Bryant ZONE PERFECT PLUS ZONEBB2KIT User manual

TABLE OF CONTENTS Page
SAFETY CONSIDERATIONS...................................................1
INSTALLATION CONSIDERATIONS....................................1
INTRODUCTION.....................................................................1-2
INSTALLATION......................................................................2-8
• Check Equipment And Job Site..................................................2
• Component Location And Wiring Considerations.....................2
• Install Components...................................................................2-3
• Install Zone Dampers...............................................................3-4
• Install Barometric Bypass Damper.............................................5
• Install Leaving Air Temperature (LAT) Sensor.........................5
• Install Heat Pump Temperature (HPT) Sensor ..........................5
• Final Wiring..................................................................5-7, 19-25
• Understanding Sequence Of Operation...................................7-8
SYSTEM CONFIGURATION..............................................8-11
• Equipment Controller Configuration ..........................................8
• User Interface Configuration .................................................8-11
SYSTEM STARTUP AND CHECKOUT..........................11-12
• Enable Installer Setup Mode ...............................................11-12
• Check Damper And Sensor Operation .....................................12
• Quick Check Of Equipment Operation ....................................12
• Longer Check Of Equipment Operation...................................12
FINAL INSTALLATION SETTINGS...............................12-14
OPERATIONAL INFORMATION .........................................14
SMART SENSOR OPERATION.............................................15
QUICK START..........................................................................16
QUICK PROGRAMMING OF
COMFORT SCHEDULES ..................................................16-17
HOLD, OFF, OUT AND ALL ZONE.....................................17
TROUBLESHOOTING .......................................................17-18
NOTE: Read the entire instruction manual before starting the
installation.
This symbol →indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause fire, electrical shock, or other conditions which
may cause personal injury or property damage. Consult a qualified
installer, service agency or your distributor or branch for informa-
tion or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this prod-
uct. Refer to the individual instructions packaged with the kits or
accessories when installing.
Follow all safety codes and wear safety glasses. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
and state building codes and Sheet Metal and Air Conditioning
National Association (SMACNA) for special installation require-
ments.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INSTALLATION CONSIDERATIONS
Before the actual installation of a zoning system can begin,
decisions need to be made to determine the number and location of
zones and sensors. This affects duct and damper selections. For
assistance with these decisions, consult the Design Guide available
from your distributor or branch.
This instruction covers the physical installation and start up of the
Zone Perfect Plus system. Use this instruction to guide the actual
installation process after all the air side decisions have been made.
1. Install User Interface and Remote Sensors in non-
condensing areas with ambients between 32°F and 120°F.
Install Dampers and Equipment Controller in non-
condensing areas with ambients between 32°F and 158°F.
2. Dampers may need to be vibration isolated to reduce noise.
3. TXV is required in air conditioning and heat pump appli-
cations.
4. Use separate isolated transformer to supply power to Zone
Perfect Plus System (40 va minimum, class 2, field sup-
plied).
5. Proper equipment and duct sizing are important in a zoned
system. Be sure to refer to the Design Guide for assistance
in making these selections.
CAUTION: TXV on indoor coil is required on all
zoning installations.
INTRODUCTION
The Zone Perfect Plus System allows air conditioning and heating
equipment to control temperatures and humidity in up to 8 distinct
spaces or Zones within a building. Each zone has independent
temperature settings.
The comfort temperature settings can change automatically
through the use of schedules. This allows Zone Perfect Plus to
change temperature settings in zones to reflect occupancy or usage.
For example, you can condition the bedrooms in a home from 5:00
PM through 7:00 AM or the kitchen from 3:00 PM through 6:00
PM. The Zone Perfect Plus System uses motorized air volume
control dampers (also called zone dampers) to regulate flow of
conditioned air into zones. In this manner Zone Perfect Plus can
selectively heat or cool certain portions of a building depending
upon space temperature requirements.
Each zone requires a motorized zone damper to control the air
supplied to it and a zone sensor to sense zone temperature. There
are 3 types of zone sensors available and they may be used in
combination:
• User Interface — Each installation has only 1 User Interface.
This is the command center for the entire system, and it will
typically be located in Zone 1 to sense and control the
installation instructions
ZONE PERFECT PLUS
Cancels: II ZONEKIT-0-7 II ZONEKIT-0-9
3-98
ZONEBB2KIT
ZONEBB4KIT
ZONEBB8KIT
—1—
→
→

temperature in this zone. If desired, a Remote Sensor may be
used to sense the Zone 1 temperature. This can give the
installer some flexibility in locating the User Interface to
another area.
• Remote Sensor — This is a temperature sensor only, having no
additional user inputs.
• Smart Sensor — Any zone other than Zone 1 may use a Smart
Sensor. It provides a display of zone temperature and means to
adjust the desired temperature in that zone only. It also displays
the outdoor temperature and indoor humidity.
Be sure to select the desired sensor type for each zone. Standard
kits include only Remote Sensors. Other types must be purchased
separately. Installation Instructions for Smart Sensors are included
with them.
INSTALLATION
I. CHECK EQUIPMENT AND JOB SITE
A. Inspect Equipment
File claim with shipping company, prior to installation, if shipment
is damaged or incomplete.
II. COMPONENT LOCATION AND WIRING
CONSIDERATIONS
WARNING: To prevent personal injury or possible
equipment damage disconnect power supply before rout-
ing wire.
All wiring must comply with national, local, and state codes.
A. Locating Equipment Controller
All wiring is run back to the Zone Perfect Plus Equipment
Controller. Select a location near the furnace or fan coil where
wiring from the User Interface, each Remote Sensor or Smart
Sensor, each damper actuator, and the equipment itself can come
together easily.
The Zone Perfect Plus System is approved for indoor use only and
should never be installed with any of its components exposed to
the elements. The Equipment Controller (and the zone dampers)
may be installed in any area where the temperature remains
between 32° and 158°F, and there is no condensation. The cover
must be installed to prevent damage from other sources. Do not
locate where it will be accessible to children. Avoid areas in which
the sound of relays energizing on the Equipment Controller may be
an annoyance. It may be mounted in either vertical or horizontal
position. Remember that wiring access is likely the most important
consideration.
CAUTION: To prevent possible damage to Equipment
Controller, do not mount on plenum, duct work, or flush
against furnace.
B. Locating User Interface
The User Interface is the command center for the Zone Perfect
Plus system. It should be located where it is easily accessible and
visible to home or business owner. It is also normally the Zone 1
sensor and as such needs to be located to properly measure the
temperature in Zone 1. If these 2 requirements conflict, a separate
Remote Sensor can be added for Zone 1. When Remote Sensor is
connected to Zone 1 terminals (OS1 and OS1C) of Equipment
Controller, the system automatically switches to using this sensor
for Zone 1 and ignores the sensor within the User Interface. This
arrangement allows User Interface to be located at any convenient
place within the home or business, and only the Zone 1 Remote
Sensor must be located in Zone 1.
NOTE: The User Interface also controls humidity functions. If
the User Interface is not used to control Zone 1 temperature, it
must still be located in a suitable area where humidity control will
not be affected.
C. Locating Sensors
For proper operation, each sensor must accurately measure the
temperature within its zone. Remember that zone sensors can be a
combination of 3 different types as described in introduction.
For accurate temperature measurement, the following guidelines
should be followed:
Sensor should be mounted:
• Approximately 5 ft (1.5m) from floor.
• Close to the center of its zone, preferably on an inside wall.
• On a section of wall without pipes or duct work.
Sensor should NOT be mounted:
• Close to a window, on an outside wall, or next to a door leading
to the outside.
• Where it will be exposed to direct light and heat from a lamp,
sun, fireplace, or other temperature-radiating object which may
cause a false reading.
• Close to or in direct airflow from supply registers and return-air
grilles.
• In areas with poor air circulation, such as behind a door or in
an alcove.
The Remote Sensor terminals are not marked for polarity because
polarity is not important.
D. Wiring Considerations
All wiring in the Zone Perfect Plus system may be unshielded.
Ordinary thermostat wire is ideal. Use 22 gage or larger for normal
wiring. Lengths over 100 ft should use 20 gage or larger wire.
Remote Sensors require only 2 conductors, but it is recommended
that at least 4 conductors be run. This will allow a Smart Sensor to
replace the Remote Sensor with no wiring changes at a later date.
The User Interface requires 4 conductors, each damper actuator
requires 3 conductors. The connection to equipment (furnace or
fan coil) could require as many as 8 conductors for a multi-stage
installation. The leaving air temperature (LAT), heat pump tem-
perature (HPT)—used with heat pumps only, and optional outdoor
air temperature (OAT) sensors require 2 conductors each. The
outdoor air temperature sensor may be able to be connected at the
outdoor unit using existing wiring. Refer to Installation Instruc-
tions included with the outdoor air temperature sensor.
Cables with excess conductors are acceptable. Cut off or fold back
and tape any unneeded conductors.
Plan the routing of wiring early to avoid possible problems later
on.
Remember all wires converge at the Equipment Controller, so its
location is important.
III. INSTALL COMPONENTS
A. Install Equipment Controller
The Equipment Controller is designed so that wires can enter it
from behind, above, or below. Plan wire routing before mounting
Controller.
1. Open doors or remove cover to access mounting holes.
Remove the 2 Zone system cover from the left side first.
2. Mount back plate to wall using screws and wall anchors
provided.
3. Level back plate and tighten screws.
B. Install User Interface
1. Open User Interface rear door (mounting base) to expose
mounting holes. Press back half of the right end inward and
then pull front and back halves apart at the right end to
open. The mounting base (the back half of the plastic) can
be separated from the User Interface body by snapping the
hinge apart.
—2—
→

a. Remove hinged cover by snapping apart its hinge.
b. Separate the main body from the mounting plate by
snapping its hinge apart.
c. Mount base before wiring and attaching remaining parts.
2. Route User Interface wires through large hole in mounting
base. Level mounting base against wall and mark wall
through 2 mounting holes. Any thermostat cable of 4 or
more conductors may be used. Shielded cable is not needed.
3. Drill two 3/16-in. holes in wall where marked.
4. Secure mounting base to wall with 2 screws and anchors
provided, making sure all wires extend through hole in
mounting base.
5. Adjust length and routing of each wire to reach proper
terminal and connector block on mounting base with 1/4 in.
of extra wire. Strip only 1/4 in. of insulation from each wire
to prevent adjacent wires from shorting together when
connected.
6. Match and connect 4 wires to proper terminals of the
connector blocks. Recommended connection is RED to V+,
WHITE to VG, BLUE or YELLOW to RS+, and GREEN
to RS-.
CAUTION: Improper wiring or installation may damage
the User Interface. Check to make sure wiring is correct
before proceeding with installation or turning on unit.
7. Push any excess wire into wall and against mounting base.
Seal hole in wall to prevent air leaks. Leaks can affect
operation.
8. Snap hinge back together.
9. Close User Interface assembly making sure pins on back of
circuit board align with sockets in connector.
C. Install Remote Sensors
1. Separate the sensor and mounting back plate (with provided
screws and anchors). Squeeze the top and bottom of the
cover together firmly by grasping the raised top and bottom
ridges. This will release the cover.
2. Pull a 2-conductor wire through hole on right-hand side.
3. Recommended connection is BLACK to either terminal,
WHITE to remaining terminal. Stranded or common bell
wire may be used. Lengths up to 1000 ft will contribute no
noticeable error.
4. Align sensor case with base plate then press firmly until
cover snaps into place.
For installation of other sensor types, refer to Installation Instruc-
tions provided for them.
IV. INSTALL ZONE DAMPERS
Proper selection and sizing of dampers is very important for proper
system operation. Be sure to consult the System Design Manual for
assistance in making these selections. Selection and sizing infor-
mation is not provided in this installation instruction.
If conditions exist for possible condensation, do not mount the
actuator beneath the duct.
If duct work requires multiple dampers for a single zone, up to 3
dampers may be wired in parallel. A multi-damper enabler is not
needed.
For retrofit applications, older type dampers with their original
actuators may be used under the following conditions:
1. A single damper may be connected directly to a Zone
Perfect Plus output.
2. If multiple dampers are needed for a single zone, a
multi-damper enabler must be used.
Older type dampers having an extended shaft and driven by a
crank arm may be fitted with the new DAMPACT actuators for
quieter operation. Mounting is straightforward. Be sure to use 45°
actuators (part No. DAMPACT45DEG) with round dampers and
90° actuators (part No. DAMPACT90DEG) with rectangular
dampers. When new actuators are fitted to older dampers, multi
damper enablers are not needed and up to 3 actuators can be
connected in parallel to a single Zone Perfect Plus output.
Zone dampers may be installed in any position.
Install dampers so that actuator is visible for inspection and
accessible in the event it would ever need to be serviced. The black
mark on the end of damper shaft represents position of damper
blade.
NOTE: Insulate damper using 1-1/2 in. insulation (check local
codes). In areas where excessive condensing may occur, carefully
insulate over the actuator assembly. Make sure insulation does not
interfere with operation of actuator.
Before insulating over the actuator, check for proper damper
operation. This will be done as part of the installer set up or may
be done by applying 24vac between COM and OPN to open
damper and between COM and CLS to close damper. (See Fig. 1.)
The damper will modulate counter-clockwise to open and clock-
wise to close (viewed from the actuator end).
If in an emergency it becomes necessary to force a damper open,
manually press in the red quick blade release button with one hand
and turn mounting hub to reposition damper shaft. Release button
to hold damper shaft in new position.
A. Round Metal Duct Work
1. Crimp end of branch duct.
2. Slip end of zone damper over end of duct work. Use
self-tapping sheet metal screw to secure. (See Fig. 2.)
3. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuator.
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check
your local codes.)
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
Fig. 1—Damper 24-vac Connections A95096
90
45
0
CLS
COM
OPN
ACTUATOR
HOUSING
MOUNTING
BRACKET
QUICK BLADE
RELEASE
BUTTON
(RED)
FIELD
INSTALLED
POWER WIRING
ANGULAR
ROTATION
STOPS
POSITION
INDICATOR
MOUNTING
HUB
AIRFLOW
AIRFLOW
—3—

B. Rectangular Metal Duct Work
1. Make connections using S-lock and drives. (See Fig. 3.)
2. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuator.
3. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check
your local codes.) (See Fig. 4.)
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
C. Round Flexible Duct Work
1. Slip 1 end of flexible duct work over 1 end of zone damper.
(See Fig. 5.)
2. Secure flexible duct to zone damper using SMACNA or
other approved method.
3. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuator.
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check
your local codes.) (See Fig. 6.)
NOTE: All zone dampers and duct work must be properly
supported according to local codes or SMACNA standards.
D. Rectangular Fibrous Glass Duct Work
1. Insert 1 end of zone damper into 1 end of fibrous glass duct
work approximately 2 to 3 in. (See Fig. 7.)
2. Screw field-supplied screws and tabs into zone damper.
3. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuator.
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check
your local codes.) (See Fig. 8.)
Fig. 2—Insulated Round Metal Duct Work A95130
/ ″STEEL STRAP
1 2
Fig. 3—Rectangular Metal Duct Work A92478
DRIVE ZONE
DAMPER
S-LOCK
SUPPLY
AIR DUCT
Fig. 4—Insulated Rectangular Metal Duct Work
A95131
1 / " TO 2"
INSULATION
12
Fig 5—Round Flexible Duct Work A95132
FLEXIBLE
DUCT ZONE
DAMPER
Fig. 6—Insulated Round Flexible Duct WorkA95133
/ ″STEEL STRAP
12
Fig. 7—Rectangular Fibrous Glass Duct Work
A92480
ZONE
DAMPER
2″TO 3″
FIBROUS
GLASS
DUCTWORK FIELD
SUPPLIED
SCREWS
Fig. 8—Insulated Rectangular Fibrous Glass
Duct Work
A95134
1 / ″TO 2″
INSULATION
12
—4—

V. INSTALL BAROMETRIC BYPASS DAMPER
NOTE: The barometric bypass damper is a critical part of Zone
Perfect Plus System for controlling noise at minimum airflow. A
barometric bypass should be installed unless the duct work and
indoor unit have been sized for use without a bypass.
The bypass should be installed according to local codes and
SMACNA standards. Be sure bypass is properly supported.
For proper installation, refer to Installation Instructions packaged
with barometric bypass.
CAUTION: Failure to properly install leaving air tem-
perature sensor can cause permanent damage to the
HVAC equipment.
VI. INSTALL LEAVING AIR TEMPERATURE (LAT)
SENSOR
Locate LAT sensor in main supply trunk after heating and cooling
coil and before bypass damper and first branch. The LAT sensor is
radiant shielded to prevent heat from affecting correct air tempera-
ture.
1. Drill a 1/4-in. hole at location in supply trunk where sensor
will be installed.
2. Insert sensor in hole and use as a template to mark the 2
mounting holes.
3. Drill two 1/16-in. holes to accept No. 6 screws through
pre-drilled holes in duct temperature sensor back plate.
4. Use 2 No. 6 sheet metal screws to mount duct temperature
sensor to unit.
5. Connect sensor to 2-conductor wire using provided wire
nuts. (See Fig. 9, 10, or 11 for connection to Equipment
Controller.)
VII. INSTALL HEAT PUMP TEMPERATURE (HPT)
SENSOR
The HPT sensor is required in all heat pump/fan coil installations.
It is not used in dual fuel(heat pump/furnace installation). It
measures the temperature of the air leaving the indoor coil. The
sensor is to be installed downstream of the indoor coil but before
the electric heaters. It can be installed through the wall of the fan
coil or may be located entirely inside the fan coil near the blower
inlet. Anchor firmly in place with cable ties so that it cannot
interfere with the blower wheel. (See Fig. 9, 10, or 11 for
connection to Equipment Controller.)
VIII. FINAL WIRING
Bring all Equipment Controller wires together at Equipment
Controller. Make all connections as indicated on Fig. 9 (for 2-zone
installations), Fig. 10 (for up to 4-zone installations), or Fig. 11
(for up to 8-zone installations).
Figures 15 through 38 show the connection between the Equip-
ment Controller and the HVAC equipment. Select proper diagram
for your equipment and connect accordingly. This connection will
require as few as 4 or as many as 7 conductors. See Table 4 to
identify the correct wiring figure.
NOTE: Table 4 and wiring diagrams appear in sequence near the
end of this document.
NOTE: It is good practice to mark each wire as the final
connection is made. This will preserve its identity if it is ever
disconnected.
→Fig. 9—2-Zone System Wiring Diagram A98085
O REVERSING VALVE COOL
B REVERSING VALVE HEAT
RH HEATING TRANSFORMER
RC COOLING TRANSFORMER
SEE
FIGURES FOR
EQUIPMENT
WIRING
DEFROST
JUMPER NEEDED
FOR HEAT PUMP
APPLICATIONS
24 VAC
ZONING
TRANSFORMER
C
RZ
DHUM DEHUMIDIFY
DEF DEFROST
HUM HUMIDIFY
G FAN
W2 HEAT STAGE 2
W1 HEAT STAGE 1
Y2 COMPRESSOR STAGE 2
Y1 COMPRESSOR STAGE 1
HPT
HPTC
LAT
LATC
OATC
OAT OUTDOOR AIR
TEMP SENSOR
LEAVING AIR
TEMP SENSOR
HEAT PUMP
TEMP SENSOR
CLS1
COM1
OPN1
CLS2
DAMPERS
OPTION
SWITCHES
NOTE SWITCH
#8 IS AT TOP
CLS_
COM_
OPN_
8
1
=
=
=
CLOSE
COMMON = 24VAC FROM RZ
OPEN
COM2
OPN2
ZONE 1
DAMPER
ZONE 2
DAMPER
DAMPER
FUSE
3A
D20
(LED)
2 ZONE EQUIPMENT CONTROLLER
NOTES: *= OPTIONAL COMPONENTS
= INSTALLING ZONE 1 REMOTE SENSOR AT OS1AND OS1C WILL OVERRIDE
TEMPERATURE SENSOR ON USER INTERFACE
= COMMUNICATION BUS ARE IN PARALLEL WITH EACH OTHER
(EITHER CONNECTOR CAN BE USED)
†
†
V+
USER INTERFACE
RS+
V+
RS+
RS-
VG
V+
RS+
RS-
VG
OS1
OS1C
ZS2
ZS2C
RS-
VG
VG
OPTIONAL
ZONE 1
SENSOR
REMOTE
SENSORS ZONE 2
SENSOR
COMMUNICATION
BUS
COMMUNICATION
BUS
V+
SMART SENSORS*
RS+
RS-
WHITE
RED
BLUE/YELLOW
GREEN
WHITE
RED
BLUE/YELLOW
GREEN
†
†
†
—5—
→
→
→
→

Separable RC and RH connections are provided for systems with
separate transformers for heating and cooling. To accommodate
separate transformers, cut jumper R12 on the Equipment Control-
ler board. It is located just below and to the right of the RC and RH
connections. As shipped, the R12 jumper ties RC and RH
terminals together so either can be used in single transformer
application.
When installing a 24-vac humidifer, connect it directly to the
HUM terminal on Equipment Controller, and C terminal of indoor
equipment. Do not use an external humidstat. All necessary control
is provided by Zone Perfect Plus.
When using an FK series fan coil, connect DHUM (dehumidify)
output directly to DH terminal of fan coil. This output may also
drive a relay (connected with other side to C) which can be
connected to reduce fan speed in other types of blowers. The relay
will be energized when humidity is normal and will deenergize
when humidity is high, calling for reduced fan speed.
An LAT sensor must be connected in all systems. Both LAT and
HPT sensors must be connected in heat pump/fan coil systems.
WIRING CONSIDERATIONS
Zone Perfect Plus treats all furnaces as if they were 2-stage. For
single stage equipment, connect to W1. The same holds true for
auxiliary heat in fan coils. (Refer to Fig. 15-38.)
With any 2-stage furnace, configure the furnace so that low fire is
controlled by W1 and high fire is controlled by W1 and W2
together. This means the internal algorithm is to be disabled. See
furnace instructions.
Some variable speed furnaces have a "zoning" setting. If such a
setting exists, it should be turned on. It forces the furnace to adjust
its airflow more frequently to accommodate the effects of damper
movement. See furnace instructions.
All 2-speed air conditioners and heat pumps need to be configured
so that Y1 controls low speed and Y1 and Y2 together control high
speed in both heating and cooling. This is usually done by
selecting the "zoning" position of the stage 2 latch pot. See 2-speed
equipment instructions.
In 2-speed dual fuel applications (2-speed heat pump and furnace),
do not set the furnace interface jumper on the heat pump to ON,
→Fig. 10—4-Zone System Wiring Diagram A98086
O REVERSING VALVE COOL
B REVERSING VALVE HEAT
RH HEATING TRANSFORMER
RC COOLING TRANSFORMER
DEF DEFROST
DHUM DEHUMIDIFY
SEE
FIGURES FOR
EQUIPMENT
WIRING
24 VAC ZONING
TRANSFORMER C
RZ
4 ZONE EQUIPMENT CONTROLLER
HUM HUMIDIFY
G FAN
W2 HEAT STAGE 2
W1 HEAT STAGE 1
Y2 COMPRESSOR STAGE 2
Y1 COMPRESSOR STAGE 1
HPTC
LAT
LATC
HPT
OAT
OATC
V+
RS+
RS-
VG
DAMPERS
8
1
CLS_
COM_
OPN_
=
=
=
CLOSE
COMMON = 24VAC FROM RZ
OPEN
OUTDOOR AIR
TEMP SENSOR
LEAVING AIR
TEMP SENSOR
HEAT PUMP
TEMP SENSOR
CLS3
COM3
OPN3
CLS4
COM4
OPN4
ZONE 3
DAMPER
ZONE 4
DAMPER
CLS1
COM1
OPN1
CLS2
COM2
OPN2
ZONE 1
DAMPER
ZONE 2
DAMPER
JUMPER NEEDED
FOR HEAT PUMP
APPLICATIONS DAMPER
FUSE
3A
OPTION
SWITCHES
NOTE SWITCH
#8 IS AT TOP
D20
(LED)
NOTES: *= OPTIONAL COMPONENTS
= INSTALLING ZONE 1 REMOTE SENSOR AT OS1AND OS1C WILL OVERRIDE
TEMPERATURE SENSOR ON USER INTERFACE
= COMMUNICATION BUS ARE IN PARALLEL WITH EACH OTHER
(EITHER CONNECTOR CAN BE USED)
DEFROST
†
†
REMOTE
SENSORS
COMMUNICATION
BUS
ZONE 3
SENSOR
ZONE 4
SENSOR
OPTIONAL
ZONE 1
SENSOR
ZONE 2
SENSOR
V+
COMMUNICATION
BUS
RS+
RS-
VG
OS1
OS1C
ZS2
ZS2C
ZS3
ZS3C
ZS4
ZS4C
V+
USER INTERFACE
RS+
RS-
VG
VG
V+
SMART SENSORS*
RS+
RS-
WHITE
RED
BLUE/YELLOW
GREEN
WHITE
RED
BLUE/YELLOW
GREEN
†
†
†
—6—
→

even though its instructions say to do so. The necessary interlock-
ing to keep both the heat pump and furnace from operating at the
same time is done by Zone Perfect Plus.
The special 3-stage auxiliary heat feature of Bryant thermostats is
incorporated into Zone Perfect Plus. This requires an FK type fan
coil and specific heater packages with a single-speed heat pump.
See FK fan coil Installation Instructions.
IX. UNDERSTANDING SEQUENCE OF OPERATION
A. Temperature Set Points
The Zone Perfect Plus System uses 2 temperature set points for
each zone, the higher for cooling and the lower for heating. A
minimum difference of 2°F is enforced between the 2 set points.
Each set point may be manually adjusted or controlled by a
programmed time schedule established by the home or business
owner.
B. Heating and Cooling Comfort Set Points
If space temperature is between heating and cooling set points for
the zone, then the zone is said to be "satisfied" with respect to
temperatures. When a zone is satisfied, no heating or cooling is
required. When all zones are satisfied, there is no demand and the
equipment is turned off. For example, if cooling set point is 76°F
and heating set point is 72°F, then a space temperature of 73°F is
assumed to be satisfactory and no heating or cooling of the zone is
required.
If space temperature in a zone falls below heating set point, then
that zone needs to have heat added to zone which will raise space
temperature back to heating set point. For example, if heating set
point is 72°F and space temperature is 70°F, then space tempera-
ture must be raised 2°F in order for zone to be satisfied. In this
case, temperature "heating demand" for zone is 2°F. (72° minus
70°F.)
Otherwise, if space temperature in a zone rises above cooling set
point, then that zone needs to have heat removed from zone which
will lower space temperature back to cooling set point. For
example, if cooling set point is 76°F and space temperature is
77°F, space temperature must be lowered 1°F in order for zone to
be satisfied. In this case, "cooling demand" for zone is 1°F. (77°
minus 76°F.)
C. Out Feature
A new feature called OUT can be selected via the OUT button.
When this selection is made, the system is being told that the
→Fig. 11—8-Zone System Wiring Diagram A98087
O REVERSING VALVE COOL
B REVERSING VALVE HEAT
RH HEATING TRANSFORMER
DHUM DEHUMIDIFY
DEF DEFROST
RC COOLING TRANSFORMER
SEE
FIGURES FOR
EQUIPMENT
WIRING
24 VAC ZONING
TRANSFORMER C
RZ
8 ZONE EQUIPMENT CONTROLLER
HUM HUMIDIFY
G FAN
W2 HEAT STAGE 2
W1 HEAT STAGE 1
Y2 COMPRESSOR STAGE 2
Y1 COMPRESSOR STAGE 1
CLS7
COM7
OPN7
CLS8
HPTC
LAT
LATC
HPT
OAT
OATC
DAMPERS
8
1
CLS_
COM_
OPN_
=
=
=
CLOSE
COMMON = 24VAC FROM RZ
OPEN
COM8
OPN8
ZONE 7
DAMPER
ZONE 8
DAMPER
OUTDOOR AIR
TEMP SENSOR
LEAVING AIR
TEMP SENSOR
HEAT PUMP
TEMP SENSOR
CLS5
COM5
OPN5
CLS6
COM6
OPN6
ZONE 5
DAMPER
ZONE 6
DAMPER
CLS3
COM3
OPN3
CLS4
COM4
OPN4
ZONE 3
DAMPER
ZONE 4
DAMPER
CLS1
COM1
OPN1
CLS2
COM2
OPN2
ZONE 1
DAMPER
ZONE 2
DAMPER
JUMPER NEEDED
FOR HEAT PUMP
APPLICATIONS DAMPER
FUSE
3A
OPTION
SWITCHES
NOTE SWITCH
#8 IS AT TOP
D20
(LED)
DEFROST
NOTES: *= OPTIONAL COMPONENTS
= INSTALLING ZONE 1 REMOTE SENSOR AT OS1AND OS1C WILL OVERRIDE
TEMPERATURE SENSOR ON USER INTERFACE
= COMMUNICATION BUS ARE IN PARALLEL WITH EACH OTHER
(EITHER CONNECTOR CAN BE USED)
†
†
V+
RS+
RS-
VG
REMOTE
SENSORS
COMMUNICATION
BUS
ZONE 3
SENSOR
ZONE 4
SENSOR
OPTIONAL
ZONE 1
SENSOR
ZONE 2
SENSOR
V+
COMMUNICATION
BUS
RS+
RS-
VG
OS1
OS1C
ZS2
ZS2C
ZS3
ZS3C
ZS4
ZS4C
ZONE 7
SENSOR
ZONE 8
SENSOR
ZONE 5
SENSOR
ZONE 6
SENSOR
ZS5
ZS5C
ZS6
ZS6C
ZS7
ZS7C
ZS8
ZS8C
V+
USER INTERFACE
RS+
RS-
VG
VG
V+
SMART SENSORS*
RS+
RS-
WHITE
RED
BLUE/YELLOW
GREEN
WHITE
RED
BLUE/YELLOW
GREEN
†
†
†
—7—
→

selected zone is unoccupied. It will normally supply no condition-
ing to an OUT zone. If zone temperature exceeds 85°F or goes
below 60°F, conditioning will be supplied to maintain the zone
within these limits.
The system will also use OUT zones to relieve the equipment
under overload conditions. If the total demand from all zones is
such that airflow is insufficient (or bypassing is excessive) this
condition will be sensed by the LAT or HPT temperature sensors.
When these temperatures begin to approach their limits, Zone
Perfect Plus will first begin to open dampers in the OUT zones to
relieve overload condition. The system will also monitor tempera-
tures in the OUT zone and never allow them to become cooler than
the coolest zone (in cooling) or warmer than the warmest zone (in
heating). This prevents over conditioning of OUT zones while still
using them to relieve an overload condition.
Zones can be set to OUT at any time or OUT can be programmed
like any other temperature. The home or business owner can then
program OUT for times that the zone is not likely to be occupied.
When OUT is selected, both heating and cooling set points are
replaced by "--."
D. Sequence Of Events For Normal Heating Or Cooling
Cycle
Given comfort set points and space temperature for zones within
system, Zone Perfect Plus will determine if active heating or
cooling is required. If so, Zone Perfect Plus will perform the
following:
1. Fully open 1 or more dampers and position others so that all
zones will be conditioned back to their set points at the
same time.
2. Turn on equipment.
3. While equipment is on, continually make small adjustments
in damper positions so that all zones converge on their set
points at the same time.
4. Turn off equipment when all zones reach their set points.
5. Leave dampers at their final positions while equipment is
off.
6. If equipment does not run for 2 hours, it will fully open all
dampers.
This is the basic sequence of operation for the Zone Perfect Plus
system. The actual control of dampers, HVAC equipment, and
system fan will change with the configuration of system. Depend-
ing upon configuration, Zone Perfect Plus can control heat pumps,
furnaces, and dual fuel applications.
E. Control Strategy for Heating / Cooling Stages
The Zone Perfect Plus system will attempt to minimize use of
additional stages of heating or cooling equipment.
Zone Perfect Plus controls multi-stage equipment in response to
the level of demand and the number of zones with demand. In
general, it tries to satisfy demand with a minimum number of
stages. In heat pump systems, where auxiliary heat is usually
expensive, a small extra demand is required to bring on auxiliary
heat. This acts to prevent the unnecessary use of auxiliary heat. In
addition, when an outdoor sensor is attached, the system can be set
to lock out auxiliary heat for outdoor temperatures above an
installer selectable value. This will be covered under System
Configuration.
SYSTEM CONFIGURATION
Zone Perfect Plus must be configured to match the type of
equipment connected to it. In addition, there are several choices of
configuration based on how the user wants the system to operate.
Configuration is done in 2 parts. One is the setting of 8 DIP
switches on the Equipment Controller. The second is a group of 11
software selections made via User Interface. Follow the sequence
below for easy setup.
Configuration of the Equipment Controller is done first with the
power off. Then power is applied and the User Interface is
configured with power on.
NOTE: A DIP switch module is oriented with switch 1 at the
bottom and switch 8 at the top. Refer to Fig. 12 for switch
orientation and labels.
I. EQUIPMENT CONTROLLER CONFIGURATION
Located near bottom of Equipment Controller circuit board, there
is an 8 section DIP switch. The use of each switch is described
below. Using a pen or pencil, set each switch to its proper state.
ON is to the left and is the factory setting. OFF is to the right. Fig.
12 is a pictorial drawing of this selector switch.
Switch 1—Selects AC or HP.
ON—Selects AC.
OFF—Selects HP.
Switch 2—Selects single- or 2-speed compressor.
ON—Selects single speed.
OFF—Selects 2 speed.
Switch 3—Selects 3-stage electric heat. Equipment must include
FK fan coil with single-speed heat pump and selected heater with
2:1 ratio element size.
ON—Normal 1- or 2-stage electric heat.
OFF—Special 3-stage electric heat.
Switch 4—Selects Smart Recovery in both heating and cooling.
The system starts adjusting temperature 1-1/2-hours earlier than
selected recovery time so it will arrive at new temperature at
selected time.
ON—Smart recovery.
OFF—Normal recovery.
Switch 5—Zone system address selection. When 2 zoning systems
are connected together, the second system should be set to OFF.
ON—Normal single system.
OFF—Address selection for second zoning system.
Switch 6—Select installer test mode to assist in checking out the
system. See Starting System.
ON—Selects normal operation.
OFF—Selects installer test mode.
Switch 7—Disables cooling when outdoor temperature is below
55°F. Requires outdoor air temperature sensor.
ON—Cooling enabled at all temperatures.
OFF—Low temperature cooling disabled.
Switch 8—Dual fuel selection for systems with heat pump and
furnace.
ON—Selects normal system.
OFF—Selects dual fuel system.
II. USER INTERFACE CONFIGURATION
The User Interface is configured via a group of selections made
through the keypad in a special configuration mode. Before the
equipment is operated, the system must be properly configured.
Make sure this step is not left out.
Before turning power on to the zoning system, disable the system
equipment itself by either turning off its main power or by
temporarily disconnecting its 24-vac power at the RC and RH
terminals of the Equipment Controller. This will allow the zoning
system only to operate. Go through the following steps with the
equipment power off.
By this time 8 DIP switches on the Equipment Controller should
be properly set.
Turn on power to the zoning system by applying power to its
24-vac transformer. When power is first applied to Zone Perfect
Plus the Equipment Controller immediately begins positioning all
dampers to fully open by running each damper motor in the open
direction for 15 sec. This is done in succession, 2 zones at a time,
starting with Zone 1. The time required will be 15 sec for each pair
of zones. Remember that the system automatically determines the
number of zones by detecting the presence of zone sensors.
—8—
→
→
→
→

At power up the User Interface displays all segments for a few sec.
This is followed by the selected system type for an additional few
sec. The system type shows as follows:
1. AC—1-Speed Air Conditioner
2. HP—1-Speed Heat Pump
3. A2—2-Speed Air Conditioner
4. H2—2-Speed Heat Pump
5. AS—1 or 2-Speed Air Conditioner with 3-Stage Auxiliary
Heat
6. HS—1 or 2-Speed Heat Pump with 3-Stage Auxiliary Heat
7. dF—Dual Fuel with 1-Speed Heat Pump
8. d2—Dual Fuel with 2-Speed Heat Pump
Power-on check of the User Interface itself can be done by
separating the User Interface from its backplate and then recon-
necting it by attaching the 2 parts. This will allow observation of
the User Interface at power up.
Several installer select options are set using the User Interface
keypad.
These configuration options, like DIP switch settings, are intended
to be selected at installation and are normally not modified by
home or business owner. These options are not discussed in the
Owner’s Guide and therefore must be made as part of the
installation. A special procedure allows entry into configuration
mode. Zone Perfect Plus will automatically exit this mode if no
button is pressed for 3 minutes. While in the configuration mode,
11 configuration choices can be made. In addition, LAT and HPT
temperatures as well as all damper positions can be viewed. A brief
description of each is given below, followed by instructions on
how to make the selection.
A. To Enter the Configuration Mode:
Press and hold FAN button for approximately 10 sec until room
temperature and set point displays change to 2 numbers. You are
now in the configuration mode.
Option 1—Clean filter timer
Option 2—English/Metric
Option 3—Fan ON with W
Option 4—User Interface address
Option 5—Disable zoning
Option 6—Ignore LAT and HPT safeties
Option 7—Variable speed blower present
Option 8—Select LAT shutdown temperature
Option 9—Auxiliary heat lockout
Option 10—Dual fuel crossover temperature
Option 11—Auto changeover timer
Option 12 to 18—Not available
Option 19—Display HPT temperature reading
Option 20—Display LAT temperature reading
Option 21 and up—Display zone damper positions.
NOTE: If END button is pressed or if no button is pressed for 180
sec, Zone Perfect Plus will exit configuration mode and return to
normal operation. To re-enter configuration mode, FAN button
must be pressed and held for 10 sec again.
While in configuration mode, the large display shows the selection
which has been made and the smaller display (COOL set point
display) shows current option number. One of these will be
flashing.
The up and down buttons are used both to move between available
options and to make selection for each option. When option
number (small display) is flashing, the up and down buttons adjust
it, moving between available option numbers. After desired option
number has been selected, press SET TIME/TEMP button. The
large display will now flash, indicating that the up and down
buttons now control available choices within that option. Each
press of the SET TIME/TEMP button switches between available
option (small display) and available selections within each option
(large display).
Available options and available selections for each are described
below.
OPTION 1—CLEAN FILTER TIMER
Select hours of blower operation (heating, cooling, or fan) before
CLEAN FILTER icon is displayed. With OFF selected, icon will
never come on, disabling this feature. Time selection can be from
400 to 3600 hours by selecting numbers 1 through 9. (Time is
400X number selected.) Factory default is 2 (800 hours). Recom-
mended selections are: disposable filter—400 to 800 hours, media
filter—1200 to 1600 hours, or electronic air cleaner—1600 to 2400
hours of blower operation.
TO SELECT or ADJUST:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 1 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
Factory default is 2.
4. Use up and down buttons to alternate between OF (off), 1,
2, 3, 4, 5, 6, 7, 8, or 9.
→Fig. 12—DIP Switch Settings A98183
NORM
NORM
NORM
NORM
SMART
RECOVERY
1 SPD
AC
ON
(CLOSED)
NORM
DISABLE LOW
TEMP COOLING
INSTALLER TEST MODE
ADDRESS 11
3 STG HEAT
NORM
2 SPD
HP
OFF
(OPEN)
DUAL FUEL
7
6
5
3
4
2
1
8
Switch factory
default is closed.
NOTE:
—9—
→
→
→

5. Press SET TIME/TEMP button to flash 1 on small display.
Up and down buttons now move between option choices.
Or press END button to exit configuration mode.
OPTION 2—ENGLISH/METRIC
Select between Fahrenheit or Celsius operation. Factory default is
Fahrenheit.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 2 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up or down buttons to alternate between F and C.
5. Press SET TIME/TEMP button again to flash 2 on small
display, or press END button to exit configuration mode.
OPTION 3—FAN ON WITH W
This selection determines whether the G (fan) output is to be ON
or OFF when any W (furnace or strip heat) output is ON. Most
furnaces and fan coils manage their own blowers and do not
require a separate G signal. For these applications, select OFF.
Some auxiliary heaters require a separate G signal to turn on the
blower. In this case, select ON. Factory default is OFF.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 3 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between OF (off) and
ON.
5. Press SET TIME/TEMP button again to flash 3 on small
display, or press END button to exit configuration mode.
OPTION 4—USER INTERFACE ADDRESS
When 2 Zone Perfect Plus systems are connected together on the
same bus, each must have a different address. Address 01 is used
for single systems. Address 11 is selected for second User
Interface when present. Factory default is 01.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 4 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between 01 and 11.
5. Press SET TIME/TEMP button again to flash 4 on small
display, or press END button to exit configuration mode.
OPTION 5—DISABLE ZONING
When this option is selected, all dampers go fully open and zone
1 sensor (normally User Interface itself) becomes the sensor for the
entire home or business. In effect, the zoning system disappears
and is replaced by a single thermostat. In this mode, the ZONE X
where X is the zone number is not displayed. Factory default is OF
(off), zoning enabled. This option is used to check out the system
equipment. The User Interface acts as normal thermostat.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 5 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between ON and OF
(off). Remember: OF (off) enables zoning, ON disables
zoning.
5. Press SET TIME/TEMP button again to flash 5 on small
display, or press END button to exit configuration mode.
OPTION 6—IGNORE LAT AND HPT TEMPERATURES
CAUTION: Leaving this selection ON can cause perma-
nent damage to HVAC equipment
This option, when ON, tells the system to ignore the LAT and HPT
temperature information. It should only be used for troubleshoot-
ing and to allow temporary operation with a failed or missing
sensor until the sensor can be replaced. Factory default is OF (off).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 6 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between ON and OF
(off). Remember ON is for temporary use only.
5. Press SET TIME/TEMP button again to flash 6 on small
display, or press END button to exit configuration mode.
OPTION 7—VARIABLE SPEED (ICM) OR PSC BLOWER
If the furnace or fan coil contains a variable speed ICM blower, set
this option ON. For normal (PSC) blowers, set to OF (off). This
selection enables the system to use the special dehumidification
features available only with the ICM blower. Factory default is OF
(off).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 7 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between OF (off) and
ON.
5. Press SET TIME/TEMP button again to flash 7 on small
display, or press END to exit configuration mode.
OPTION 8—LEAVING AIR TEMPERATURE (LAT) SHUT-
DOWN TEMPERATURE
This option selects maximum allowable LAT in furnace and fan
coil auxiliary heat installations. Equipment will be turned off if its
LAT exceeds selected value. Values are 35, 40, 45, 50, 55, 60, 65,
70, or 75 corresponding to temperatures of 135° to 175°F. As LAT
nears selected limit, actions are taken by the system to try to reduce
the LAT. These include staging down multi-stage equipment and
limited conditioning of OUT zones.
When the LAT temperature approaches its limit, OUT zone
dampers progressively open, allowing more airflow into the duct
system. The temperatures of the OUT zones are also monitored. As
any OUT zone approaches the temperature of the most conditioned
zone, its damper closes again, preventing the OUT zone from
being over conditioned. If OUT zones are not available and LAT
temperature cannot be maintained at a safe value, the system will
shut down the equipment when the LAT temperature reaches its
limit. With earlier Comfort Zone systems, temperature set here
was temperature where actions were started. Shutdown tempera-
ture was 20°F higher than selected temperature. Therefore a setting
of 155°F on Zone Perfect is equivalent to 175°F on Zone Perfect
Plus.
HPT temperature limit for shut down is fixed at 115°F and cooling
LAT temperature limit for shut down is fixed at 40°F (down from
Zone Perfect which was 45°F.)
Fan coils vary greatly in their LAT (leaving air temperature)
because of variations in the size of their heaters and their air flow.
This makes proper selection of LAT limits difficult. A value of 50
—10—
→
→
→

(150 °F limit) should be adequate. After the system is in operation,
LAT can be monitored via User Interface (configuration option 20)
to check actual operating temperature. For furnaces select a value
of 75°F plus the rated maximum temperature rise from the furnace
nameplate. Factory default is 50 (or 150°F).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 8 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between 35, 40, 45,
50, 55, 60, 65, 70, and 75.
5. Press SET TIME/TEMP button again to flash 8 on small
display, or press END button to exit configuration mode.
OPTION 9—AUXILIARY HEAT/DUAL FUEL UPPER LOCK-
OUT TEMPERATURE SELECTION
This option is available only with heat pump and dual fuel systems.
In heat pump systems, auxiliary heat is prevented from coming on
while outdoor temperature is above the selected value. In dual fuel
systems, the furnace is prevented from operating while outdoor
temperature is above the selected value. This temperature must be
set higher or equal to that of option 10. (See option 10 below.)
Outdoor temperatures of 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, or
55°F, or OF (off) may be selected. If OF (off) is selected, outdoor
temperature does not affect system operation. Factory default is
OF (off).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 9 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between OF (off), 5,
10, 15, 20, 25, 30, 35, 40, 45, 50, or 55.
5. Press SET TIME/TEMP button again to flash 9 on small
display, or press END button to exit configuration mode.
OPTION 10—DUAL FUEL LOWER LOCKOUT
TEMPERATURE SELECTION
This option is only available with dual fuel systems. While outdoor
temperature is below the selected value, only the furnace is used
for heating. This option must be set higher than or equal to that of
option 9. (See option 9 above.) If the temperature selections of
option 9 and 10 are set to the same value, a dual fuel system will
use the heat pump only above this temperature and the furnace
only below this temperature. If the selections are different, the
range between the 2 selections will use the heat pump as the first
stage and the furnace as the second stage. Once the furnace comes
on, it will remain on until the demand is satisfied. The following
cycle will start with the heat pump. Outdoor temperatures of 5, 10,
15, 20, 25, 30, 35, 40, 45, 50, or 55°F, or OF (off) may be selected.
If OF (off) is selected, outdoor temperature does not affect system
operation. Factory default is OF (off).
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 10 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between 5, 10, 15, 20,
25, 30, 35, 40, 45, 50, 55, and OF (off).
5. Press SET TIME/TEMP button again to flash 10 on small
display, or press END to exit configuration mode.
OPTIONS 11—AUTO CHANGEOVER TIMER
This option selects either a 10 or 30 minute time delay between
heat and cool while in auto changeover mode. System must have
no demand in current mode for selected time (10 or 30 minutes)
before changeover between heating and cooling is allowed. Fac-
tory default is 30 minutes.
TO SELECT:
1. Enter configuration mode (if not already there).
2. Use up and down buttons to display 11 on flashing small
display.
3. Press SET TIME/TEMP button once to flash large display.
4. Use up and down buttons to alternate between 30 and 10.
5. Press SET TIME/TEMP button again to flash 11 on small
display, or press END to exit configuration mode.
OPTIONS 12-18—NOT AVAILABLE
OPTION 19—DISPLAY HPT TEMPERATURE READING
OPTION 20—DISPLAY LAT TEMPERATURE READING
OPTION 21 AND UP—DISPLAY DAMPER POSITIONS
These options allow direct viewing of the temperatures of the HPT
and LAT sensors and the positions of all zone dampers. They are
useful for setup and troubleshooting. When these options are
selected, the temperatures or positions appear on the large display.
All other system operation is unchanged. Zone 1 damper position
appears as option 21, Zone 2 as option 22, and so on for all zones.
Closed position is 0. Fully open is 15. Temperature above 100°F
are shown as the amount above 100.
TO SELECT:
1. Enter the configuration mode.
2. Use up or down buttons to display 19 for HPT, 20 for LAT,
or 21 and up for positions on small display. The correspond-
ing values will appear on the large display.
3. When finished viewing, use up or down buttons to select
other options or press END button to exit configuration
mode.
SYSTEM STARTUP AND CHECKOUT
Zone Perfect Plus is designed with built-in checkout capability for
both the equipment and the zoning system. Use the sequence
below for trouble free setup. When it is time to start up system for
the first time, you may want to check out the zoning system first
and the equipment second or to reverse the process, checking
equipment first and zoning system second. Either way is accept-
able.
The following sequence checks out zoning system first. If you
wish to check equipment first, proceed to Step 4 below. Then, after
equipment is operating properly, return to Steps 1, 2, and 3 to
check out zoning system.
I. ENABLE INSTALLER SETUP MODE
Before proceeding, temporarily disconnect all Y and W wires at
Equipment Controller so that heating and cooling cannot occur
during Steps 1 and 2. Leave G connected so that fan can operate.
Select installer setup mode at the Equipment Controller by moving
DIP switch No. 6 to the OFF position. (See Fig. 12.) This may be
done with power on or off. This mode is indicated by InSt
appearing in the User Interface clock display. In this mode
several special features are available to assist in the setup/checkout
process:
a. When a zone is selected with the NEXT ZONE button,
its damper opens fully and all other dampers close.
b. The selected zone’s temperature appears on the large
display.
—11—
→
→

c. The FAN button turns the blower ON or OFF.
d. The MODE button operates HEAT, COOL, or EHEAT
for 2 minutes and then returns automatically to OFF. No
demand from the zones is needed to bring on the
equipment in installer setup mode.
II. CHECK DAMPER AND SENSOR OPERATION
At the User Interface, set the mode to OFF using the MODE
Button to make sure cooling or heating outputs are not turned on.
Use the FAN button to turn on the blower by selecting ON (not
AUTO) under the fan icon. This will start the blower (if its supply
power is on). Use the NEXT ZONE button to select ZONE 1 above
the large display. This will open Zone 1 fully and close all other
zones. It will take the system 15 sec for each zone to complete this
process.
You may now observe the dampers to verify their positions are
correct (and check for air blowing out all Zone 1 registers only).
The large display reads the temperature in Zone 1. Use this
opportunity to verify the Zone 1 sensor is properly connected and
is located in Zone 1 by breathing on the Zone 1 sensor and
observing the temperature change. Remember, the Zone 1 sensor is
normally inside the User Interface but a remote sensor may be
used.
Use the NEXT ZONE button to select Zone 2 and repeat the above
process. Continue through all zones. When finished, you will have
verified that all the dampers and zone sensors are properly
connected and working.
III. QUICK CHECK OF EQUIPMENT OPERATION
Either this or the next step (Step 4) may be used for initial startup.
This check runs equipment for only 2 minutes on each stage and is
adequate to see that each stage comes on properly. For temperature
rise, charge levels, etc. use the longer check, or disable zoning
feature.
Be sure installer setup is still selected (Equipment Controller DIP
switch No. 6 is OFF).
Reconnect W and Y wires to enable equipment operation.
At User Interface, select HEAT mode. The first stage of heat will
come on immediately (no temperature demand is needed). For a
heat pump, this will be Y1 and G. For an air conditioning system,
this will be W1. The first stage will remain on for 2 minutes. Then
the second stage of heat will come on for 2 minutes. This will be
Y1, Y2, and G for a heat pump, or W1 and W2 for an air
conditioning system. At the end of 4 minutes, equipment will turn
off and mode will automatically return to OFF. If mode is set to
OFF at any time during 4 minutes, equipment will turn off
immediately. Note that single stage system (heat or cool) will
remain on for full 4 minutes because there will be no connection
to Y2 or W2.
The same applies to COOL. When selected, cooling will come on
immediately with no need for temperature demand. First stage will
be Y1, G (and O if a heat pump) and will run for 2 minutes. Then
Y1, Y2, G (and O if a heat pump) will come on for next 2 minutes.
At the end of 4 minutes equipment will turn off and mode will
return to OFF.
In a heat pump system, EHEAT may also be selected at User
Interface. This will turn on W1 only for first 2 minutes and then
W1 and W2 for the second 2 minutes. The compressor will not run.
As above, equipment may be turned off at any time during the 4
minutes by setting mode to OFF.
For all operation in this installer setup mode, no demand is needed,
no compressor timeguard exists, and no temperatures are moni-
tored. This means there is no protection for equipment, and this is
the reason that operation is limited to 4 minutes.
When leaving this step, be sure to return installer setup switch
(Equipment Controller DIP switch No. 6) to ON position. This will
enable normal operation.
When any output is turned on, a red LED on the Equipment
Controller board adjacent to the output’s connection terminal is
also turned on. This can be used at any time to monitor the state of
the Equipment Controller outputs, even if the equipment is not yet
connected or powered. Remember, the DEHUM output is a reverse
logic relay. This means its LED will be ON while there is no
dehumidify demand. See dehumidification section.
IV. LONGER CHECK OF EQUIPMENT OPERATION
When more detailed tests need to be made on equipment, the 2 or
4 minute run time provided in Step 3 may not be adequate. By
selecting disable zoning mode (turn Option No. 5 to ON under
User Interface configuration), system operates like a standard
thermostat system. All dampers go fully open, and the zone which
is displayed on User Interface provides set points. This zone’s
temperature is the only controlled temperature. Equipment will
operate as if it were being controlled by a single thermostat in the
displayed zone. Use this option to check out equipment as you
would with a normal thermostat. When finished, be sure to return
to the configuration mode and turn Option No. 5 OFF to enable
normal zoning operation.
FINAL INSTALLATION SETTINGS
→HUMIDIFICATION
If a humidifier is included in the system, Zone Perfect Plus can
directly control it. If a conventional humidity control exists, it
should be removed and the zoning system used in its place. Zone
Perfect Plus provides superior convenience and features. When
installing a 24-vac humidifier, connect it directly to the HUM
terminal on the Equipment Controller and C terminal of indoor
equipment.
A humidity sensor is built into the User Interface to monitor and
control relative humidity. The HUM output will control any
humidifier with a 24-vac input. A humidify set point can be set by
the home or business owner to any value between 10 percent and
45 percent or can be turned off. When the humidity drops 2 percent
below the set point, the HUM output is activated to turn on a
humidifier. When the humidity rises 2 percent above the set point,
the HUM output will turn off.
When an outdoor air temperature sensor is attached, an automatic
humidity level adjustment can be selected. This selection provides
a 1 percent reduction in the humidity set point for every 2 degrees
reduction in outdoor temperature. The set point can be changed at
any time, and it will then automatically adjust itself up and down
with changes in outdoor temperature. In no case will the set point
go above 45 percent or below 10 percent. This feature is to prevent
sweating of windows in very cold weather while allowing higher
humidity levels in warmer weather.
Another selection involves the interlocking of the HUM output to
heating or fan operation. The HUM output can be set to come on
only when there is a humidity demand and any heat output is on
(heat pump, furnace, or auxiliary heat). A second setting allows the
HUM output and the blower to turn on when there is humidity
demand. This selection allows humidification with the fan when
there is a no heat call. In no case will the HUM output be on
without either heat or fan.
It may be advisable to configure the humidity control as part of the
installation process. Following is a brief description of the hu-
midify setup process. It is also covered in the Owner’s Manual.
There are 5 selections for humidification in the heating mode:
1. Normal Humidify
2. Fan Humidify
3. Auto Humidify
4. Auto and Fan Humidify
5. OFF
—12—
→
→
→

To make a humidification selection or change the humidity (hu) set
point, a 2-button keypad press is required. Press SET TIME/TEMP
and FAN buttons simultaneously (indicated on the keypad by the
RH symbol) to enter the humidity mode. Either hu (humidify) or
dhu (dehumidify) will appear on the display. Use the SET
TIME/TEMP buttons to select hu (humidify). Now UP and
DOWN buttons may be used to adjust the value of the humidify set
point to a value between 10 and 45 percent. One of the following
humidification modes may also be selected:
1. Normal Humidify Mode — This is the factory default. This
configuration will bring on the humidifier only in the
heating mode when there is a humidify demand.
2. Fan Humidify Mode — This is selected by pressing FAN
button to turn on FAN icon. This configuration allows a
humidify demand to turn on the fan and humidifier together,
even if there is no heat demand.
3. Auto Humidify — This is selected by pressing MODE
button to turn on AUTO icon. This configuration allows the
rh set point to automatically track and adjust according to
the outdoor air temperature. The set point will automatically
increase or decrease with every 2°F change in outdoor
temperature between 0° to 50°F. To use this feature an
outdoor air sensor must be attached, or an E3 error will
occur.
4. Auto and Fan Humidify — This is selected by pressing both
MODE button and FAN button to turn on AUTO and FAN
icons. This configuration combines both fan humidify and
auto humidify together in bringing on the humidifier when
there is a humidify demand (without any heating demand),
and will automatically track and adjust the rh set point
according to the outdoor air temperature.
5. Humidify Off — This is used to disable the humidify mode.
To turn the humidify function OFF, use DOWN button to
scroll the humidity set point all the way down. The lowest
setting will be 10 percent before off (OF) appears in the
display. When OF is displayed, the humidification mode is
disabled.
To exit humidity setup mode, press END button, or if no buttons
are pressed for 3 minutes, the User Interface will save and exit this
mode returning to normal operation.
→DEHUMIDIFICATION
Zone Perfect Plus contains a rich set of capabilities for the
enhancement and control of dehumidification, particularly when
used with a variable speed (ICM) blower.
A dehumidification set point(separate from the humidification set
point) can be set to a value between 50 percent and 90 percent
humidity or can be turned off. When the humidity rises above this
set point by 2 percent, the dehumidify output is turned off. When
the humidity falls to 2 percent below this set point, the dehumidify
output turns on, supplying 24vac at its output. This output can be
used to control any 24-vac device which decreases humidity when
its control signal is removed.
When a variable speed blower with a dehumidify input is used
with the system, the dehumidify output can be connected to its
dehumidify input. This connection provides reduced cooling air
flow while dehumidification is needed yielding better moisture
removal from cooling air.
If the system has a 2-speed compressor (as selected by Equipment
Controller DIP switch No. 2) and a PSC blower (as selected by
User Interface Option No. 7), a dehumidify demand will make
compressor operate at high speed only for any cooling demand.
High speed provides better water removal than low speed when a
2-speed compressor is used with PSC blower.
Another selection provides humidity control by operating the
cooling system when cooling is not required. If the humidity rises
above the dehumidification set point, a special dehumidification
routine is executed. As long as zone temperatures are not more
than 3°F below their cooling set points, a dehumidify demand will
turn on the cooling equipment but will limit its ON time to no more
than 7 minutes at a time.
Finally, OUT zones are used to their maximum capability. When
a zone is set to OUT it can be used to help remove humidity by
cooling it as much as possible. When there is a dehumidify demand
and a zone set to OUT, its damper is fully opened, and it can be
cooled down to as low as 70°F. If it reaches 70°F its damper will
close.
When all zones are set to OUT the house or business is in vacation
mode. The cooling equipment will come on either to maintain the
house or business below 85°F or to maintain the dehumidify set
point by cooling the house or business down to as low as 70°F.
This is a valuable feature for unoccupied homes or businesses in
hot and damp climates.
IMPORTANT: It may be advisable to configure the dehumidify
control as part of the system installation process. Following is a
brief description of the dehumidify setup process. It is also covered
in the Owner’s Manual.
There are 4 selections for dehumidification in the cooling mode:
1. Normal Dehumidify
2. Cool to Dehumidify
3. Vacation Dehumidify
4. OFF
To make a dehumidification selection or change the dehumidify
(dhu) set point, a 2-button keypad press is required. Press SET
TIME/TEMP and FAN buttons simultaneously (indicated on the
keypad by the RH symbol) to enter the humidity mode. Either hu
(humidify) or dhu (dehumidify) will appear on the display. Use
SET TIME/TEMP buttons to select dhu (dehumidify). Now UP
and DOWN buttons may be used to adjust the value of the
dehumidify set point to a value between 50 and 90 percent. One of
the following dehumidification modes may also be selected:
The dehumidify relay is a reverse logic relay. When the humidity
level is above the dehumidify set point, the DHUM relay is off.
When the humidity level is below the dehumidify set point, the
DHUM relay is on.
When in the dehumidification mode, the following can be selected:
1. Normal Dehumidify Mode — This is the factory default.
The dehumidification feature is designed for use with
variable speed indoor equipment. When normal dehumidify
is selected, the compressor will not turn on without a
cooling demand. If a dehumidify demand exists while
cooling, the dehumidify output will be active (i.e. 24vac
removed from DHUM).
2. Cool to Dehumidify Mode — This is selected by pressing
the MODE button to turn on the COOL icon. In selecting
this mode, you are controlling to the rh set point. The cool
to dehumidify feature allows the system to turn on the air
conditioning (i.e. Y output) as needed to try to reach the
selected set point. The equipment will be cycled for
approximately 7 minutes on, and 8 minutes off to control
the humidity. Zone temperatures may be over conditioned
up to 3°F when trying to lower the humidity level. If a
cooling demand exists at the same time as a dehumidify
demand, then the equipment will run until the cooling
demand is satisfied.
3. Vacation Dehumidify — This is selected by selecting the
above cool to dehumidify function (turning on COOL icon),
then exit the humidity program by pressing END key. Next,
press HOLD, OUT, and ALL ZONE buttons in that order to
program all zones to an unoccupied status. The air condi-
tioning equipment will now turn on as needed to control to
the selected dehumidification set point, but it will not drop
the indoor temperature lower than 70°F.
—13—

4. Dehumidify Off — This is used to disable the dehumidify
mode. To turn this function OFF, use UP button to scroll the
set point all the way up. The highest setting will be 90
percent before off (OF) appears in the display. When OF is
displayed, the dehumidification mode is disabled (the
DHUM relay will remain on).
To exit humidity setup mode, press END button, or if no buttons
are pressed for 3 minutes, the User Interface will save and exit this
mode returning to normal operation.
OPERATIONAL INFORMATION
FIVE-MINUTE COMPRESSOR TIMEGUARD
This timer prevents the compressor from starting unless it has been
off for at least 5 minutes. It can be defeated for 1 cycle by
simultaneously pressing the FAN mode button and the UP button.
It is not active in the installer setup mode.
FIFTEEN-MINUTE CYCLE TIMER
This timer prevents the start of the next cycle until at least 15
minutes after the start of the present cycle. Its job is to assure that
equipment is not cycled more than 4 times per hour (or 1 cycle
every 15 minutes). It is defeated for 1 cycle when the desired set
point is manually changed to provide fast response to set point
change. It can also be defeated for 1 cycle by simultaneously
pressing the FAN mode and UP buttons.
STAGING TIMER
In multistage heating or cooling this timer prevents any higher
stage from coming on until the previous stage has been on for 10
minutes. The timer is extended to 15 minutes for heat pump
auxiliary heat and dual fuel furnace operation.
MINIMUM ON TIME
When a cooling or heating stage is turned on, it will remain on for
at least 3 minutes. These timers are canceled when set points are
changed.
HEAT/COOL SET POINT DIFFERENCE
A minimum deadband of 2°F is enforced between heating and
cooling set points. This is done by allowing one set point to "push"
the other to maintain this difference.
AUTO CHANGEOVER
When the auto changeover mode is selected, a change from heat to
cool or cool to heat cannot occur until a demand exists in the new
mode and no demand has appeared in the old mode for 30 minutes
or 10 minutes if option 11 is used. This prevents cycling
continually between heat and cool.
EMERGENCY HEAT MODE
When system is configured for a heat pump and EHEAT mode is
selected, Y outputs are disabled and W outputs only are used for
heat.
POWER-ON CHECK
When power is first applied to the system the large display
indicates the equipment type selected by DIP switches as follows:
1. AC—1-Speed Air Conditioner
2. HP—1-Speed Heat Pump
3. A2—2-Speed Air Conditioner
4. H2—2-Speed Heat Pump
5. AS—1 or 2-Speed Air Conditioner with 3-Stage Auxiliary
Heat
6. HS—1 or 2-Speed Heat Pump with 3-Stage Auxiliary Heat
7. dF—Dual Fuel with 1-Speed Heat Pump
8. d2—Dual Fuel with 2-Speed Heat Pump
OTHER MESSAGES
Small Arrow—A small arrow is located to the left of HEAT and
COOL icons which are located under the two set point displays.
These indicate when cooling or heating equipment is actually
operating. When arrows flash, equipment is waiting to come on but
is being held off by compressor timeguard, cycle timer, or because
LAT or HPT has exceeded its limits and temporarily turned
equipment off.
INITIAL POWER-ON PERFORMANCE
When power is applied to system all dampers are fully opened. As
operation progresses, the system "learns" optimum damper posi-
tions needed to maintain set points in all zones. This learning
process may require up to 2 hours of operation. Allow the system
time to complete its learning.
OVERSHOOT CONTROL
If for any reason a zone is overconditioned by more than 1.5
degrees and the equipment is still operating, that zone’s damper
will close until the overconditioning is less than 1.5 degrees.
TEMPERATURE BALANCING
Under heavy load conditions when the HVAC system does not
have sufficient capacity to maintain all set points, the system does
not automatically open all dampers fully. It continues to control
dampers to keep temperature error in each zone the same as all
others.
VENTILATOR MODE
An automatic ventilation mode is provided by keeping all dampers
at their final position while equipment is off. If the fan is left ON,
more air is supplied to zones which required most conditioning.
Those which required none will have their dampers closed. If 2
hours pass and there is no call for conditioning, all dampers open
fully. In addition, if the mode selection is set to OFF and the fan
selection is set to ON, all dampers will immediately open.
OUTPUTS VS. STAGES
Table 1 lists the active outputs for each stage of each possible
system configuration. G is not shown. It is turned on with any Y.
If installer setup No. 3 is on, G is also turned on with any W.
For 1-stage furnaces and auxiliary heat connect to W1 and leave
W2 open.
For single speed compressors, connect to Y1 and leave Y2 open.
—14—
→
→
→→

→SMART SENSOR OPERATION
NOTE: Refer to Smart Sensor Installation and Start-Up Instructions for proper installation and set-up procedure.
The Smart Sensor can control the setting of zone temperature, OUT, HOLD, or OFF. It can also display outdoor temperature and indoor humidity.
A97187
A. Changing Desired Temperature
1. The current temperature in that zone will be displayed in the LCD.
2. Press UP or DOWN button to display desired temperature for that zone. The LCD will display the
current mode of operation, either heat or cool.
3. Press UP or DOWN button again as needed until new desired temperature is shown.
4. Press SET TEMP button to change temperature between COOL desired temperature and HEAT
desired temperature.
5. Pressing HOLD button will hold desired temperature setting indefinitely. Pressing HOLD button
again removes HOLD function.
6. Pressing OUT button will program zone as being unoccupied. Pressing OUT button again changes
zone to occupied. When a zone is set to OUT, desired temperature will be displayed as dashes when
UP and DOWN buttons are pressed.
B. Viewing Outdoor Temperature and Indoor Humidity
1. Pressing both UP and DOWN buttons simultaneously will display outdoor temperature, if this
feature is included, and indoor humidity. Outdoor temperature will be displayed first for 5 sec,
followed by humidity for 5 sec. Smart Sensor will then return to normal. The humidity value will
be humidity level as measured at user interface.
NOTE: If All Zone feature has been enabled from user interface, you will not be able to override settings
at Smart Sensor location. The desired temperature will be displayed as dashes when UP and DOWN
buttons are pressed. You must first remove All Zone function by pressing ALL ZONE button on user
interface.
A Smart Sensor does not remove or transfer features from User Interface. It only provides a location within
zone where access is provided to some of User Interface features. Any input that can be provided at Smart
Sensor can also be provided at User Interface.
OUT
COOL
DESIRED TEMP
OUT
Smart Sensor display
with ALL ZONE enabled
—15—

→QUICK START
The quick start procedure outlined below will allow you to use
your zoning system before you learn all the details of system
operation. This setup may be done by the installer. For the best
comfort and energy-saving results, we recommend that you read
through the Owner’s Manual and setup the system to match the
end-user’s schedule and comfort requirements.
To begin, locate the User Interface and follow the steps outlined
below: (See Fig. 14.)
Set current day and time:
1. Press NEXT DAY button until current day of the week is
shown.
2. Press SET TIME/TEMP button until the TIME icon flashes.
3. Press UP or DOWN buttons until the desired time is shown,
making sure that the AM or PM time is correct.
4. Press HOLD/END key to exit.
Select system Mode:
1. Press MODE button to select HEAT or COOL.
2. Press HOLD/END button.
3. Press UP or DOWN button until the desired temperature is
displayed.
4. Press ALL ZONE button if this desired temperature is
needed for every zone. Otherwise press NEXT ZONE
button, and repeat HOLD function in selecting the desired
temperature for each zone.
→QUICK PROGRAMMING OF COMFORT SCHEDULES
The following is a brief overview of how to access and program
schedules in your new zoning system. We highly recommend that
you read and follow the programming information provided in the
Owner’s Manual for detail step-by-step instructions.
Before proceeding, set the correct Time and Day at the User
Interface (see above Quick Start).
However, if you followed the above Quick Start procedure in
selecting the system mode, you will need to reverse the ALL
ZONE and/or HOLD functions before proceeding. Simply press
ALL ZONE and/or HOLD button to remove these icons from the
display. (See Fig. 14.)
During the programming process, you will have access to 4
program time periods, e.g., WAKE, DAY, EVE, and SLEEP. You
will be able to select program start times and the heat/cool set
points for each time period and zone. Use the Keypad to enter and
move around inside the program. Use the temperature UP and
DOWN buttons to adjust the start times and to raise and lower set
points. When inside the program, the blinking icon indicates that a
setting may now be changed.
1. Decide on a program schedule that you desire. Table 2 is an
example of what already exists in the User Interface as the
Energy Star recommended setting.table
2. To begin programming, press PROGRAM button.
3. Press NEXT ZONE button until ZONE 1 appears on the
LCD display.
4. Press NEXT DAY button until Monday (Mo) is displayed.
5. Press NEXT PERIOD button until the WAKE period is
displayed.
6. Press SET TIME/TEMP button until the TIME icon is
flashing.
7. Start programming ZONE 1 beginning with the WAKE
start time. Press the UP or DOWN button until the desired
starting time is displayed, make sure that the AM is correct.
8. Press SET TIME/TEMP button until the HEAT icon is
flashing. Press UP or DOWN button until the desired
heating temperature for that period is displayed.
9. If that zone is going to be unoccupied, press OUT button.
For more information regarding the Out feature, read the
following section pertaining to Hold, Off, Out, and All
Zone.
10. Press SET TIME/TEMP button until the COOL icon is
flashing. Press UP or DOWN button until the desired
cooling temperature for that period is displayed. You have
now programmed the time and desired heating and cooling
temperatures for Monday, ZONE 1, in the WAKE time
period.
→TABLE 1—OUTPUTS VS. STAGES
SYSTEM TYPE COOL 2 COOL 1 HEAT 1 HEAT 2 HEAT 3 HEAT 4 HEAT 5
1-Speed AC N/A Y1 W1 W1,W2 N/A N/A N/A
with 3-Stage Heat N/A Y1 W1 W2 W1,W2 N/A N/A
2-Speed AC Y1,Y2 Y1 W1 W1,W2 N/A N/A N/A
with 3-Stage Heat Y1,Y2 Y1 W1 W2 W1,W2 N/A N/A
1-Speed HP N/A Y1,O Y1 Y1,W1 Y1,W1,W2 N/A N/A
with 3-Stage Heat N/A Y1,O Y1 Y1,W1 Y1,W2 Y1,W1,W2 N/A
2-Speed HP Y1,Y2,O Y1,O Y1 Y1,Y2 Y1,Y2,W1 Y1,Y2,W1,W2 N/A
with 3-Stage Heat Y1,Y2,O Y1,O Y1 Y1,Y2 Y1,Y2,W1 Y1,Y2,W2 Y1,Y2,W1,W2
1-Speed Dual Fuel N/A Y1,O Y1 W1 W1,W2 N/A N/A
2-Speed Dual Fuel Y1,Y2,O Y1,O Y1 Y1,Y2 W1 W1,W2 N/A
Fig. 14—Zone Perfect
Plus
Keypad Display A98134
TABLE 2—USER INTERFACE SETTINGS
TIME COOL HEAT
WAKE 6:00 AM 78 68
DAY 8:00 AM 85 60
EVE 5:00 PM 78 68
SLEEP 10:00 PM 82 60
—16—

11. Press NEXT PERIOD button to change from WAKE to the
DAY period. Repeat steps 6 through 11 for programming
the time and desired heating and cooling temperatures for
Monday, ZONE 1, in the DAY time period. Use NEXT
PERIOD button again to select EVE and SLEEP, and repeat
procedure.
12. After Monday ZONE 1 is completely programmed, you
may select NEXT DAY and advance to Tuesday. You can
now press COPY DAY button and copy the program
schedule from Monday into Tuesday. This can be repeated
as needed for each remaining day in the week. However, if
copying the previous day is not desired, you may individu-
ally program each day using the NEXT DAY button and
repeating steps 6 through 12. Press HOLD/END button to
exit programming mode.
You may also use the button pair marked NEXT ZONE (COPY
PERIOD and COPY DAY buttons simultaneously), to copy a full
week from 1 zone to the next. First use NEXT ZONE to select the
new zone and then press the COPY ZONE pair to copy the entire
week from the original zone into the new zone.
NOTE: Other ways to program comfort schedules with their
function keys can be found in the Owner’s Manual.
→HOLD, OFF, OUT, AND ALL ZONE
The following will provide detailed information regarding HOLD,
OFF, OUT, and ALL ZONE functions: (See Fig. 14.)
A. Hold Function
At the User Interface or Smart Sensor(s):
Pressing HOLD button activates and deactivates HOLD function
for a single zone.
When HOLD function is active, HOLD icon is displayed, and the
current set points will be used until the user cancels the HOLD
function. The HOLD function prevents the set points from
changing according to the program schedule. Cancelling the
HOLD function changes the set points to whatever is in the
program schedule for that period of the day.
B. OFF Function
At the User Interface:
Scrolling the heat set point past its lower limit (40°F), or the cool
set point past its upper limit (90°F) activates the OFF function for
a single zone. When a zone is set to OFF, the set points are
displayed as "OF" and the damper is closed. No conditioning will
be provided to that zone.
To cancel OFF, press UP button to change the heat set point, or
DOWN button to change the cool set point.
When a zone is set to OFF, the HOLD icon will turn on indicating
that OFF is a permanent override. The HOLD icon cannot be
turned off by pressing the HOLD button. However, if HOLD was
turned on prior to turning OFF that zone, then HOLD status will
remain after OFF is cancelled.
The ALL ZONE function cannot be activated from a zone that is
set to OFF.
All zones cannot be set to OFF. If end-user attempts to do this, the
User Interface software will prevent the last zone from going to
OFF.
At the Smart Sensor(s):
Same as above; scrolling the heat set point past its lower limit
(40°F), or the cool set point past its upper limit (90°F) activates the
OFF function for a single zone. When a zone is set to OFF, the set
points are displayed as "OF" and the damper is closed. No
conditioning will be provided to that zone.
C. OUT Function
At the User Interface:
Pressing OUT button activates and deactivates OUT function for a
single zone. When OUT function is active, OUT icon is displayed.
This function programs the zone as being unoccupied.
When OUT function is active, the zone has no set points. The zone
temperature will be kept within the 60-85°F range and if necessary,
the zone will be used as a "dump" zone to relieve LAT problems.
The set points are displayed as "--", and pressing UP and DOWN
buttons will have no effect.
To cancel OUT function, press OUT button and OUT icon will
turn off. Pressing OUT button is a temporary override that will be
cancelled at the next programmed schedule time or by a power
cycle, unless HOLD function is also active.
The OUT function is also a programmable option. You can
program the OUT function in the program schedules.
If a zone is set to OFF, the OUT button will have no effect. OFF
must be cancelled before OUT can become active.
At the Smart Sensor(s):
Same as the above; pressing OUT button will program the zone as
being unoccupied. Pressing OUT button again changes the zone to
occupied. When a zone is set to OUT, the desired temperature will
be displayed as "--" when UP and DOWN buttons are pushed.
D. ALL ZONE
At the User Interface:
Pressing ALL ZONE button activates and deactivates ALL ZONE
function. When the ALL ZONE function is active, ALL icon is
displayed.
This function allows the "entire house or business" to be controlled
to the set points and program schedule of a single zone.
The zone that is displayed when ALL ZONE button is pressed is
the controlling zone. Its set points will be displayed normally. If
the NEXT ZONE button is pressed while ALL ZONE is active, the
room temperature for each zone will be displayed, but the set
points for the non-controlling zones will be displayed as "--".
This function is not available if the zoning has been turned off
through software configuration.
This function is not available if the controlling zone is set to OFF.
At the Smart Sensor(s):
The ALL ZONE function cannot be changed from the Smart
Sensor, but if the function is active, and the Smart Sensor is in a
zone other than the controlling zone, the set point display will
show "--".
If the Smart Sensor is in the controlling zone, then it cannot be
scrolled to OFF.
→TROUBLESHOOTING
A. Error Messages
Several error messages are provided. They appear on the large
display and alternate with the normal room temperature data at a 2
sec rate. These are:
1. E1—COMMUNICATION FAILURE. An E1 will be dis-
played if the User Interface cannot communicate with the
Equipment Controller. Check and make sure V+, Vg, RS+,
and RS- are wired correctly between the User Interface and
Equipment Controller. This error message may sometimes
take up to 30 seconds before it is displayed. After the
problem has been fixed, cycle power to insure that all errors
have cleared.
2. E2—LAT or HPT SENSOR FAILURE. An E2 will be
displayed if the temperature sensor is open, or if it is
reading below -40°F or above 230°F. This error can be
temporarily overridden for troubleshooting purposes only
by turning on configuration option No. 6 in the User
Interface. This will ignore the LAT/HPT sensors while you
—17—

replace the sensors and/or investigate the problem. Dis-
abling this feature should only be temporary. Failure to
properly install the LAT/HPT sensors can cause permanent
damage to the HVAC equipment, as well as lose other
features that the zoning system can provide, e.g., OUT
zone, etc.
3. E3—OUTDOOR AIR TEMPERATURE SENSOR FAIL-
URE. An E3 will be displayed if the outdoor air temperature
sensor is open, or if it is reading below -40°F or above
180°F. This error will also occur if the following features
are active and the Equipment Controller cannot detect the
outdoor air temperature sensor:
Auxiliary Heat Lockout (System is configured as a heat
pump and Option No. 9 is active).
Dual Fuel Setup (DIP switch No. 8 off. System is config-
ured as a heat pump with dual fuel).
Cooling Lockout Below 55°F (DIP switch No. 7 off.
System is configured to disable cooling when outdoor
temperature is below 55°F).
Automatic Humidify Feature (User Interface is setup for
auto-humidify in heating mode).
4. E4—NONVOLATILE MEMORY FAILURE. An E4 will
be displayed if the configuration and program schedules
cannot be read. This is usually the result of a microproces-
sor failure. If cycling power does not reset this error, the
User Interface must be replaced.
5. E5—DEFROST LOCKED. An E5 will be displayed if the
defrost cycle is in process longer than 10 minutes. The
mode will automatically change to the EHEAT mode.
Cycling power will reset error, however, outdoor unit
should be checked to determine if defrost is operating
properly.
6. FF—DAMPER FUSE BLOWN. An FF will be displayed if
the fuse is open or missing. Remove plastic cover on
Equipment Controller to locate and replace fuse.
7. "--" (2 dashes)—TEMPERATURE SENSOR FAILURE.
Two dashes "--" will be displayed if a zone temperature
sensor has failed or is out of range. The User Interface and
Remote Room Sensors are considered failed if the tempera-
ture reading is outside the -40°F to 140°F range. A Smart
Sensor is considered failed if the temperature is outside the
32°F to 140°F range. See Table 4 to determine the
temperature/ohm relationship for a Remote Sensor. Do not
confuse dashes in the display ("--") for a zone that is set to
OUT or ALL ZONE.
OTHER HELPFUL HINTS
Read and understand "System Startup and Checkout" to review
Installer Test Setup Mode and check the equipment operation. This
is a good place to start in evaluating any problems associated with
the zoning system or the system equipment.
TEMPERATURE/OHM RELATIONSHIP
Table 3 shows a temperature/ohm relationship to help aid in
troubleshooting the Zone Perfect Plus System. This table will
evaluate the Remote Sensor, LAT, and HPT sensor operation. Use
a digital multimeter to perform the following:
To verify if a sensor is good, disconnect both leads from I/O board
and measure resistance through the sensor. Match ohm reading to
the table and compare temperature reading on table to ambient
temperature surrounding sensor (accuracy should be +/- 5 to 10
percent).
e.g. If 10.72k ohms are measured, this equals approximately 74°F.
To verify if I/O board is functioning normal, reattach sensor to I/O
board and set meter to 5vdc. Measure voltage across terminal
connections with sensor attached. A typical voltage of approxi-
mately 2.5vdc will indicate I/O board is functioning correctly.
→TABLE 4—WIRING DIAGRAM REFERENCE CHART
EQUIPMENT
SELECTION 1-SPEED
AC 2-SPEED
AC 1-SPEED
HP 2-SPEED
HP
1-Stage
Furnace Fig. 15 Fig. 16 Fig. 17 Fig. 18
2-Stage
Furnace Fig. 19 Fig. 20 Fig. 21 Fig. 22
Variable-Speed Non-
Condensing Furnace Fig. 23 Fig. 24 Fig. 25 Fig. 26
Variable-Speed Con-
densing Furnace Fig. 27 Fig. 28 Fig. 29 Fig. 30
Typical Fan Coil Fig. 31 Fig. 32 Fig. 33 Fig. 34
FK4C Fan Coil Fig. 35 Fig. 36 Fig. 37 Fig. 38
TABLE 3—TEMPERATURE/OHM RELATIONSHIP
TEMP F° OHMS
30 34,480
32 32,630
34 30,760
36 29,220
38 27,470
40 26,020
42 24,680
44 23,320
46 22,070
48 20,910
50 19,830
52 18,820
54 17,870
56 16,920
58 16,160
60 15,260
62 14,530
64 13,790
66 13,090
68 12,480
70 11,860
72 11,270
74 10,750
76 10,250
78 9,750
80 9,300
82 8,840
84 8,432
86 8,042
88 7,668
90 7,310
92 6,993
94 6,661
96 6,368
98 6,085
100 5,811
102 5,571
104 5,313
106 5,088
108 4,869
110 4,660
112 4,450
114 4,268
116 4,019
118 3,918
120 3,750
—18—

→Fig. 17—Single-Stage Furnace
with 1-Speed Heat Pump (Dual Fuel)
A98091
C
O
R
W2
C
R
Y
W
G
Y
SINGLE-STAGE
FURNACE
SINGLE-
SPEED HEAT
PUMP
EQUIPMENT
CONTROLLER
O
B
RH
RC
DEF
DHUM
HUM
W2
W1
G
Y2
Y1
N/A
HEAT STAGE 2
FAN
N/A
COOL/HEAT STAGE 1
N/A
RVS COOLING
DEFROST
N/A
HUMIDIFY
24 VAC HOT
See notes 1, 2, 3, 6, 10, and 11
HUMIDIFIER
(24 VAC)
→Fig. 15—1-Stage Furnace with
1-Speed Air Conditioner
A98089
CC
R
Y
W
G
Y
N/A
SINGLE-STAGE
FURNACE
SINGLE-
SPEED AIR
CONDITIONER
EQUIPMENT
CONTROLLER
N/A
24 VAC HOT
N/A
N/A
HUMIDIFY
O
B
RH
RC
W2
W1
G
Y2
Y1
DEF
DHUM
HUM HUMIDIFIER
(24 VAC)
N/A
HEAT STAGE 1
FAN
N/A
COOL STAGE 1
→Fig. 18—1-Stage Furnace with
2-Speed Heat Pump (Dual Fuel)
A98092
TWO-
SPEED HEAT
PUMP
C
O
R
W2
Y2
W3
C
R
Y1
W
G
Y
O
B
RH
SINGLE-STAGE
FURNACE
EQUIPMENT
CONTROLLER
RC
DEF
DHUM
HUM
W2
W1
G
Y2
Y1
N/A
N/A
N/A
HEAT STAGE 3
FAN
DEFROST
HUMIDIFY
RVS COOLING
24 VAC HOT
COOL/HEAT STAGE 2
COOL/HEAT STAGE 1
See notes 1, 2, 3, 4, 6, 7, 8, 9, 10, and 11
HUMIDIFIER
(24 VAC)
→Fig. 16—1-Stage Furnace with
2-Speed Air Conditioner
A98090
CC
R
Y1
Y2
W
G
Y
SINGLE-STAGE
FURNACE
TWO-
SPEED AIR
CONDITIONER
EQUIPMENT
CONTROLLER
O
B
RH
RC
W2
W1
G
Y2
Y1
N/A
HEAT STAGE 1
FAN
N/A
24 VAC HOT
N/A
COOL STAGE 2
COOL STAGE 1
See note 4
R
N/A
N/A
HUMIDIFY
DEF
DHUM
HUM HUMIDIFIER
(24 VAC)
—19—

→Fig. 21—2-Stage Furnace
with 1-Single Speed Heat Pump (Dual Fuel)
A98095
C
O
R
W2
C
R
G
Y
W/W1
W2
Y/Y2
O
B
RH
DEF
DHUM
HUM
RVS COOLING
TWO-
STAGE
FURNACE
SINGLE-
SPEED HEAT
PUMP
EQUIPMENT
CONTROLLER
N/A
24 VAC HOT
DEFROST
N/A
HUMIDIFY
RC
W2
W1
G
Y2
Y1
HEAT STAGE 3
HEAT STAGE 2
FAN
N/A
COOL/HEAT STAGE 1
HUMIDIFIER
(24 VAC)
See notes 1, 2, 3, 6, 10, 11, and 12
→Fig. 19—2-Stage Furnace
with 1-Speed Air Conditioner
A98093
CC
R
Y
W/W1
G
W2
Y/Y2
O
B
RH
N/A
TWO-STAGE
FURNACE
SINGLE-
SPEED AIR
CONDITIONER
EQUIPMENT
CONTROLLER
N/A
24 VAC HOT RC
W2
W1
G
Y2
Y1
HEAT STAGE 2
HEAT STAGE 1
FAN
N/A
COOL STAGE 1
See note 12
N/A
N/A
HUMIDIFY
DEF
DHUM
HUM HUMIDIFIER
(24 VAC)
→Fig. 22—2-Stage Furnace
with 2-Speed Heat Pump (Dual Fuel)
A98096
W/W1
W2
Y/Y2
TWO-
SPEED HEAT
PUMP
C
O
R
W2
Y2
W3
C
R
Y1
G
O
B
RH
RC
DEF
W2
W1
G
Y2
Y1
HEAT STAGE 4
HEAT STAGE 3
FAN
COOL/HEAT STAGE 2
COOL/HEAT STAGE 1
See notes 1, 2, 3, 4, 6, 7, 8, 9, 10, 11, and 12
TWO-STAGE
FURNACE
EQUIPMENT
CONTROLLER
RVS COOLING
DEFROST
HUMIDIFY
N/A
24 VAC HOT
DHUM
HUM
HUMIDIFIER
(24 VAC)
→Fig. 20—2-Stage Furnace
with 2-Speed Air Conditioner
A98094
CC
R
Y1
W/W1
G
W2
Y/Y2
O
B
RH
N/A
TWO-STAGE
FURNACE TWO-SPEED
AIR CONDITIONER
EQUIPMENT
CONTROLLER
N/A
24 VAC HOT RC
W2
W1
G
Y2
Y1
HEAT STAGE 2
HEAT STAGE 1
FAN
COOL STAGE 2
COOL STAGE 1
See notes 4 and 12
N/A
N/A
HUMIDIFY
DEF
DHUM
HUM HUMIDIFIER
(24 VAC)
R
Y2
—20—
Other manuals for ZONE PERFECT PLUS ZONEBB2KIT
1
This manual suits for next models
2
Table of contents
Other Bryant Control System manuals
Popular Control System manuals by other brands

Techtrol
Techtrol VLC Installation & operational manual

Key Digital
Key Digital KD-FIX418A-2 operating instructions

Franke
Franke DVS UC07-001 Installation & operating instructions

Phason
Phason PEC Plus quick start guide

Contrive
Contrive Quad400 manual

Crystal Vision
Crystal Vision Indigo CoCo 3G user manual