
12
Table 2 – 10K Temperature Sensor Resistance Table
°C °F OHM °C °F OHM °C °F OHM °C °F OHM
--- 5 5 --- 6 7 963,800 --- 9 16 52,410 37 99 6,015 83 181 1,141
--- 5 4 --- 6 5 895,300 --- 8 18 49,660 38 100 5,774 84 183 1,105
--- 5 3 --- 6 3 832,100 --- 7 19 47,070 39 102 5,545 85 185 1,071
--- 5 2 --- 6 2 776,800 --- 6 21 44,630 40 104 5,326 86 187 1,038
--- 5 1 --- 6 0 719,900 --- 5 23 42,330 41 106 5,116 87 189 1,006
--- 5 0 --- 5 8 670,200 --- 4 25 40,160 42 108 4,916 88 190 975
--- 4 9 --- 5 6 624,200 --- 3 27 38,120 43 109 4,725 89 192 945
--- 4 8 --- 5 4 581,600 --- 2 28 36,190 44 111 4,542 90 194 916
--- 4 7 --- 5 3 542,200 --- 1 30 34,370 45 113 4,368 91 196 889
--- 4 6 --- 5 1 505,800 032 32,650 46 115 4,201 92 198 862
--- 4 5 --- 4 9 472,000 134 31,030 47 117 4,041 93 199 836
--- 4 4 --- 4 7 440,700 236 29,500 48 118 3,888 94 201 811
--- 4 3 --- 4 5 411,600 337 28,050 49 120 3,742 95 203 787
--- 4 2 --- 4 4 384,700 439 26,690 50 122 3,602 96 205 764
--- 4 1 --- 4 2 359,700 541 24,400 51 124 3,468 97 207 741
--- 4 0 --- 4 0 336,500 643 24,170 52 126 3,339 98 208 720
--- 3 9 --- 3 8 314,900 745 23,020 53 127 3,216 99 210 699
--- 3 8 --- 3 6 294,900 846 21,920 54 129 3,099 100 212 679
--- 3 7 --- 3 5 276,200 948 20,890 55 131 2,986 101 214 659
--- 3 6 --- 3 3 258,800 10 50 19,900 56 133 2,878 102 216 640
--- 3 5 --- 3 1 242,700 11 52 18,970 57 135 2,774 103 217 622
--- 3 4 --- 2 9 227,600 12 54 18,090 58 136 2,674 104 219 604
--- 3 3 --- 2 7 213,600 13 55 17,260 59 138 2,579 105 221 587
--- 3 2 --- 2 6 200,500 14 57 16,470 60 140 2,488 106 223 571
--- 3 1 --- 2 4 188,300 15 59 15,710 61 142 2,400 107 225 555
--- 3 0 --- 2 2 177,000 16 61 15,000 62 144 2,316 108 226 539
--- 2 9 --- 2 0 166,400 17 63 14,330 63 145 2,235 109 228 525
--- 2 8 --- 1 8 156,400 18 64 13,380 64 147 2,157 110 230 510
--- 2 7 --- 1 7 147,200 19 66 13,070 65 149 2,083 111 232 496
--- 2 6 --- 1 5 138,500 20 68 12,490 66 151 2,011 112 234 483
--- 2 5 --- 1 3 130,400 21 70 11,940 67 153 1,942 113 235 470
--- 2 4 --- 1 1 122,800 22 72 11,420 68 154 1,876 114 237 457
--- 2 3 --- 9 115,800 23 73 10,920 69 156 1,813 115 239 445
--- 2 2 --- 8 109,100 24 75 10,450 70 158 1,752 116 241 433
--- 2 1 --- 6 102,900 25 77 10,000 71 160 1,693 117 243 422
--- 2 0 --- 4 97,080 26 79 9,573 72 162 1,637 118 244 411
--- 1 9 --- 2 91,620 27 81 9,166 73 163 1,583 119 246 400
--- 1 8 086,500 28 82 8,778 74 165 1,531 120 248 389
--- 1 7 181,700 29 84 8,409 75 167 1,480 121 250 379
--- 1 6 377,190 30 86 8,057 76 169 1,432 122 252 370
--- 1 5 572,960 31 88 7,722 77 171 1,386 123 253 360
--- 1 4 768,980 32 90 7,402 78 172 1,341 124 255 351
--- 1 3 965,250 33 91 7,098 79 174 1,298 125 257 342
--- 1 2 10 61,740 34 93 6,808 80 176 1,256 126 259 333
--- 1 1 12 58,440 35 95 6,531 81 178 1,216 127 261 325
--- 1 0 14 55,330 36 97 6,267 82 180 1,178 128 262 317
SHIGH PRESSURE SWITCH: The high pressure switch safety
is designed to shut down the compressor if it exceeds limits. Cut
in 420 +/-- 15 psig and cut out 600 +/-- psig.
SLOW PRESSURE SWITCH: The low pressure switch safety is
designed to shut down the compressor of loss of charge. Cut in 60
+/-- 15 psig and cut out 40 +/-- psig.
SINTELLIGENT RESET: If a fault condition is initiated, the 5
minute delay on break time period is initiated and the unit will
restart after these delays expire. During this period the fault LED
will indicate the cause of the fault. If the fault condition still exists
or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip
switch) before 60 minutes, the unit will go into a hard lockout and
requires a manual lockout reset.
A single condensate overflow fault will cause the unit to go into a
hard lockout immediately, and will require a manual lockout reset.
SLOCKOUT RESET: A hard lockout can be reset by turning the
unit thermostat off and then back on when the “RESET” dip
switch is set to “Y” or by shutting off unit power at the circuit
breaker when the “RESET” dip switch is set to “R”.
NOTES: The blower motor will remain active during a lockout
condition.
SECM TEST MODE: ECM test mode is to override the motor to
constant torque mode for motor troubleshooting. If the motor
runs in ECM test mode, the module and motor are good. To
engage in ECM test mode, only one switch can be selected. Select
TEST ON and all others OFF. Reset the board to NORM ON and
TEST OFF when test is complete.
If the unit remains in test mode for normal operation, the system
will not run different CFMs based on thermostat call such as Y1,
Y2 or dehumidify. It may also experience problems with
nuisance strip during electric heat operation.
There is no way to check CFM based on number of blinks if the
board is set to test mode.