BST Solutions Flamonitec IFC 11 User manual

Operating manual (US)
UV Compact Flame Detector
IFC 11

Content
1.1 General aspects
1.1 Introduction
1.2 Warning notes
1.3 Copyright protection
1.4 Disposal information
1.5 Warranty
1.6 Obligation of the operating company
1.7 Liability disclaimer
1.8 Address of the manufacturer
2 Safety
2.1 Intended use
2.2 Requirements on persons
2.3 Safety instructions
2.4 Safety devices
2.4.1 Fundamental aspects
2.4.2 Safety devices on the compact
industrial flame controller IFC 11
2.5 Safety instructions in case of maintenance
and troubleshooting
2.5.1 Fundamental aspects
2.5.2 Electrical / electronic devices
2.5.3 Inspection in accordance with the Ordinance on
Industrial Safety and Health
2.5.4 Safety test
3 Technical data
3.1 General characteristic features
3.2 Electrical system, optical system, mechanical system
3.3 Weight
3.4 Dimensions
3.5 Block diagram IFC 11
4 Transport, installation and connection
4.1 Scope of delivery
4.2 Packaging
4.3 Shipping instructions
4.4 Dimensions IFC 11
4.5 Installation
4.5.1 Alignment of IFC 11
4.5.2 Usage of glasses and lenses
4.5.3 Purge air connection
4.6 Connection
4.6.1 Electrical connection
4.6.2 Connection diagram IFC 11
4.7 Storage
4
4
4
5
5
5
6
7
8
9
9
9
10
10
10
10
11
11
12
12
12
12
13
13
13
14
14
14
15
15
15
15
16
16
17
17
17
18
18
18
18

Content
5 Description
5.1 Functional description IFC 11
5.2 Optionally function blocks for IFC 11
5.2.1 Relay module for flame detectors RMF 1
5.2.1 Diagnostic with UVT-Com
6 Operation of the compact flame detector IFC 11
6.1 Test of the compact flame detector
6.2 Operating indicator LED
7 Maintenance and servicing
7.1 Cleaning
7.2 Maintenance interval
7.3 Safety-related check
7.4 Behavior in case of malfunction
8 Troubleshooting
9 Order data
10 Accessories
19
19
19
19
19
20
20
20
21
21
21
21
21
22
22
23

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 4
GENERAL ASPECTS
1 | General aspects
1.1 Introduction
These operating instructions are a helpful guide for ensuring the successful and safe ope-
ration of the compact flame detektor IFC 11. They contain important information on how to
operate the system safely, correctly and efficiently. Observing the operating instructions will
help to prevent hazards, reduce costs of repair and downtimes and increase the reliability
and life of the device.
All illustrations and drawings in these operating instructions are shown for illustration pur-
poses and do not contain details for design.
The operating instructions always have to be accessible at the device. They have to be read
and applied by each person who is required to work with/on the device.
This work may involve, for example:
• operation
• troubleshooting during operation
• servicing
• maintenance (upkeep, inspection, repair) and/or
• transport
This should be confirmed by the operating company in writing.
1.2 Warning notes
The following warning notes are used in these operating instructions:
This warning level indicates an imminent hazardous situation.
If the hazardous situation is not prevented, this will result in death or severe injury.
Follow the instructions that accompany this warning to prevent the risk of death and severe
personal injury.
This warning level indicates a potentially hazardous situation.
If the hazardous situation is not prevented, this may result in death or severe injury.
Follow the instructions that accompany this warning to prevent the potential risk of death
and severe personal injury.
This warning level indicates a potentially hazardous situation. If the hazardous situation is not
prevented, this may result in slight or moderate injuries. Follow the instructions that accom-
pany this warning to prevent the injury of persons.
DANGER
!
WARNING
!
CAUTION
!

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 5
GENERAL ASPECTS
1.3 Copyright protection
These operating instructions have to be treated as confidential. They may only be used by
authorised staff. Access by third parties may only be granted upon written agreement of BST
Solutions.
All documents are protected in accordance with the German copyright law.
The disclosure and reproduction of documentation, in whole or in part, as well as the ex-
ploitation and communication of its content shall not be permitted unless expressly stated
otherwise. Offenders are liable for prosecution and the payment of damages.
We reserve all rights to exercise industrial property rights.
1.4 Disposal information
The flame detector is equipped with electrical and electronic components and
must be disposed separate from household waste. Follow the local and actual
regulations for waste disposal.
1.5 Warranty
Read these operating instructions carefully and in full before operating the compact flame
detektor IFC 11!
The manufacturer is not liable for damage or operating malfunctions that result from the
operating instructions not being observed.
The operating company has to supplement the operating instructions with operating inst-
ructions on the basis of national regulations on accident prevention and environmental pro-
tection, including information on supervision and notification requirements with respect to
special operating circumstances, e.g. regarding organisation of work, working processes and
staff deployed.
The recognised technical rules for safe and professional working also have to be observed in
addition to the operating instructions and the regulations on accident prevention applicable
to the country and place of use.
This warning level indicates potential damage to property. If this situation is not prevented,
it may result in damage to property. Follow the instructions that accompany this warning to
prevent damage to property.
A notice indicates additional information that will make the handling of the device easier.
NOTICE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 6
GENERAL ASPECTS
It is recommended that the operator of the device concludes a service contract with
BST Solutions. This guarantees that the device is regularly checked by our service staff
and ensures that any required wearing and spare parts are available without long deli-
very periods.
The UV tube is a wearing part whose service life depends on various factors that BST
Solutions cannot influence. Therefore, BST Solutions GmbH does not provide any war-
ranty on the service life of UV tubes.
This warranty does not apply to shipping damage, broken glass of the lens (photocell
/ UV tube) or any other damage caused by unskilled handling, improper or inadequate
maintenance setting.
NOTICE
NOTICE
NOTICE
1.6 Obligation of the operating company
The compact flame detektor may cause hazards if it is operated inappropriately or in an im-
proper condition.
The operating company is under the obligation to operate the machine in proper state only.
The operating company has to secure hazardous areas that exist between BST devices and
the customer‘s own equipment.
The operating company has to appoint and instruct responsible staff:
• Only deploy trained or instructed staff.
• Clearly set out the responsibilities of the staff with regard to operation, set-up, maintenance
and repair.
• Regularly check that staff are safety conscious and aware of hazards and are observing the
operating instructions.
The warranty shall become void, for example, in the event of:
• inappropriate use
• use of impermissible equipment
• incorrect connection
• prior works that are not part of the supplied product or service
• non-use of original spares and accessories
• conversion, if this has not been approved by BST Solutions
• non-performance of specified maintenance work

Page 7BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US)
GENERAL ASPECTS
• Before starting work, staff who are assigned to work with/on the device have to have read
and understood the operating instructions, in particular the chapter on „Safety“, as well as
the relevant regulations.
• The operating instructions and relevant regulations have to be stored in such a way that they
are accessible to operating and maintenance staff.
• Set out who will have responsibility for device operation and ensure that this person has the
authority to overrule any unsafe instructions of third parties.
1.7 Liability disclaimer
All technical information, data and guidance on device operation that are contained within
these operating instructions are, to the best of our knowledge, correct at the time of printing,
taking into account our present understanding and experience.
We reserve the right to make technical changes with respect to the further development of
the flame detector outlined in these operating instructions. No claims can be made based on
the specifications, illustrations and descriptions of these operating instructions.
We shall not be liable for damage or operating malfunctions that result from operating errors,
inappropriate repairs or the non-observance of the operating instructions. We expressly state
that only original spare parts and accessories approved by us may be used. This also applies
to the components of other manufacturers that have been used.
The installation or use of non-approved spare and accessory parts and any unauthorized re-
trofits and modifications are not permitted for safety reasons and exclude any liability by BST
Solutions for consequential damages.
BST Solutions is liable for possible errors or omissions with the exclusion of additional claims
entered into in the framework of the warranty obligations conceded to in the contract. Claims
for damages, on whatever legal basis they may be, shall be excluded.
Translations into foreign languages are carried out in good faith. We cannot accept any liability
for translation errors; this also applies where the translation has been carried out or has been
commissioned by us. The original text alone shall be binding.
Descriptions and illustrations do not necessarily depict the delivered product or a possible
spare parts order. Drawings and graphics are not to scale.
In addition to the operating manual, observe and instruct generally applicable legal and
other binding regulations for accident prevention and environmental protection.
NOTICE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 8
GENERAL ASPECTS
1.8 Address of the manufacturer
BST Solutions GmbH
Ruegenstr. 7 . 42579 Heiligenhaus . Germany
T +49 2056 98947-0 . E-Mail: info@flamonitec-bst.com
www.flamonitec-bst.com

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 9
2 | Safety
2.1 Intended use
The IFC 11 is a compact UV flame detector, which is specially designed for severe conditions
often experienced in industrial applications for single flame combustion. The IFC 11 can be
connected directly to the ionisation or LDR input of the control box. The UV sensor ensures
that the flame detector does not react to background radiation from hot refractory or from
any other infrared light source.
The IFC11 is a compact UV flame detector specially designed for use in industrial combustion
systems. The flame detector can be connected directly to a tuned ionisation or LDR input of
the burner control box. The IFC11 flame detector is designed in accordance with EN298 for
burner control boxes that do not check whether a flame signal is still present after a control
shutdown. The internal increase of the UV tube voltage immediately after the supply volta-
ge is applied ensures the safety requirement according to UL 372-2, CSA C22.2 and EN 298
for checking the UV tube for ignition for intermittent burner operation within the pre-purge
phase.
In case of a fault, the burner control recognises this condition as extraneous light.
With the Dioptric holder, which serves also as a connection interface of the flame detector to
the combustion chamber, the IFC 11 can be fitted with different glasses and lenses to special
requirements. The flame detector is equipped with an optical interface which visibly indicates
the flame signal intensity. A simple diagnosis of the flame intensity is directly on the furnace
or boiler possible.
The manufacturer/supplier shall not be liable for damage resulting from use for non-intended
purposes. The user/operating company alone shall bear the risk.
Danger when improperly used!
The device may cause hazards if it is not used as intended and/or for any other purposes.
The device has to be used only for the purposes for which it is intended.
The procedures described in the operating instructions have to be observed.
GENERAL ASPECTS
WARNING
!
The flame detector must be de-energised for at least 5 s between burner shutdown
and restart.
CAUTION
!

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 10
2.2 Requirements on persons
Do not allow any persons who are being apprenticed, educated, instructed or on a general
training programme to work on the device without the constant supervision of an experien-
ced person.
Persons who are under the influence of drugs, alcohol or medication that affects reactivity
shall not be permitted to carry out work on the device.
Connection, set-up, maintenance and repair work may only be carried out by qualified spe-
cialist staff.
This device may cause hazards if it is operated inappropriately by untrained staff or if it is not
used for its intended purpose.
Generally valid legal and other binding regulations on accident prevention and environmental
protection in addition to basic health and safety requirements have to be observed. The ope-
rating company has to instruct its staff accordingly.
2.3 Safety instructions
The following instructions on accident prevention have to be observed when operating the
compact flame detektor IFC 11.
NOTICE
SAFETY
Only operate the device if it is in a proper state!
• Do not remove or disable safety devices.
• Check for externally noticeable damage and defects prior to using the device! Immediately
notify the appropriate authority/person of any changes that occur (including changes in
operating performance). If necessary, stop and secure the device immediately.
• Allow only authorised specialist staff to carry out set-up and/or maintenance work.
• Replace worn or defective parts.
• Use suitable maintenance tools only.
• After repair work, refit all safety devices and carry out electrical and mechanical checks.
• Check the operating instructions for details of displays as well as switch-on and
switch-off procedures.
• Prior to switching on the device, make sure that no-one can be endangered by the
device!
• The operating instructions always have to be kept close to the device and be readily
at hand.
• Any non-compliance with the safety instructions outlined in these operating instruc-
tions may lead to damage to property, personal injury or even death.
Work on/with the device may only be performed by persons authorized to do so based
on their training and qualification. Furthermore, such persons have to have been com-
missioned by the operating company.
NOTICE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 11
2.4 Safety devices
2.4.1 Fundamental aspects
Check the safety equipment and locking devices on the device for safe operational condition.
Only operate the device if all safety devices are present and enabled. The operating company
or operator of the compact flame detektor IFC 11 is responsible for the proper operation of
the device.
2.4.2 Safety devices on the compact flame detektor IFC 11
The compact flame detektor IFC 11 has been fitted with the following safety devices:
• Housing (protection against accidental contact)
• Earth connection on housing
2.5 Safety instructions in case of maintenance and troubleshooting
2.5.1 Fundamental aspects
• Deadlines set or indicated in the operating instructions for repetitive checks / inspections
shall have to be observed!
• Appropriate workshop equipment is essential for performing maintenance work.
• In conformance with the electrical regulations, work on the electrical equipment of the sys-
tem may only be carried out by an electrical specialist or by trained staff under the direction
and supervision of an electrical specialist.
• The adjustment, maintenance and inspection activities and deadlines stipulated by BST
Solutions, including information on the replacement of parts / assemblies, have to be ob-
served! These tasks may only be carried out by authorised specialist staff.
• Operating staff have to be informed before maintenance or other special work is carried out.
A supervisor has to be appointed.
• Screw connections which have been loosened during maintenance and servicing work, have
to be tightened.
• If maintenance and repairs require safety devices to be dismantled, these devices have to
be remounted and checked as soon as the maintenance and repair work has been comple-
ted.
• Operating and auxiliary materials as well as exchanged parts have to be disposed of in a
safe and eco-friendly way.
• Spare parts supplied by BST Solutions or approved of by BST Solutions only may be used.
SAFETY
The device has been fitted with warning and danger signs for the protection of operating
staff. These signs have to be observed. Damaged or illegible signs have to be replaced
immediately.
NOTICE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 12
2.5.2 Electrical / electronic devices
Important rules of conduct
• Check the device in regular intervals. Any defects or faults ascertained have to be corrected
immediately. Switch off the device until the defects have been corrected.
• Equipment parts undergoing inspection, maintenance or repair work have to be made
deenergised, if required. First check that the disconnected parts are no longer live, then
short to earth. Also isolate neighbouring live parts
• If work is required on live parts, a second person has to be assigned who can disconnect
the power supply in case of an emergency. Only use insulated tools!
• Fuses must not be repaired or bridged. Only use original fuses with the specified current!
2.5.3 Inspection in accordance with the Ordinance on Industrial Safety and Health
In the event of the combination or installation of units from different manufacturers or sup-
pliers, a precise test must be done by the operator before commissioning in accordance with
the applicable industrial safety regulations and the applicable electrical engineering rules.
In case of queries, please get in touch with BST Solutions.
2.5.4 Safety test
Danger to life caused by electrical current!
Contact with live wires or components presents a danger to life!
Prior to any work on the electrical equipment, disconnect the flame amplifiering system
from the power supply network!
SAFETY
DANGER
!
In keeping with the electrical regulations, work on electrical / electronic parts / compo-
nents may only be carried out by electrical specialists.
To ensure proper operation, the UV flame detector must be tested several times in all
applications by starting the burner several times. IFC 11 must be tested several times by
starting and stopping the burner several times. and stopped several times. The flame re-
lay must switch off reliably in all cases if there is no flame.
This test should be carried out in different operating situations (see technical data sheet).
This is an indispensable prerequisite for safe and proper operation of the unit!
NOTICE
WARNING
!

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 13
TECHNICAL DATA
Optical features 185 to 265 nm, tolerated flame signal fades ap-
prox. 200 ms
Orientation axial
Lifetime of the tube approx. 10,000 h
Distance to flame < 80 in
Input 230 V AC
120 V AC (optional)
Nominal frequency 50-60 Hz
Prefuse max. 1 A , slow
Consumption max. 5.5 mA
Operating temperature 0 °F to 140 °F (temperatures higher than 125 °F
reduces life of the UV tube )
Operating position any position
Kind of protection IP 65
Protection class I
Humidity max. 95 % r. H., non-condensing
Restart time > 5s between controlled shutdown and renewed
heat request
Output data Flame on reaction time typically 0.5 s
Log off time < 0.5 s
Signal output Open collector output
max. switching current 15 mA
max. switching power 0.3 W
max. switching voltage 280 V AC / 400 V DC
3 | Technical data
3.1 General characteristic features
• UV-Tube
• Intermittent operation
• Spectral analyzing process
• MH47747
3.2 Electrical system, optical system, mechanical system

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 14
3.3 Weight
Weight approx. 1.15 lb
3.4 Dimensions
Length (without plug or gland) 4.0 in
Width 2.6 in
Height 3.6 in
Dimensions see under item 4.4
3.5 Block diagram IFC 11
TECHNICAL DATA
Applies for the maximum length of cable:
By an appropriate size depending on the length of cable is to ensure the compliance
with the data in the controller specified switching voltages / currents
NOTICE
Signal
Protected Earth
(5)
(7)
L1
N
(1)
(2) 12
4
5
3
6
1 UV-Sensor
2 Amplifier
3 Filter
4 Signal switch
5 Power supply
6 Time controlled
voltage increase

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 15
4 | Transport, installation and
connection
4.1 Scope of delivery
• Compact flame detektor IFC 11
• Operating instructions (optional, customer dependend)
• Connection cable (optional)
Refer to the order papers for the exact scope of delivery and compare with the delivery note.
Checking for completeness
Check the entire delivery for completeness against the accompanying delivery note. Please
refer to our terms of sale and delivery otherwise.
Report any damage
After arrival of the device and accessories, notify the shipping agent, the insurance company
and BST Solutions immediately in case of any damage caused by transport or inadequate
packaging.
Take steps to minimise and prevent further damage.
Report the insurance case to the insurance company without delay and transmit the full
claim documents at once in order to expedite the claims settlement (at the latest in suf-
ficient time before the expiry of any periods of preclusion and/or limitation relating to the
compensation claims against third parties).
4.2 Packaging
The compact flame detektor IFC 11 is shipped in different packaging materials.
The most frequently used packaging materials are cardboard and plastics (foils, foamed ma-
terial).
4.3 Shipping instructions
All installation and connection work may be carried out by qualified and approved
specialist staff only!
Observe the legal stipulations and adjustment instructions of the plant operator!
NOTICE
TRANSPORT, INSTALLATION AND CONNECTION
Packaging has to be disposed of in an environmentally friendly way and in accordance
with the relevant provisions on disposal.
NOTICE
Do not subject the appliance to heavy impacts during transport.
Do not subject the appliance to any humidity!
NOTICE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 16
4.4 Dimensions IFC 11
All dimensions in inch
4.5 Installation
The IFC 11 should be mounted close to the flame with straight alignment. The compact flame
detector should be mounted with the diopter. The diopter guaranties a quick mounting and
demounting of the compact flame controller. A diameter of 1‘‘ is recommended for viewing
tube that is cut down on the port side of the rear sight to ½‘‘. The sight pipe must be ade-
quately dimensioned.
The alignment is to concentrate on the primary zone of the flame (flame root). The distance
from the flame should be less than 80 in. Upon completion of the assembly work the screws
of the rear sight to the flame menwächters are to be tightened down. At high temperature
on the sight glass, which could heat the UV tube to about 140 °F, an air connection is to be
provided. To avoid interference, the direct view is to avoid a spark.
The maximum cable length of the cable is to be noted (see „Technical data). The connecting
cable is to run separately from the high-energy ignition and power lines over long distances
and not parallel to transfer it to.
All installation and connection work may be carried out by qualified and approved spe-
cialist staff only! The legal regulations as well as adjustment instructions of the plant
operator have to be observed!
NOTICE
TRANSPORT, INSTALLATION AND CONNECTION
For safety reasons, there must be at least one control shutdown per 24 hours. With the
IFC 11, to check the UV tube in accordance with UL 372-2, CSA C22.2 and EN 298, the bur-
ner control to be used must during the restart check the flame detector for the presence
of an extraneous light signal. Between the control shutdown and the restart, the UV flame
detector must be de-energised for at least 5 sec. between control shutdown and restart.
DANGER
!
2.6
4.7
4.0
2.9
3.6

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 17
4.5.1 Alignment of IFC 11
4.5.2 Usage of glasses and lenses
Depending on the distance and view angle to the flame, the diopter lens to be used when
needed. If pressure prevailing in the combustion chamber, a diopter with quartz glass is re-
commended.
4.5.3 Purge air connection
If the sensor temperature may rise due to high combustion chamber temperatures above 140 °F, a
purge air connection in order to limit the temperature sensor to provide a maximum of 140 °F is
essential. The dimensioning of the scavenging air is dependent on the parameters of the furna-
ce back pressure, and the pending purge air pressure and temperatures. Purge air connections
are available as the diameters ¼‘‘ and ½‘‘ optionally. The air connection is combined with the
adapter. Depending on the application again lenses and glasses are available. This eliminates
the normal adapter.
TRANSPORT, INSTALLATION AND CONNECTION

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 18
4.6 Connection
4.6.1 Electrical connection
For connection data, please refer to the chapter titled „Technical data“ as well as to the fol-
lowing terminal diagram.
Ensure that the available supply voltage complies with the voltage indicated on the type plate.
Prior to connection, check the device and the connecting cables for visible damage.
4.6.2 Connection diagram IFC 11
4.7 Storage
Do not unpack any packed compact flame detektor IFC 11 and accessories.
The following conditions apply to storage:
• Store in a dry place. Maximum relative humidity 95 %. Non condensing. In addition, it has
to be assured that the floor in the storage area will remain dry throughout the storage period.
• Protect from direct sunlight. Storage temperature:
40 °F to 100 °F.
• Store in a dustfree location.
• Avoid mechanical vibrations and damage.
Danger to life caused by electrical current!
The safety instructions and local safety regulations have to be observed during
connection!
DANGER
!
TRANSPORT, INSTALLATION AND CONNECTION
Occupancy male and female plug
PIN Internal
connection
AC/DC
Cable number
3 + PE
Connection for
ionization output / LDR
1 L 1 L
2 N 2 N
3 free - -
4 free -
53ION / LDR
6 free - -
PE PE
Green / yellow
PE

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 19
5 | Description
5.1 Functional description IFC 11
The IFC11 is a compact UV flame detector specially designed for use in industrial combustion
systems. The flame detector can be connected directly to a tuned ionisation or LDR input of the
burner control box. The IFC11 flame detector is designed in accordance with UL 372-2, CSA C22.2
and EN 298 for burner control boxes that do not check whether a flame signal is still present
after a control shutdown. The internal increase of the UV tube voltage immediately after the
supply voltage is applied ensures the safety requirement according to UL 372-2, CSA C22.2 and
EN 298 for checking the UV tube for ignition for intermittent burner operation within the pre-
purge phase. In case of a fault, the burner control recognises this condition as extraneous light.
The flame detector must be de-energised for at least 5 s between burner shutdown and restart.
With the Dioptric holder, which serves also as a connection interface of the flame detector to the
combustion chamber, the IFC 11 can be fitted with different glasses and lenses to special require-
ments. The flame detector is equipped with an optical interface which visibly indicates the flame
signal intensity. A simple diagnosis of the flame intensity is directly on the furnace boiler possible.
5.2 Optionally function blocks for IFC 11
5.2.1 Relay module for flame detectors RMF 1
The UV compact flame detector IFC 11 is a low power signal output equipped to simulate ioni-
zationtion or LDR signal. If a relay switch contact is required, the use of RMF 1 is recommen-
ded. The RMF 1 has an electrically isolated changeover contact with a maximum switching
voltage of 250 V AC, a maximum switching current of 1 A and a maximum rating of 250 VA.
More information can be found in BA RMF1 EN in its current version.
5.2.2 Diagnostic with UVT-Com
With the data interface UVT-Com, consisting of optical adapter with cable, USB-Interface and
software BST-Com, the following information can be read from the IFC 11:
• present pulses of the UV-tube
For this purpose, the USB-optoadapter UVT-Com must be inserted into the recess of the LED.
Via the connection cable and the interface, the data can be read into a laptop or PC using the
corresponding BST-Com software. Further information can be found in the BST-Com operating
instructions.
DESCRIPTION

BST Solutions GmbH | UV COMPACT FLAME DETECTOR IFC 11 (US) Page 20
6 | Operation of UV compact flame
detector
6.1 Test of the UV compact flame detector
To ensure the proper operation, the UV compact flame detector has to be testet several times
by starting and stopping the burner. As long as there is no flame in all cases the flame relays
has to be switched off solid. The test should be repeat for differnt operation situations (see
also datasheet). This is a essential condition for a safe and proper operation.
6.2 Operating indicator LED
Via the built-in LED the UV compact flame detector IFC11 is indicating the following operating
conditions:
LED Meaning
off IFC 11 is without connection or there is no detected
flame
Blinking Flame is detected
The blinking of the LED representes the flame signal
intensity
Increasing blinking = higher intensity
on The flame is detected with highest intensity
OPERATING OF THE FLAME DETECTOR IFC 11
This manual suits for next models
2
Table of contents
Other BST Solutions Security Sensor manuals
Popular Security Sensor manuals by other brands

Reer
Reer JANUS Installation, use and maintenance

STEINEL PROFESSIONAL
STEINEL PROFESSIONAL IS 2180-2 installation instructions

Guardall
Guardall GP15 installation manual

Smartwares
Smartwares RVS47LA manual

PCB Piezotronics
PCB Piezotronics 301A10 Installation and operating manual

SECOLink
SECOLink BK4 quick start guide