Brivo B-ACS-SDC-E User manual

Brivo Single Door
Controller (B-ACS-SDC-E)
Installation Manual
Introduction
ILegal Disclaimers ............................................................................ 2
Introduction..................................................................................... 4
Pre-Installation
II
Understand the function of the ACS-SDC-E................................. 6
Understand ACS-SDC-E product compatibility............................ 6
Verify client site is ready for installation...................................... 6
Verify shipping contents ................................................................ 7
Planning the installation ................................................................ 7
Follow safety precautions .............................................................. 8
General Assembly
III Assemble and mount ACS-SDC-E.................................................. 9
If not using PoE ............................................................................. 10
Conguration
VConnecting to the ACS-SDC-E via local area network............... 16
Verify connection of ACS-SDC-E to local area network ............ 16
Wiring
IV
Wiring the ACS-SDC-E ................................................................... 11
Grounding the ACS-SDC-E............................................................ 13
Powering the ACS-SDC-E.............................................................. 13
LED behavior for the ACS-SDC-E ................................................. 15
Resetting the ACS-SDC-E to factory default............................... 15

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
2
Brivo ACS-SDC-E Installation Manual
Legal Disclaimers
Federal Communications Commission (FCC) Compliancy
You are cautioned that changes or modications not expressly approved by the part responsible for compliance
could void the user’s authority to operate the equipment.
FCC 15B Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment o and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and receiver.
3. Connect the equipment into an outlet on a circuit dierent from that to which the receiver is
connected.
4. Consult the dealer or an experienced radio/TV technician for help.
This telecommunication equipment conforms to NTC technical requirements.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two
conditions:
(1) this device may not cause interference, and (2) this device must accept any interference, including interference
that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence.
L’exploitation est autorisée aux deux conditions suivantes:
(1) l’appareil ne doit pas produire de brouillage, et (2) l’appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le fonctionnement.
Underwriter Laboratories (UL) Compliance
The ACS-SDC-E complies with the UL294 Standard for access control units.
Canada-Underwriters Laboratories (C-UL) Compliancy (CSA C22.2 No. 205)
For C-UL Listed applications, the unit shall be installed in accordance with Part 1 of the Canadian Electrical Code.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
3
Brivo ACS-SDC-E Installation Manual
UL294/ULC Listing Compliancy
UL294 Performance Levels
Model
Number
Access Control
Line Security
Level
Destructive
Attack Level
Endurance
Level
Stand-by
Power Level Conditions
Brivo ACS-SDC-E Level 1 Level 1 Level 4 Level 1 N/A
Parts and Service
The ACS-SDC-E controller (part numbers listed below) contains no user serviceable parts.
ACS-SDC-E Part Numbers
B-ACS-SDC-E Brivo Single Door Controller
Documentation Disclaimer and Restrictions
Information in this document is subject to change without notice and does not represent a commitment on the part
of Brivo Systems LLC. For the most up-to-date information, visit www.brivo.com.
This document and the data herein shall not be duplicated, used or disclosed to others for procurement or
manufacturing, except as authorized with the written permission of Brivo Systems LLC. The information contained
within this document or within the product itself is considered the exclusive property of Brivo Systems LLC. All
information in this document or within the hardware and software product themselves is protected by the copyright
and/or other intellectual property laws of the United States.
Product Support
All support for this product is provided by the third-party dealer. Please contact the dealer who installed the product
with questions and support requests.
© 2023 Brivo Systems LLC. All rights reserved.
Brivo® is a trademark of Brivo Systems LLC. Brivo Systems LLC., 7700 Old Georgetown Road, Suite 300, Bethesda,
MD 20814

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
4
Brivo ACS-SDC-E Installation Manual
Introduction
Document Objectives
This installation manual provides step-by-step instructions for installing the Brivo ACS-SDC-E single door access
control device. Its primary audience is trained access control installation technicians (Installers) who are responsible
for installing the ACS-SDC-E at client sites.
The manual is also intended for IT personnel. It may be used by dealers and their sales professionals to help them
conduct pre-sales, and to provide client support during the installation process. Finally, it may be used for in-house
training purposes and ongoing support.
Document Layout
This manual is organized into a series of procedural checklists, detailing steps you must follow to ensure a safe and
eective installation. The main sections of the manual are:
Pre-Installation Procedures
General Assembly Procedures
Conguration Procedures
Wiring Procedures
Terminology
The following is a list of terms that are used throughout this document. While some of these terms may have other
meanings, the denitions provided below are the ones intended in this Installation Manual.
Control Panel: Brivo’s Single Door Controller (ACS-SDC-E) is a native Ethernet enabled access control panel in
a compact form factor. It is capable of supporting up to two readers; one primary access control card
reader and an additional reader that can be added for in/out antipassback congurations.
Reader: The ACS-SDC-E includes the connection for one access control card reader with an optional second
reader for in/out antipassback situations.
Brivo Access: Brivo’s cloud based software application which enables the end user to manage his or her
Brivo account.
Brivo Cloud Server: The o-site servers, hosted by Brivo, that are used to store an account’s database.
Conguration and maintenance of the control panel is managed through Brivo.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
5
Brivo ACS-SDC-E Installation Manual
Wire Requirements
Signal Belden # or
Equivalent AWG Twisted
Pair Shielded? Conductors Max Length
Power (18 gauge) 6300FE 18 No No 2 500 ft
RJ45-Ethernet N/A Cat5 or
greater Yes No 8 328 ft
Request-to-Exit 5520FE/6300FE 22/18 No No 4 500 ft
Door Contact 5500FE 22 No No 2 500 ft
Earth Ground N/A 18 No Yes 1 (solid) 40 ft
Reader OSDP 9842 24 Yes Yes 4 500 ft
Additional Resources
The following additional resources are available for the installer as well as the client.
· ACS-SDC-E Data Sheet
· Panel Networking Guide
· Brivo ACS-SDC-E Quick Start Guide
· Technical Support: 1-866-BRIVO-4-U
· www.brivo.com
· support.brivo.com (for non-hardware specic help)

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
6
Brivo ACS-SDC-E Installation Manual
Pre-Installation Procedures
Before you begin installing the Brivo control panel, perform the following tasks to ensure a safe, speedy, and suc-
cessful installation.
Understand the function of the Brivo ACS-SDC-E control panel
The ACS-SDC-E is a one door control panel with a single access point. This control panel is considered a
standalone system with internet connectivity to Brivo Access. The control board has one RS485 connection
for one (or optionally two) OSDP reader connections. A second reader is supported for single door in/out
antipassback congurations.
The Brivo ACS-SDC-E uses an on-board Ethernet PoE interface to communicate via any TCP/IP networking
technology that can be connected through a hub, router or switch, including satellite communications. It is
an IP-enabled Access Control System that interacts with the Brivo cloud server via the Brivo Access
application.
Understand Brivo ACS-SDC-E product compatibility
The ACS-SDC-E control panel allows for the attachment of one primary and one additional OSDP reader
directly to the ACS-SDC-E control panel for the purposes of in/out scenarios (antipassback). As such, the
ACS-SDC-E is compatible with a large number of standard OSDP reader models. Brivo products are designed
to accommodate the latest updates in OSDP using RS485 reader formats. The ACS-SDC-E control board
is compatible with OSDP readers using RS485.
A current list of compatible readers and keypads is maintained on Brivo’s website at www.brivo.com. If you
have a specic model of reader or keypad that is not listed on the Brivo website, please contact Technical
Support at 1-866-BRIVO-4-U to determine compatibility.
Verify that the client site is ready to support the installation
1. Check with the IT department to ensure that the ACS-SDC-E to be installed is compatible with the
company’s local area network (LAN).
a) The ACS-SDC-E is equipped with a standard RJ45 socket that accepts a CAT5 cable with an
RJ45 plug on any 10/100 Ethernet network. Physically connecting the panel is the same as
plugging any computer or other device into the LAN.
b) Refer to connection instructions or in the Panel Networking Guide for instructions on
connecting to the LAN. The Panel Networking Guide also contains a complete list of
requirements regarding TCP/IP conguration parameters and information about security
considerations.
2. Download the Brivo ACS-SDC-E Quick Start Guide from the Brivo website and provide it to the
Primary Administrator. This document provides instructions for registering and conguring the
control panel in the application.
3. Make sure the account has been created and the control panel is registered through Brivo. If the
control panel has not been registered by the dealer, the installer may either contact Brivo Technical
Support for assistance or simply register the panel directly.
4. Verify that the Primary Administrator and any other employee who will be accessing the system
have Internet access on a computer equipped with a supported Web browser.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
7
Brivo ACS-SDC-E Installation Manual
Verify shipping contents
1. Locate and check the contents of the Control Panel kit.
The ACS-SDC-E kit should contain the following parts:
a) 1 cardboard box containing the following:
·The B-ACS-SDC-E unit, with its identication label on the back
·An additional loose label for reference
·A quick start guide
·A bag of accessory parts containing:
· One MOV (Metal Oxide Varistor)
·Two 120 ohm RS485 bus termination resistors.
· Six 2k ohm end-of-line (EOL) tamper termination resistors
·One cover plate for a single gang electrical junction box
· One strain relief zip tie for Ethernet cable
Plan your installation and decide where to install the ACS-SDC-E
1. If not using Power over Ethernet (PoE), do not place the ACS-SDC-E more than 100 feet from the
12V DC power supply transformer. This is the maximum cable run allowed by most external power
supplies.
a) The ACS-SDC-E does not specify a maximum wiring length between the ACS-SDC-E and a
reader, but the keypad/reader manufacturer may. Follow manufacturer guidelines for wiring
type and distance between controller and reader.
b) Place the ACS-SDC-E within 500 feet of its associated electronic strike or latch.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
8
Brivo ACS-SDC-E Installation Manual
Follow safety precautions
WARNING: Fire Code
Never connect a keypad/reader or lock to doors without rst consulting the applicable re code. You must consult
with, and get approval from, local re ocials before installing locks or devices on any doors that may be re exits.
Use of egress push buttons may not be legal. Single action exits may be required. Always obtain proper permits and
approvals in writing before installing equipment
WARNING: Fail Secure Mode
Do not install the system in the fail secure mode unless permitted by the local authority having jurisdiction. Doing
so may cause interference with the operation of panic hardware.
WARNING: Heat and Noise
Do not install the control panel in an area that does not comply with the listed temperatures below. Doing so can
cause damage to components within the control panel.
The ACS-SDC-E control panel is UL tested to between -35°C (-31°F) and 66°C (150°F) and EN -40°C (-40°F) to 70°C
(158°F) and 85% humidity.
Do not install the control panel near or on the same circuit with devices that produce large amounts of electrical
noise. This includes grinders, electric motors and blowers, electrical switch-gear and other electrically noisy equip-
ment. Electrical noise can interfere with panel operation. If it is not possible to install the panel away from such
sources of noise, it is advisable to isolate it by using a high-quality UPS (Uninterruptible Power Supply) between the
AC Mains and the transformer.
·Unit is primarily for indoor use. It can be used outdoors if contained in a protected water tight
enclosure.
·Power wiring attached to the ACS-SDC-E unit should be 18 AWG or larger.
·Category 5 cabling is the minimum performance category recommended.
·Do not connect to a receptacle controlled by a switch.
· Compliance with IEEE 802.3 (at or af) specications was not veried as part of UL294/B.
·If powered by 12V DC, the power supply must be a UL294 listed or UL 603 listed power supply.
Battery capacity for loss of primary power at least zero (0) hours.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
9
Brivo ACS-SDC-E Installation Manual
General Assembly Procedures
Assemble and mount ACS-SDC-E
1. Mount the ACS-SDC-E unit using the method described below:
a) This Single Door Access Control Device (ACS-SDC-E) is intended to be installed within the
secure/protected area.
b) To mount the ACS-SDC-E:
i) Fully wire the ACS-SDC-E, ensure all cables have proper strain relief, and use the
provided zip tie for additional CAT5 or greater cable strain relief.
ii) Push the ACS-SDC-E into the junction box facing inwards.
iii) Attach the provided cover plate.
ACS-SDC-E Mounting Diagram

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
10
Brivo ACS-SDC-E Installation Manual
OPTIONAL: If not using Power over Ethernet, wire the 12V DC In and Ground wires to an external 12V DC Power
Supply
1. Use 18 AWG or 22 AWG wire (see table on Page 5) to connect the appropriate input power wires to
the ACS-SDC-E unit.
Connecting optional External Power to the ACS-SDC-E
Model Circuit Voltage (VDC) Current (A)
Brivo B-ACS-SDC-E Input 12VDC 800mA
Tamper
When triggered, the ACS-SDC-E will generate a tamper event to Brivo Access. It will be visible in the real time event
interface and can be congured to generate email notications. Tamper for ACS-SDC-E is motion triggered. Once
triggered, the ACS-SDC-E will stop after a period of time (10 to 15 seconds) with the reader at rest. In order for the
tamper alarm to be audible, an OSDP reader must be attached to the ACS-SDC-E unit and the tamper alarm will
sound through the attached OSDP reader.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
11
Brivo ACS-SDC-E Installation Manual
Wiring Procedures
Provided below is the wire block diagram for the ACS-SDC-E unit.
NOTE: The ACS-SDC-E has a pair of RS485 wires for connecting up to two external OSDP readers. The
ACS-SDC-E can support one wired lock with up to two readers for use at one door for in/out antipassback
situations.
For the ACS-SDC-E unit to be used for controlling a door, make the following connections:
ACS-SDC-E Wire Block Diagram
Power In
1. DC Power In is rated from 10V DC to 15V DC. DC Power shall be provided through a UL294
approved Power Supply with Class 2 limited output.
2. Optionally power can be supplied through Power over Ethernet (PoE) through the RJ45 connector.
3. In the case of both DC power and PoE, the ACS-SDC-E will draw power from the DC power
source.
WARNING: Use of 24V DC
The Brivo ACS-SDC-E Single Door Controller should be powered from Power over Ethernet (PoE) or a 12V DC
power supply. Do NOT use 24V as input power to the ACS-SDC-E. The only place on the ACS-SDC-E that you
can connect 24V is the Normally Open or Normally Closed relay contacts.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
12
Brivo ACS-SDC-E Installation Manual
Lock Control
The ACS-SDC-E controls a single door lock through either a magnetic lock or door strike.
There are two 12V DC outputs each capable of up to 500mA that can be used to power the door strike in conjunc-
tion with the lock control relay.
Lock Relay Output
The relay is rated up to 30V DC and 2A with 0.6 power factor. If power is provided via one of the ACS-SDC-E’s
12V outputs, the relay power would be 12V DC and the rated output of 500 mA of the ACS-SDC-E’s limited
current.
The ACS-SDC-E lock relay output has both Normally Open and Normally Closed contacts for wiring
depending upon your application.
Lock Wiring using onboard 12V DC (normally open shown)

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
13
Brivo ACS-SDC-E Installation Manual
Lock Wiring with 3rd Party power supply (normally closed shown)
Switched Ground (Aux Output)
Switched Ground output enables or disables a Ground connection. This acts as a electronic relay switch to Ground.
1. Congure the default power as either Power-On or Default Power-O through the Brivo Access
Account Cong Tool.
Supervised Inputs
1. There are three (3) Supervised Inputs:
· Request To Exit (REX)
· Door Switch Monitor/Door Contact (DSM)
· Auxiliary Input (AUX).
The Inputs can be congured as:
· Two (2) State (non-supervised) with Closed / Open Status.
· Four (4) State (use of two 2Kohm End of Line Resistors) supervised with Closed / Open /
Short / Cut Status.
2. If used, wire the Aux Input using the Aux wire and the Ground wire. The Aux Input can be used for a
variety of purposes, and is programmed through the Brivo Access Account Cong Tool.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
14
Brivo ACS-SDC-E Installation Manual
WARNING: Noise Suppression
1. Install the MOV across the conductors, as close as possible to the electric strike, latch, or
magnetic lock. This will normally be at the connection from the eld-installed wiring to the
pigtail or screw terminals of the electronic strike, latch, or magnetic lock.
2. Use the wire recommended by the manufacturer of the electric strike or latch. If no wire is
recommended, use a minimum of 18 AWG wire with sucient strands for specic electronic
strike or latch.
Wire the Reader
The ACS-SDC-E communicates to external readers through OSDP.
One of the 12V DC outputs can be used to power the OSDP Reader(s) up to 500mA.
NOTE: For In/Out use cases, two readers can be connected to the same RS485 port, and OSDP multi-drop
allows communication to both readers.
NOTE: The ACS-SDC-E can communicate to external readers connected through 1000 ft of twisted pair, 24
AWG wire at 9600 Baud.
1. Connect RS485- and RS485+ for reader to ACS-SDC-E.
2. Connect the power wire to 12V Out and GND.
IMPORTANT RS485 WIRING INFORMATION
NOTE: If the external OSDP reader is a signicant distance from the ACS-SDC-E unit, then it is recommended
that both ends of the RS485 bus are terminated using a 120 ohm resistor.
NOTE: When wiring the RS485 bus, use only twisted pair shielded wire.
NOTE: Input reader must be OSDP Address 1 and output antipassback reader must be OSDP Address 2.
NOTE: If needed, OSDP addressing can be performed using the Brivo programing interface (WebCLI).
Ground the ACS-SDC-E
1. When grounding the ACS-SDC-E unit, use 18 AWG or larger wire to connect the ACS-SDC-E to a
suitable earth ground.
2. The ground contact point is the GND contact located directly on the ACS-SDC-E unit.
Power up the ACS-SDC-E
NOTE: The ACS-SDC-E is UL listed when using DC power.
1. Ensure that all wiring is complete prior to powering up the ACS-SDC-E unit.
2. Plug the CAT5 or greater cable into the LAN/PoE connector.
3. If not using PoE, plug in power to the ACS-SDC-E unit using 12V In and Ground.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
15
Brivo ACS-SDC-E Installation Manual
4. Optionally, you may use PoE and an external 12V power supply for redundant simultaneous power
input.
LED behavior for the ACS-SDC-E
The ACS-SDC-E unit has ve LEDs with the following colors and functions:
1. Power - [GREEN]
2. Network Link - [GREEN]
3. LED3 [RED] : OSDP Reader State Blink / Factory Reset
4. LED2 [GREEN] : PCS Connection Solid ON/OFF
5. LED1 [BLUE] : Heartbeat Blink
Resetting the ACS-SDC-E to factory default
The ACS-SDC-E unit goes into a factory default reset sequence when the following steps are performed:
1. Press and hold the factory default reset (FDR) button for ten (10) seconds and wait for the solid red
LED to light up and stay solid.
2. Release the button within three (3) seconds.
3. After releasing the button, the ACS-SDC-E unit will recognize that a factory reset is desired and will
initiate the factory default reset procedure. As the ACS-SDC-E unit restarts, the rmware will
automatically update. Once LED operation returns to normal, the ACS-SDC-E unit will have been
reset.
NOTE: If the Factory Default Reset (FDR) button is released after 13 seconds or more than three seconds
after the red LED is solid, a factory reset will not occur.

© 2023 Brivo Systems LLC. All rights reserved. PUB-Brivo ACS-SDC-E Installation Manual_v1.2
16
Brivo ACS-SDC-E Installation Manual
Conguration Procedures
If any manual conguration is required, connect a laptop to the same local area network as the ACS-SDC-E unit
NOTE: The laptop and ACS-SDC-E unit MUST be on the same subnet.
1. Set your NIC interface on your laptop/PC to IP 169.254.242.122 and net mask 255.255.255.0 .
2. Connect the CAT5 or greater cable from the NIC interface on the laptop to the PoE network switch.
3. Connect another CAT5 or greater cable from PoE network switch to ACS-SDC-E unit. Allow a few
seconds for the ACS-SDC-E unit to boot up.
4. Open a web browser and navigate to 169.254.242.121 .
5. When the prompt appears for username/password, use username cli and password new5cli.
a) The Administrative Interface (WebCLI) is used to gain access to the onboard functionality for
debugging and manual conguration utilities.
Verify connection of the LAN to the ACS-SDC-E
1. Using CAT5 or greater cable, connect the LAN to the ACS-SDC-E unit via its LAN port.
a) The LAN port is a 10/100 Ethernet interface with an RJ45 jack for connecting the Ethernet
port on the ACS-SDC-E to a Local Area Network in order for it to gain connectivity to the
Internet.
b) Use a straight, (i.e., non-crossover) cable to connect this port to a local hub, switch or router.
2. Verify the connection of the LAN to the ACS-SDC-E by accessing the Administrative Interface
(WebCLI) Using the instructions listed in the previous step. On the main page of the Administrative
Interface, you should see a recent time/date stamp in the Last Contact with Central eld.
NOTE: Firmware Upgrade - When rst registered and connected to the Brivo cloud service, your ACS-SDC-E
will automatically download and install the latest rmware. This process may take several minutes, so do
not disconnect or cut power to your ACS-SDC-E during this process. If you encounter any diculties during
Revision Table
Version Date Content
1.0 02/07/2023 Original document
1.1 02/17/2023 Updated wire requirements table
1.2 02/28/2023 Added wiring graphics
Table of contents
Other Brivo Controllers manuals
Popular Controllers manuals by other brands

SMC Networks
SMC Networks IRV10 Operation manual

Gira
Gira System 3000 operating instructions

Precision Digital Corporation
Precision Digital Corporation PROVU PD6310 instruction manual

COMECO
COMECO RT28U Operation manual

Coelbo
Coelbo EPR instruction manual

Flowserve
Flowserve NORBRO 40R Series User instructions