDL-2I (of version
1.15 and higher) (hereinafter referred to as KDL) as part of an Orion integrated security system. The S2000-OST supports
DPLS_v2.00 Multiplex Addressable Polling Loop Protocol. A part of the lighting circuit with a power supply is galvanically isolated
from the control circuit of the polling loop. Electromagnetic compatibility of the S2000-OST meets the requirements of the third
immunity level accordingly to Russian standards. The version of S2000-OST firmware is v.1.00.
S2000-OST is available with one of the following signs: “EXIT”, “FIRE”, “AUTO OFF”, “GAS ESCAPE”, “GAS KEEP OUT”,
“POWDER ESCAPE”, “POWDER KEEP OUT”, Arrow Left Sign, Arrow Right Sign, Man / Arrow Left Down Sign, Man / Arrow
Right Down Sign, “ESCAPE EXIT” or any customizable lettering/pictogram.
1.2
Specifications
1) Ingress Protection Rating - IP41
2) Climatic Category (Russian Industry Standard ОСТ 25 1099-83) - О3
3) Polling Loop Voltage - 8 to 11 V
4) Current Consumed from the Polling Loop - 0.5 mA
5) Lighting Circuit Power Voltage - 12 to 24 V
6) Current Consumed from Lighting Power Supply
–12 V - 25 mA max
–24 V - 13 mA max
7) Galvanic Isolation between the PL and Lighting Circuit - Up to 4 kV
8) Operating Temperatures - Minus 30°Сto +55°С
9) Relative Humidity - Up to 93% at +40°С
10)Transportation and Storage Temperature - Minus 50°Сto +55°С
11) Overall Dimensions -303.3 mm
×
112.5 mm
×
36 mm
12) Weight - 240 gram
13) The content of precious materials: no need to account for the storage, disposal and recycling. (Clause 1.2 of ГОСТ 2.608-78).
1.3 Standard Delivery
–S2000-OST LED Sign Board – 1 pc.;
–Instruction Manual – 1 pc.;
–Woodscrew 3×25 – 2 pcs.;
–Wall Plug (for 3x25 woodscrew) – 2 pcs.;
–Woodscrew 4×40 – 2 pcs.;
–Wall Plug (for 4x40 woodscrew) – 2 pcs.;
–Packing – 1 pc.
2OPERATION DIRECTIVES
2.1 External Connection Diagram and Mounting
The figure shows the typical connection diagram for
the S2000-OST. The S2000-OST is designed to operate
within premises. The power supply for lighting circuit
must be battery backed.
The S2000-OST operates under a KDL and all
operation conditions (a control program, activation
time, activation delay) are defined in the KDL
configuration by means of UProg. To use the S2000-OST, the relevant addressable device type for the S2000-OST address must be
selected by means of UProg and, if necessary, the relevant links between inputs and outputs of the KDL must be defined. To get more
information about addressable device types and configuration parameters, please refer to user’s manuals for KDL, S2000M, and
Orion Pro software.
addressable
device
addressable
device
+PL
−
PL
+PL
−
PL
S2000
-
OST
XT1
XT2
1
2
3
4
1
2
3
4
0
+12/24V
+12/24V
0
to the power supply
S2000
-
KDL
+PL
−
PL

2.2 Auxiliary LED Performance
There is an auxiliary green LED on the PCB which indicates the S2000-OST status as shown in table below.
Flashes once per four seconds Norm
Flashes four times once per four seconds The S2000-OST is being programmed with an address
Solid light The S2000-OST is waiting for establishing communication with the KDL.
A proper combination of presses on the button to change address has been
performed
Others Trouble
2.3 Assigning an Address
The S2000-OST stores its polling loop address in its non-volatile memory. The factory value of the loop address of the S2000-
OST is 127. To assign a new polling loop address to the S2000-OST, one of the following commands should be given to the KDL
from the S2000M panel or PC:
–Program Device with Address;
–Change Device Address.
The command Program Device with Address provides assigning a polling loop address to an S2000-OST without regards to which
address is assigned to it at the time. It can be required when the same address is assigned to two or more addressable devices. Give a
command for assigning the specific address from the S2000M panel or PC. Then within no more than 5 minutes perform on the
S2000-OST PCB a combination of three long presses (between 1 s and 3 s) and one short press (less than 0.5 s) on the button – (long-
long-long-short). In this case the panel or PC displays events about missing the device with an old address and connecting the device
with the new address. If several devices had the same address before assigning then no messages about missing devices with the old
address is displayed.
If it is necessary to change address of a device which address is known then the Change Device Address command should be
selected. Give a command to change address specifying the old and new addresses as parameters from the S2000M panel or PC. The
panel or PC shall display events of loss of communication with the device with the old address and connecting the device with the
given address.
2.4 Testing
2.4.1Before testing notify the proper authorities that the equipment is undergoing maintenance and will be temporarily out of
service. Disconnect all outputs of control devices and executive modules that can run an automated fire-fighting system.
2.4.2Apply power to the KDL and to the S2000M panel or PC. Remove the front cover from the S2000-OST and ensure the
auxiliary LED on the PCB shows solid light. When communication with the KDL has been established the auxiliary LED starts
flashing once per four seconds indicating normal conditions.
2.4.3Simplified testing is carried out by pressing on the button on the S2000-OST PCB three times for a short time (shorter than
0.5 s) and then for a longer time (between 1 s and 3 s) – (short-short-short-long). After that the auxiliary LED shall flash 10 times.
2.4.4Then test operation of the S2000-OST as part of the system by giving the S2000-OST output control commands. The system
shall integrate an S2000M control panel or a PC with Orion Pro software installed and a KDL polling loop controller.
2.4.5When testing has been completed ensure that the S2000-OST is ready for operation. Restore all binds between system
executive outputs and automated fire-fighting systems and notify the proper authorities that the system is back in operation.
When testing, please be sure all the equipment is known to be operable.
3MANUFACTURER DATA
The Bolid Company, Russia
Address: 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia
Tel./fax: +7 (495) 775-71-55 (multi-channel), +7 (495) 777-40-20, +7 (495) 516-93-72
4CERTIFICATES
4.1 S2000-OST Addressable LED Emergency Sign Board is approved by Conformity Certificate No. C-RU.ЧС13.В.00516.
4.2 Conformity Certificate ТС №RU Д-RU.МЕ61.В.00610 certifies that S2000-OST Addressable LED Emergency Sign Board
meets the requirements of Technical Regulations of Custom Union TR CU 020/2011.
4.3 Production of S2000-OST Addressable LED Emergency Sign Board is certified according to ГОСТ ISO 9001-2011 by a
conformity certificate No.РОСС RU.ИК32.К00153.
5PRODUCT ACCEPTANCE CERTIFICATE
The S2000-OST Addressable LED Emergency Sign Board (marked with its serial number on its case) is
qualified as proper for
operation and is packaged by CJSC NVP “Bolid”
.
Responsible for acceptance and packaging
QCD ________________________________ ________________________
Full Name Date, Month, Year