
2.3
Unusual behavior of a working system
Case 1: Current too low
If available please check the charge/discharge current limit from the inverter data. This value
is provided by the battery to the inverter. This value may vary depending on the
circumstances, such as SOC close to 0% or 100%, alarms or temperature below 12 degrees
(See User manual for details on derating).
If the real current is below the current limit set by the battery please check the remaining
components in the system
Case 2: Battery cannot charge/discharge
Please follow the recommendations for case 1 first. When to charge or discharge is decided
by the inverter with the data provided by the meter or CT clamp. Please check if those
components are communicating properly and no alarms are present. Alternatively check with
the inverter provider regarding the correct working modes and parameters for your
installation.
Case 3: Abnormal SOC or SOC jumps
There can be two causes for this issue.
Lack of calibration: LFP batteries have a very stable voltage curve and only show meaningful
changes of voltage when SOC is close to 0% or 100%. Therefore, it is important to let the
batteries charge completely with certain regularity. One time should be enough but if the
problem persists please perform several full cycles from close to 0% SOC until 100% SOC.
Small loads for a large period of time: Some devices in an energy storage system are
powered by the batteries. Most of these devices have a very low power consumption. There
is a limit to the current measurement precision of the batteries, any load below that will not
be measured so it will not have an influence in the SOC calculation. Therefore, if the system
is idle or under a very small load for a long period of time it is possible that the SOC shown
is not the real one. Once that occurs please perform a calibration cycle.