BrainQ RSC/2 User manual

8G.52.09.00/10.05
BrainQ RSC/2
BrainQ RSC/2 Thermostat
USER MANUAL

NL GB F I
English

GB
Contents
Control level
Display and operating instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-5
Operation - display - standard display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-6
Temporary change of room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-7
Operational mode selection for heating and hot water (Synoptic) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-8
Functions of operational modes (holiday, absent, party, automatic, summer, heating, reduced, standby) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-9
Plant information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-10
Info-time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-11
Programming level
Entry level overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-12
Programming of timeprograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-14
Page GB-3
8A520900_GB.qxp 11.11.2004 14:40 Seite 3

Copying of timeprograms (forming of blocks) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-16
Deletion of timeprograms – reloading of standard programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-18
Table for individual timeprograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-20
TIME-DATE level (time, year, month, day, weekday, automatic change of daylight saving time) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-21
Extended installer level (code input for levels SYSTEM, DHW, UNMIXED CIRC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-22
SYSTEM level (language selection, timeprograms, separate operation, summer ECO-temperature, return to standard display,
parameter reset) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-23
DHW level (night temperature, legionella protection, domestic hot water temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-27
UNMIXED CIRC level (nightly set back, room sensor display, room sensor function, heating curve adaptation, inrush optimization,
day temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-29
Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-35
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GB-37
Page GB-4
GB
8A520900_GB.qxp 11.11.2004 14:40 Seite 4

GB
Page GB-5
Display and operating instruments
Program selection key with corresponding
program symbols
Displaying operating information including
temperatures
LCD display
Rotary pushbutton
Time bar heating times
Actual room temperature
Date
Time
8A520900_GB.qxp 11.11.2004 14:40 Seite 5

GB
The centrally arranged rotary pushbutton and the keys labeled with symbols facilitate ease of operati-
on. It is, however, recommended to read this manual attentively to be informed about the repeating
steps.
– Each changeable value flashes in the display and can be changed by means of the rotary push-
button. A flashing display is appropriately highlighted in this manual.
Turn to the right (+) in clockwise direction: increasing values
Turn to the left (–) in anti-clockwise direction: decreasing values
– Press briefly: Acceptance of the selected and indicated value, store.
– Hold depressed for approx. 3 seconds: Entry into the programming level (level selection)
If the value is not saved with the rotary pushbutton after an operation step, the value adjusted
last is automatically accepted after approx. 60 seconds.
Turn: select, change
Press: confirm, store
LCD display
The control is equipped with a large display, all information appears in plain text and several lan-
guages are available (see page 23).
During commissioning of the installation or after a power failure a segment test with automatic error
diagnostic takes place, followed by the short-term indication of instrument type and software versi-
on.
Standard display
The subsequently appearing standard display shows day, date, time and room temperature. The time
bar above the date specifies the heating times. * The display will be in dutch (NL) Refere to pages
12, 22 and 23 to alter display to english
Symbolism used in this manual:
Page GB-6
Operation
2211..55
1166::3322
WWEE2255JJUUNN..;;0033
°C
mm
0246 10 12 18 2220
81416 24
Standard display
Actual room temperature
T1.30
RRSSCC--22
mmInstrument information
Software-Version
bb
15.05.
8A520900_GB.qxp 11.11.2004 14:41 Seite 6

Page GB-7
GB
Setting range: 5.0 ...30 °C
By short-term pressing of the rotary pushbutton in
the standard display the required room tempera-
ture can be corrected as shown in the opposite
schematic.
A room temperature correction can be made in the
operating modes AUTOMATIC, ABSENT and
PARTY. This change is only effective for the duration
of the current time block (of the set timeprogram).
After expiration of the corresponding time block,
the temperature is applied that was set in the next
time block of the timeprogram.
-221100
HHCC
RROOOOMMTTEEMMPP
°C
mm
Temperature
change
Accept
Temporary change of room temperature
current temperature setting
Tip: If it turns out that a temporary change of the room temperature is often necessary,
we recommend changing the standard temperatures in the time program.
8A520900_GB.qxp 11.11.2004 14:41 Seite 7

GB
Page GB-8
Operational mode selection for heating and hot water
AABBSSEENNTTTTIILL
SSTTAANNDDBBYY
22770088
HHOOLLIIDDAAYYTTIILL
0022
::
3300
PPAARRTTYYTTIILL
—P1
AUTOMATIC
33
—P1
AUTOMATIC
33
—P1
AUTOMATIC
33
HHEEAATTIINNGGRREEDD..HHEEAATTIINNGG
1199
::
4455
AABBSSEENNTTTTIILL
——
AAUUTTOOMMAATTIICC
—
DDHHWW
SSUUMMMMEERR
Entry into the currently active operational mode
22770088
1155::3300
HHOOLLIIDDAAYYTTIILL
0022
::
3300
1155::3300
1199
::
4455
1155::3300
PPAARRTTYYTTIILL
Select the desired operational mode
.
.
Holiday til ...
(HC=off, DHW=off)
Party til ...
(temporary
heating)
Summer DHW
(HC=off, DHW=off)*
Absent til ...
(temporary
set back)
Automatic (acc. to
time program)
Heating (HC=perma-
nent day temp.)
Set back (HC= perma-
nent night temp.)
Standby
HC=off,
frost protection active
With this button the required operational mode for heating and hot water circuit is selected. It appears in the text on the display, simultanously
an arrow at the lower edge of the display points to the appertaining program symbol.
Select: When pressing the operational mode selector button, the currently active mode is indicated by flashing. The other operational modes can be
selected and activated according to the following schematic.
33hhssmmuu
Tip:
To return to the automatic program (AUTOMATIC) from a
selected program quickly, press the program selection key
for 3 seconds until ‘AUTOMATIC’ appears in the display.
This activates the automatic program.
select, activate
set date or time
Activate program or return to standard display
* The program SUMMER DHW is not shown if a separate control of the HC
and the DHW has been selected (see page 9 and 24)
PPRROOGGRR..SSEELL..
8A520900_GB.qxp 11.11.2004 14:41 Seite 8

GB
Page GB-9
Function of operational modes (with common adjustment, see page 24)
Holiday til ...
(HC=off, DHW=off)
2244..0099
1199::2277
HHOOLLIIDDAAYYTTIILL
33hhssmmuu
1100::2277
AABBSSEENNTT
33hhssmmuu
1199::2277
PPAARRTTYY
33hhssmmuu
1199::2277
WWEE..2255..JJUUNN..;;0033
33hhssmmuu
1100::2277
SSUUMMMMEERR
33hhssmmuu
1199::2277
HHEEAATTIINNGG
33hhssmmuu
1199::2277
RREEDD..HHEEAATTIINNGG
33hhssmmuu
1199..00
1199::2277
SSTTAANNDDBBYY
33hhssmmuu
°C
2200..55
°C
2200..55
°C
2244..00
°C
2200..55
°C
Absent til ...
(temporary set back)
Party til ...
(temporary heating)
Automatic
(according to
time program)
Summer DHW
(HC=off, DHW=off)*
Heating
(HC=permanent
day temp.)
Red. heating
(HC=permanent night
temp.)
Standby
HC=off, frost protection
active
Setting range:
Curr. date ... Curr.
date + 250 days.
Return to the pre-
viously selected
operationalmode at
0.00 o’clock of the
set returndate.
The domestic hot-
water operation is
switched off in a
frost protected way.
Earlier return: Press
button ¢¢, adjust
and accept the desi-
red operational
mode by pressing
the rotary pushbut-
ton.
Timeprograms:
(s. pagee 19-20 time-
programs)
Automatic heating
and domestic hot
water operation acc.
to specified tempera-
tures and 3-Pro-
gram.
Programming of in-
dividual timepro-
grams see page 14.
Setting range:
P1: Interruption of
heating and domestic -
hot water operation
until the next activation
period (s. page 19-20
timeprograms)
0.5 ...24h: Short-term
interruption of the
heating and domestic
hot water operation up
to the set time.
Earlier return:
Press button ¢¢,
adjust and accept the
desired operational
mode by pressing the
rotary pushbutton.
Setting range:
P1: Continuation of
heating and domestic
hot water operation
until the next activation
period (s. page 19-20
timeprograms).
0.5 ...24h: Short-term
extension of heating
and domestic hot
water operation up to
the set time.
Earlier termination:
Press button ¢¢,
adjust and accept the
desired operational
mode by pressing the
rotary pushbutton.
Timeprograms:
(s. pagee 19-20 time-
programs)
Only hot water-
operation according
to settings of hot
water temperature.
(See p. 6) and 3 -
program.
Heating operation is
switched off and
frost protected.
Programming of in-
dividual timepro-
grams see page 14.
Permanent heating
and domestic hot
water operation (24
hrs) according to the
set daytemperature
and domestic hot
water temperature.
(Also see page 28)
Permanent reduced
heating and redu-
ced hot water ope-
ration (24 hrs) accor-
ding to the set night
temperature, redu-
ced operating mode
and domestic hot
water night tempe-
rature. (Also see
pages 34, 29 and
27)
Frost protected
shutdown of the
entire heating-
system (heating and
domestic hot water
switched off).
2200..55
°C
2200..55
°C
8A520900_GB.qxp 11.11.2004 14:41 Seite 9

GB
Page GB-10
Information button for the enquiry of the hea-
ting system, temperatures etc. The query is
made by turning the rotary pushbutton and
depends on the direction.
Turn clockwise:
shows all plant related temperatures first
– the actual values
– setvalues with rotary pushbutton depressed
Turn anti-clockwise:
shows information on heating and domestic hot-water
circuit first
– operational mode (holiday, absent, party, auto etc.)
– Timer program P1 (P2 or P3 after clearance)
– operational mode (daytime mode, reduced mode,
ECO mode)
– Identification (unmixed heating circuit HC, domestic hot
water DHW)
– Status of pump (On, Off)
shows the burner’s
– operational status (Off, On)
Information on temperatures etc.
(turn clockwise)
Examples:
Information on the heating system.
(turn in anti-clockwise direction)
Examples:
1133..55
OOUUTTSSIIDDEE
°C
Outside temperature*
OONN
HHCC
AAUUTTOODDAAYY
1144..55
88..00
OOUUTTMMIINN//MMAAXX
6655..00
HHEEAATTGGEENNEERR..
°C
°C
Outside temperature*
Minimum/maximum value between
0.00 hrs. and 24.00 hrs.
Heat generator temperature
of the burner after installati-
on
°C
OOFFFF
DDHHWW
AAUUTTOODDAAYY
OOFFFF
HHEEAATTGGEENNEERR..
Selected program for domestic
hot water (DHW) and status
(day, ECO, red. and unit on or
off)
Operation status of the
burner
OOFFFF
HHCC
TTHHEERRMMOOSSTTAATT
Room thermostat function
Max. limitation of
room temperature
00
MMOODDUULLAATTIIOONN
11..66
HHYYDDRRAAUU..PPRREESSSS
Modulation (%)
Hydraulic pressure (bar)
Selected program for unmixed
circuit (HC) and status (day,
ECO, red. and unit on or off)
Entry into the plant information
Plant information
%
¤¤
¤
8A520900_GB.qxp 11.11.2004 14:41 Seite 10

GB
Page GB-11
indicates of heating circuit pump and boiler pump
– boiler status (Off, On)
indicates with room sensor activated
– room thermostat function (heating Off, On)
– current room temperature
indicates in dependence on type of sensor in hot
water tank
– Domestic hot water tank temperature (with tank
sensor)
– switching condition (with tank thermostat)
2211..00
RROOOOMMTTEEMMPPHHCC
Room temperature
Unmixed heating circuit
(room sensor activated)
5522..00
DDHHWW
OOFFFF
DDHHWW
TTHHEERRMMOOSSTTAATT
°C
Domestic hot water tank
temperature
only with domestic hot water
tanksensor
switching condition tank con-
trol only with tank thermostat
RROOOOMMTTEEMMPPHHCC
Room temperature
Unmixed heating circuit
(room sensor deactivated)
or
°C
or
Info-time
The standard display will appear after a set time if no key is pressed. It is possi-
ble to have the information shown permanently with a fastkey procedure or to
adjust the display time (except for the general exit time SYSTEM - Parameter 11):
- press the i-key for 3 seconds
- INFO TIME (= duration of the information in the display) will appear
- Turn the rotary pushbutton to the desired value.
- Press the rotary pushbutton.
- The selected value is activated.
Setting range: OFF (permanent display of selected information)
0.5 to 10 minutes
Application: Permanent display of selected information (monitoring)
----
* Outside temperature is only displayed when the outside sensor is connected.
8A520900_GB.qxp 11.11.2004 14:41 Seite 11

GB
Page GB-12
TIME-DATE
--2200..55
1199::4455
WWEE..--2255..JJUUNN..0033
°C
Standard display
(e.g. automatic operation)
Entry into programming level Press rotary pushbutton for approx. three seconds
SYSTEM
SYST
TIMEPROGRAMS DHW* unmixed circ
HC
TIME
YEAR
Parameter 01
Language selection
Parameter 02
Time program
P1 P1-P3
back forward
SELECTCIRCUIT
HC (heating)
DHW (hot water)
WEEKDAY (Mo-Su)
Heating cycle (1...3)
Copying function
Parameter 01
Night temperature
Domestic hot water
reduced domestic
hot water temperature
Parameter 02
Legionella protec-
tion-day
Weekday 1-7
Parameter 01
Nightly set back
ECO/set back
Parameter 03
ROOM SENSOR
(only with
room unit)
Programming level – level synoptic
Level
select
Entry:
NL GB F I
back forward back forward back forward
back forward back forwardback forwardback forward
0246 10 12 18 2220
81416 24
3sec
can only be called up with code 1234 (see page 22)
see par. 4, 5, 6, 25, 26
8A520900_GB.qxp 11.11.2004 14:41 Seite 12

GB
Page GB-13
HEATINGEND
selected cycle
TEMPERATURE
selected cycle
DAY-MONTH
TIMECHANGE
SUMMER - WIN-
TER
HEATINGSTART
selected cycle
Parameter 03
Separate operation
common (1)
separate (2)
Parameter 04
Summer ECO-
temperature
(Heating limit)
Parameter 11
Return to standard
display
back forward
back forward
back forward
back forward
back forward
Selection and modification of parameters
and setting values
When entering the programming level, the TIME-
PROGRAMS-level will always appear first. All other levels
can be selected with the rotary pushbutton (if necessary after
entering the required code).
The selected and flashing level is activated by touching the
rotary pushbutton, the first value or parameter flashes. If
necessary, it can be changed by means of the rotary push-
button and subsequently accepted by quickly pressing the
button once again. If necessary, the other parameters should
be treated in the same way.
Return to the previous step by means of button ¤¤return to
standard display by using button ¢¢or automatically after
approx. 60 seconds.
RESET
Factory setting
reactivate
back forward
Parameter 16
Domestic hot water
temperature
back forward
Parameter 27
Heating curve
adjustment (slope)
back forward
*) The settings for DHW are only visible when an external
cylinder with either a cylinder sensor or a cylinder ther
mostat is connected.
With combination boilers these settings are not visible.
8A520900_GB.qxp 11.11.2004 14:41 Seite 13

GB
Heating
circuit
Push for approx. 3 seconds
Programming of operating times Page GB-14
2200..55
1155::3300
WWEE2255..JJUUNN..;;0033
°C
TTIIMMEEPPRROOGGRRAAMMSS
HHCC
TTIIMMEEPPRROOGGRRAAMMSSTTIIMMEEPPRROOGGRRAAMMSS
Enter timeprogram level
Standard display
DDHHWW
select
accept
Example: Direct circuit
accept
With this mode of operation individual timeprograms can be generated for heating and hot-water
mode. For this purpose the factory preset standard program (P1) is called up after selecting the res-
pective circuit and can be individually overwritten.
For the programming of timeprograms a maximum of three heating cycles with a switch-on and
switch-off time is available for each weekday. Apart from that a desired room temperature or dome-
stic hot water temperature can be set for each heating or domestic hot water cycle.
3sec
if necessary select program, if enabled (see page 23)
8A520900_GB.qxp 11.11.2004 14:41 Seite 14

GB
Page GB-15
accept
Example: Tuesday - heating cycle 1
°C
2211..00
MMOO--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
MMOO--22
0246 10 12 18 20
14 24
°C
8
2211..00
TTUU--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
8
TTUU--22
0246 10 12 18 2220
14 16 24
°C
8
SSUU--22
0246 10 12 18 2220
14 16 24
°C
816 22
-We-Th-Fr-Sa-Su-
2211..00
TTUU--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
8
2211..00
TTUU--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
8
2211..00
TTUU--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
8
Day and cycle select
Switching-on
time change
Switch-off time change
Temperature change
Setting range: 0.00...24.00 h
Setting range: 0.00...24.00 h
For heating circuit: Room temperature
Setting range: 5.0...30.0 °C
For domestic hot-water circuit: Domestic hot water
temperature
Setting range: 10.0...80 .0 °C (resp. DHW-max)
Note: The 3rd heating cycle is skipped if the 2nd
heating cycle does not contain any time-
programs!
accept
accept
accept
Change - Exit :
Each flashing adjustment value can be cor-
rected by means of the rotary pushbutton
and accepted by pressing the button again.
Return to the previous step is accomplished
with button ¤¤, return to the standard dis-
play by means of button ¢¢or automatical-
ly after approx. 60 seconds.
8
----..--
----..----------..----
----..--
----..----------..----
----..--
----..----------..----
8A520900_GB.qxp 11.11.2004 14:41 Seite 15

GB
Heating circuit
Push for approx. 3 seconds
Copying of timeprograms (formation of blocks) Page GB-16
2200..55
1155::3300
WWEE2255..JJUUNN..;;0033
°C
TTIIMMEEPPRROOGGRRAAMMSS
HHCC
TTIIMMEEPPRROOGGRRAAMMSSTTIIMMEEPPRROOGGRRAAMMSS
Enter timeprogram level
Standard display
DDHHWW
select
accept
Example: Direct circuit
accept
DDAAYY
CCOOPPYY
2211..00
MMOO--11
0066..0000--2222..0000
0246 10 12 18 2220
14 16 24
°C
8
selectCopy
3sec
With this function the timeprograms of any weekday can be copied to other days
(Mo-Su) or to the complete week (1-7) or to groups such as working days (1-5) or
weekends (6-7).
if necessary select program, if enabled (see page 23)
8A520900_GB.qxp 11.11.2004 14:41 Seite 16

GB
After acknowledging the target day will be
overwritten with the selected timeprogram. The
process is completed as soon as the weekday
display flashes again.
Setting range:
Weekdays (MO...SU), whole week (1-7),
Working days (1-5), only weekend (6-7)
Page GB-17
accept
Example:
Monday
MMOO
FFRROOMM
CCOOPPYY
Source select
First target select
Confirmation
If further copies are required continue copying
in the same way (see first target).
copy
11--55
TTOO
CCOOPPYY
OOKK
DDAAYY
CCOOPPYY
Setting range: Monday (MO)...Sunday (SU)
TTOO
CCOOPPYYMMOO
next
target select
Example: Mo - Fr
Example: Sa - Su
66--77
etc.
Change - Exit :
Each flashing adjustment value can be cor-
rected by means of the rotary pushbutton
and accepted by pressing the button again.
Return to the previous step by means of
button ¤¤, return to standard display by
means of button ¢¢or automatically after
approx. 60 seconds.
accept
8A520900_GB.qxp 11.11.2004 14:41 Seite 17

GB
Default-Time
Push for approx. 3 seconds
Reloading of standard program - deleting of individual timeprogram
Page GB-18
2200..55
1155::3300
WWEE..2255..JJUUNN..;;0033
°C
TTIIMMEEPPRROOGGRRAAMMSS
HHCC
TTIIMMEEPPRROOGGRRAAMMSS
DDEEFFAAUULLTTTTIIMMEE
Enter timeprogram level
Standard display
select
accept
Example: Direct circuit
accept
Change - Exit :
Each flashing adjustment value can be corrected by means of the
rotary pushbutton and accepted by pressing the button again.
Return to the previous step by means of button ¤¤, return to stan-
dard display by means of button ¢¢or automatically after approx.
60 seconds.
select
Heating
circuit
3sec
DDEEFFAAUULLTTTTIIMMEE
HHCC
DDEEFFAAUULLTTTTIIMMEEDDEEFFAAUULLTTTTIIMMEE
AALLLL
DDHHWW
j
An individually generated timeprogram can be replaced by its stan-
dard program as shown in the opposite programming schematic.
However, in such cases the individually generated timeprogram will
be irrevocably deleted. For this purpose individual switch-on and
switch-off times as well as specified temperatures should always be
recorded in writing (see page 21).
8A520900_GB.qxp 11.11.2004 14:41 Seite 18

GB
Reset
RREESSEETT
OOKK
press approx. 3 seconds
Standard program was reloaded
Individual program was deleted!
!
Standard timeprograms
Page GB-19
if necessary select program, if enabled (see page 23)
3sec
Timeprogram P1
Circuit Day Time programs
from Temp from Temp from Temp
07.00-09.00 20 09.00-16.00 19.5 16.00-22.30 21
00.00-24.00 63 - - - -
heating (HC) Mo-Su
Domestic hot water Mo-Su
(DHW)
Circuit Day Time programs
from Temp from Temp from Temp
07.00-08.00 20 08.00-16.00 19.5 16.00-22.30 21
07.00-08.00 20 13.00-22.30 21 - -
07.00-23.00 21 - - - -
05.00-08.00 63 15.30-22.00 63 - -
05.00-08.00 63 12.30-22.00 63 - -
06.00-23.00 63 - - - -
heating (HC) Mo-Th
Fr
Sa-Su
Domestic hot water Mo-Su
(DHW) Fr
Sa-Su
Circuit Day Time programs
from Temp
07.00-18.00 21
reduced 21
06.00-18.00 21
reduced
heating (HC) Mo-Fr
Sa-Su
Domestic hot water Mo-Fr
(DHW) Sa-Su
Timeprogram P2 (see page 22)
Timeprogram P3
(see page 22)
8A520900_GB.qxp 11.11.2004 14:41 Seite 19

GB
Day
Mo
Unmixed heating circuit
Tu
We
Th
Fr
Sa
Su
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Timeprogram P1 Timeprogram P2 Timeprogram P3
Day
Mo
Hot water circuit
Tu
We
Th
Fr
Sa
Su
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Cycle 1
from to
Cycle 2
from to
Cycle 3
from to
Page GB-20
Table for individual timeprograms
8A520900_GB.qxp 11.11.2004 14:41 Seite 20
Other manuals for RSC/2
1
Table of contents
Other BrainQ Thermostat manuals
Popular Thermostat manuals by other brands

Plikc
Plikc Fiamma-WR user manual

Airxcel
Airxcel 9630-351 Installation, operation & application guide

Danfoss
Danfoss DEVIreg Smart installation guide

Herpstat
Herpstat Intro+ user manual

OJ Electronics
OJ Electronics OCD5-1999 instructions

Neptronic
Neptronic TRO24T4XYZ3 Specification & installation instructions