1. Introduction
2. Special warnings regarding the frequency
converter
3. Types
4. Operating conditions
5. Construction
5.1. Technical features
5.2. Pushbutton functions
5.3. Interface
5.3.1. System icons
5.3.2. Display area
5.3.3. Operating icons
5.4. Submersible pump applications or high
long cables
6. Installation
7. Electrical connection
7.1. Power supply line
7.2. Motor connection
7.3. Pressure transducer
7.4. Cascade mode
7.4.1. Cascade mode installation
7.4.2. Cascade mode electrical connection
7.4.3. Cascade connection with 2 variable speed
pumps
7.4.4. Cascade connection with 1 variable speed
pump and 1 fixed speed pump
7.4.5. Cascade mode programming
7.4.6. Cascade mode plant starting
7.5. Float switch connection
7.6. Remote alarm connection
8. Dry-running protection
9. Parameters
9.1. Parameters of pump status
9.2. Programming parameters
10. Programming
10.1. PASSWORD Insertion
11. Parameters to check when starting up the
unit.
11.1. Vessel pressure
12. Plant starting
12.1. Changing direction of rotation
13. Operation
13.1. Quick set point modification
14. Use of megaohmeter
15. Maintenance
16. Accessories
16.1. RA 100
16.2. Pipe housings Kit
16.3. Union kit
17. Disposal
18. igh length cables EASYMAT
applications
18.1. Reduction of the electromagnetic noise
emissions
18.2. Reduction of the electromagnetic
irradiated noises to the motor
19. Line filter EMC/RFI for EASYMAT
applications
20. Electrical connection scheme
21. Plant conversion scheme
22. Pump installation scheme
22.1. One pump installation scheme
22.2. Two pump installation scheme
23. Declaration of conformity
Frequency converter
EASYMAT 5MM
EASYMAT 9,2MM
EASYMAT 5MT
EASYMAT 7,5MT
EASYMAT 9,2MT
O ERATING INSTRUCTIONS
16
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 16

1. Introduction
We strongly suggest that the operator carefully
reads and follows the information contained in
this instruction manual for the frequency
converter.
Symbol used:
This symbol indicates high voltage
hazard. It draws attention to components
or procedures that could represent a
potential danger to the health and welfare
of the operator.
This symbol is used to draw the operator's
attention to situations of potential danger
for people or for operations that could
cause damage to the product.
2. Special warnings regarding
the frequency converter
We strongly suggest that the operator
carefully reads and follows the information
contained in this instruction manual for the
frequency converter.
The FREQUENCY CONVERTER should
NEVER be opened or tampered with
and guards that come with it should
never be removed.
The frequency converter must be
installed, adjusted and maintained by
qualified personnel who understand the
risks involved.
The frequency converter must be fitted
with voltage surge and overload
protection devices, in accordance with the
prevailing safety standards.
The connection of the alarms can
distribute power even when the frequency
converter is turned off. Ensure that there
is no residual voltage on the terminals of
the alarms.
All the power terminals and other
terminals must be inaccessible after
installation is completed.
The maximum output frequency must not
exceed the design frequency of the pump
being controlled. Operating at a frequency
higher than the allowable frequency can
cause higher current absorption and
damage to the device.
If it is necessary to remove the frequency
converter, remove only the covers
required in order to disconnect the
electrical cables. Take care not to damage
the electronic cards.
Failure to comply with the safety
regulations not only causes risk to
personal safety and damage to the
equipment, but also invalidates every right
to assistance under warranty.
Electro-magnetic compatibility.
The frequency converter is constructed in
compliance with European standard 2004/108CE.
Responsibility:
The manufacturer is not liable for malfunctioning if
the product has not correctly been installed,
damaged, modified, and/or run outside the
recommended work range or not in accordance
with other indications given in this manual.
The Manufacturer declines all responsibility for
possible errors in this instructions manual, if due to
misprint or error in copying.
The Manufacturer reserves the right to make any
modifications to products that it may consider
necessary or useful, without affecting the essential
characteristics.
The responsibility of the manufacturer is limited to
the product and excludes costs or greater damage
caused by incorrect installation.
3. Types
Type
Freqeuency converter
Standard power
(single-phase) max current output
V230 motor
A kW
Easymat 5MM 5 0,37 - 0,55
Easymat 9,2MM 9,2 0,75 - 1,1
Type
Freqeuency converter
Standard power
(three-phase) max current output
V230 motor
A kW
Easymat 5MT 5 0,75 - 1,1
Easymat 7,5MT 7,5 1,5 - 1,8
Easymat 9,2MT 9,2 2,2
17
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 17

4. Operating conditions
(Standard execution)
The electrical panel functions correctly under the
following power and installation characteristics:
- Power fluctuation: +/-10% max
- Frequency fluctuations: +/- 4 % max
- Ambient temperature: -10 °C a + 40 °C
- Relative humidity: from 20% to 90% without
condensation
- Vibration: max 5,9 m/s2(0,6 g) to 10-55 z
- Altitude: no higher than 1000 m, inside a closed
environment.
- Max liquid temperature:
• 50 °C EASYMAT 5MM, 9,2MM, 5MT, 9,2MT
• 40 °C EASYMAT 7,5MT
- Minimum delivery: 3 l/min
The current distributed by the frequency
converter must be equal to or lower than the
maximum current absorbed by the motor to
control.
5. Construction
(Standard execution)
The system is composed of:
- Frequency converter.
- Pressure transducer.
- Pipe housings.
- Fixing screws.
- Terminal board.
- Cable glands.
- Multi-hole gaskets.
5.1. Technical features
Power supply interface: 230V ± 10%
Protection: IP55
Display: LCD Display
Keyboard: 6 buttons
Digital inputs: - float switch for dry-running
protection
- tank fill float switch
- safety pressure switch
Analogue inputs: pressure transducer 4-20 mA
Digital outputs: general alarm, the display shows
the type of alarm (see paragraphs
7.6. and 9.3.)
Connectivity: RS485
Protections: - dry-running protection
- over-current
- over-heating
- under-voltage and over-voltage
- short-circuit protection on the
motor phase
5.2. Pushbuttons functions
Through this button you can start the pump
.
Through this button you can stop the pump
.
Through this button you have access to
frequency converter programming
parameters. If you already are on the
programming function, by pushing this
button you go up on the menù
.
Through this button you have access to
frequency converter programming
parameters. If you have changed a
parameters, by pushing this button you can
confirm the indicated value.
Through this button you can increase
parameters or to change the visualized
parameter.
Through this button you can decrease
parameters or to change the visualized
parameter.
5.3. Interface
The graphic interface of the display is divided in
three visualization areas: - system icons
- display area
- operating icons
P460
4.93.410
4.93.409.1
18
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 18

5.3.1. System icons
AUTO MODE
The system is operating in auto mode.
MANUAL MODE
The system is operating in manual mode.
SET-U MODE ACTIVATED
It shows that the set-up menu is activated.
When a icon is blinking you are modifying
a parameter. You can confirm with
enter.
ALARM
It indicates that there is a fault on the
system, the error number appears on the
display area. When you are on the set-up
mode the alarm icon will not appear
SENSOR STATE
It indicates that the system is connected
with the pressure transducer; if it is blinking
there is a fault on the pressure transducer.
UM STATE
It indicates if the pump is running or in
stand-by state.
CASCADE MODE
It indicates that the cascade control mode
is working. The 2 upper symbols show if
the pump is running or if the pump is in
stand-by. The lower symbol informs if the
pump is the master (lighted icon) or slave
(blinking icon).
5.3.2. Display area
It is composed from an incremental bar proportional
with the displayed value and its measure unit
The display is backlit, the light will be turn off after
20s of system inactivity.
5.3.3. Operating icons
Constant pressure mode
The system keeps the pressure constant
when the quantity of water requested by
the user changes.
Fixed speed mode
The system works at a fixed speed that
user can choose according to need.
5.4. Submersible pumps
applications or long cables
To operate a submerged pump (or surface
pump),where the distance from the inverter is
more than 10 m, see paragraph 18.
Submersible motor must operate with a
frequency between 30 z (minimum
operating frequency) and 50 z
(maximum frequency) for 50 z motors,
and between 30 and 60 z for 60 z
motors.
The running up time from 0 to 30 z and
the running down time from 30 z and 0,
must be as short as possible, according to
the motor power to operate.
6. Installation
For easy assembling and disassembling of the
frequency converter we recommend to respect the
minimum distances as show in figure herebelow.
In case of reduced distances connect the
frequency converter with the proper unions (see
paragraph 16.3.).
Do not install the control panel in places exposed
to direct sunlight or near sources of heat.
Fasten the heatsink (a) to the pipe by means of the
pipe housings (b1-b2) and the screws (c) in
equipment.
4.93.412.5
250
100
4.93.412
b2c b1 a
19
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 19

The pressure transducer (d) must be installed on the
system. We always advise the installation of a small
accumulator (e) (8 ltrs minimum) on the pump delivery
side.
7. Electrical connection
Electrical connection must be carried out
by a qualified electrician in accordance
with local regulations.
Follow all safety standards.
The unit must be properly earthed
(grounded).
Follow the instructions in the wiring
diagram attached.
Once the electrical connection has been
completed, remove any pieces of wire,
sheath, washers or any other foreign bodies
that may be found inside the frequency
converter.
For the electrical connections on both the
terminal board and the motor use cable with
a maximum section of 2,5mm2. We also
advise the use of insulated pin terminals.
Bad connections may damage the electronic
circuit.
7.1. Power supply line
Power supply line must comply with the provisions
under paragraph 4.
If a differential protection is necessary,
install a type A differential switch,
protected against untimely activation and
with threshold of intervention of 30 mA.
Electrical connection
7.2. Motor connection
The power supply line of the electrical motor must
be connected directly to the output terminal of the
inverter.
To comply with the standards of
electromagnetic compatibility, use a
shielded three-pole cable (for MM models)
or a shielded four-pole cable (for MT
models) with external protection sheath.
The power supply line of the motor must never run
parallel to the power line of the electrical panel.
Electrical connection
4.93.413.5
d
e
4.93.412.1
4.93.413.6
20
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 20

7.3. Pressure transducer
The pressure transducer is an analogical
instrument with an output signal of 4-20 mA that
continuously reads the pressure in a system.
Features:
Standards: EN 50081-1, EN 50082-2.
Voltage: 8-28 V
Pressure range: 0-6; 0-10; 0-16 bar
Output: 4-20 mA
Working temperature: da 0 a +50 °C
Protection: IP 65
ydraulic connection : G 1/4 male
Weigth: ~ 60 g
Electrical connection
Pressure
transducer
terminal box
supplied by us
7.4. Cascade mode
The EASYMAT frequency converters are
prearranged for use in pressure boosting sets with
up to 3 pumps in the following versions:
- Pressure boosting sets with 2 variable speed
pumps
- Pressure boosting sets with 3 variable speed
pumps
- Pressure boosting sets with 1 variable speed
pump and 1 fixed speed pump (single-phase)
7.4.1.
Cascade mode
installation
Connect the frequency converters on the delivery
pipes of the pumps, the installation must comply
with the provisions under paragraph 6.
Connect the pressure transducer to the delivery
manifold of the pressure boosting sets.
It is advised to install the pressure
transducers on the same point of the
delivery manifold and complete the
installation with a pressure gauge.
7.4.2.
Cascade mode
electrical
connection
Connect the supply cables to the motors and to the
power supply following the instructions under
paragraph 7. The power supply must comply the
provisions of the paragraph 4-5.
The connection with the power supply
must be made with interpositions of
magnetothermal bipolar switches (one for
each frequency converter).
For these frequency converters an earth leakage
circuit breaker or ground fault circuit interrupter,
type B.
This circuit breaker or interrupter must be marked
with the following symbols:
7.4.3. Cascade connection with
variable speed pumps
Electrical connection with 2 pumps
By means a proper cable make the connection of the
clamps number 4-5-6 of both frequency converters.
Electrical connection with 3 pumps
By means a proper cable make the connection of the
clamps number 4-5-6 of each frequency converters.
User must provide a jumper connection
into 1 frequency converter as shown in the
picture.
Check the correct connection sequence and
check that terminals of each cable are
connected on the clamp with same number.
To comply with the standards of
electromagnetic compatibility, for cable
length greater than 1 meter, it is
recommend the use of a shielded cable
with protection sheath connected on the
ground of both frequency converters.
7.4.4. Cascade connection with
1 variable speed pump
and 1 fixed speed pump
Connect the clamps 10-11 with a contactor with
max.250 Vac and 450 mA maximum resistive
current, connect to the contactor the power supply
-
+
4.93.413.1
221133
1
3
2
4
+
RS 485
0-
4.93.413.2
+
RS 485
0- +
RS 485
0- +
RS 485
0-
21
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 21

cable and the motor cable of the fixed speed pump.
The connection with the power supply must
be made with interpositions of
magnetothermal bipolar switches with
proper size and with a type A differential
switch protected against untimely activation
and with threshold of intervention of 30 mA.
The use of the cascade mode with 1 fixed
speed pump not allow connection of a
remote alarm or a control panel remote
alarm RA100.
7.4.5. Cascade mode programming
ressure boosting sets with 2 variable speed
pumps.
After the connection, change the AP09 parameter
from OFF to UU for both frequency converters,
define which frequency converter will work on
master mode and for this frequency converter
change the AP10 parameter from SLA (slave) to
MAS (master).
ressure boosting sets with 3 variable speed
pumps.
After the connection, change the AP09 parameter
from OFF to UU for both frequency converters,
define which frequency converter will work on
master mode and for this frequency converter
change the AP10 parameter from SLA(slave) to
MAS (master). Then parameter AP15 must be
changed for each “slave” frequency converter. The
first slave frequency converter must be set as
“SLA1”, and the second slave frequency converter
must be set as “SLA2”.
For the right behavior of the booster set it is
recommended to switch off and switch on all the
frequency converter.
This configuration define an address for each
frequency converter, if not correctly configured,
cascade mode will not work properly.
ressure boosting sets with 1 variable speed
pump and 1 fixed speed pump (single-phase).
After the connection, change the AP09 parameter
from OFF to UF for the frequency converter.
7.4.6. Cascade mode plant starting
Check that all the cascade mode parameters are
with the desired values, the parameters that can
change the cascade mode operation are:
AP16 Cascade mode start fall pressure set-up
AP17 Cascade mode restart delay
AP18 Cascade mode fall pressure limit set-up
To do the plant starting follow the instructions
under paragraph 12.
7.5.
Float switch connection
To connect a float-switch connect to the
connections 8-9 the cables of the float switch. The
float switch can be used for:
- dry-running protection
if, in cascade mode, the frequency
converter which is connected the float
switch is failure, the float switch cannot
shut off the pumps.
Electrical connection
7.6. emote alarm connection
To connect a remote alarm connect to the
connections 10-11 the possible remote alarm or
the control panel for remote alarm RA100.
The remote alarm can be used to signal:
- error on the frequency converter (see
paragraph 9.3.) (nO).
- the frequency converter is running (nC).
Operating limits: 250 Vac, 450 mA
maximum resistive current.
Electrical connection
4.93.413.3
+-
4.93.413.7
+
RA 100
-
4.93.413.4
22
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 22

23
8. Dry-running protection
The frequency converter is equipped with a dry-
running protection for the pumps. When the
pressure on the system remain for a time higher
than the dry-run time (AP05) lower than value of
the dry-run pressure (AP07) the protection system
stop the pump. It is possible the use of an external
float switch for the dry-running protection (see
paragraph 7.5.). In this case the pumps start with
a delay time (in seconds) defined by AP19 (Digital
input restart time), the time will be counted after
the change of the float switch state.
For entering the programming mode see
paragraph 10.
9. Parameters
On the frequency converter the following
informations are displayed:
- Parameters of pump status.
- Programming parameters.
- Alarms.
9.1. Parameters of pump status
They allow to visualize:
- the modulation frequency of the pump (basic
display).
- the pressure of the system.
- the line absorbed current.
Starting form the basic display by pushing of the
directional arrow (plus) or (minus) the
other parameters are displayed.
Example:
9.2. Programming parameters
To display the programming parameters, select
(menu).
Will be displayed progressively:
U - User settings: these are the basis settings
that user can change.
A - Advanced settings: these settings are
available only to qualified personnel. To enter
password is required (see paragraph 10.1.).
SA - Technical assistance settings: these are
the advanced parameters, only technical
assistance personnel are allowed to access
this menu. Password is required (see
paragraph 10.1.).
MAn - Fixed speed mode activation: this allows
activation of the fixed speed mode and the
working frequency. Only qualified
personnel are allowed to access this menu.
Password is required (see paragraph
10.1.).
AE - Advanced parameters: this allows for the
display of secondary parameters which can
be useful for system diagnostics.
AE01 Software release
AE02 Supply voltage (V)
AE03 Last 5 faults
Supply voltage visualization example.
By pushing the button (menu) the UP
parameter appears. Select the AE parameter by
pushing the (plus) up to arrive at the correct
parameter , confirm with (enter).
Select the parameter by pushing the
button (plus) and confirm with (enter).
Supply voltage is displayed.
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 23

9.2.1. UP – User settings
N° Description Standard Modifications Note
UP01 restart mode power failure rA
[rA = automatic; rM = manual]
UP02 Nominal pump current (A) 0,1
UP03 Nominal pump frequency ( z) 50
UP04 Direction of rotation ---
[ --- = std rotation; --- = inverted rotation]
UP05 Set point pressure (bar) 1,5
9.2.2. AP – Advanced settings
To enter password is required (see paragraph 10.1.)
N° Description Standard Modifications Note
AP01 Pressure transducer set-up (bar) 10
[sensor full-scale]
AP02 Ramp down (s) 3
AP03 Ramp-up (s) 2 MT
(fixed value for MM) 0 MM
AP04 Time before stop (s) 30
AP05 Dry-run time (s) 10
AP06 First dry-run time (s) 60
AP07 Dry-run pressure (bar) 1,5
AP08 System dynamic 3
[1 = fast dynamic; 5 = slow dynamic]
AP09 Cascade mode oFF
[oFF; UU = cascade mode with double inverter;
UF = cascade mode with an inverter]
AP10 Master/Slave setting SLA
MAS = master; SLA = slave
AP11 Reset to factory set-up
AP12 Digital input activation 1
[0 = oFF; 1 = no; 2 = nC]
AP13 Digital output activation 0
[0 = oFF; 1 = on; 2 = no; 3 = nC]
AP14 Restart fall pressure set-up (bar)
AP15 Pump address SLA1
AP16 Cascade mode start fall pressure set-up (bar) 0,3
AP17 Cascade mode restart delay (s) 10
AP18 Cascade mode fall pressure limit set-up (bar) 0,6
AP19 Digital input delay time (s) 30
[float switch delay time]
24
4.93.410
P460
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 24

9.2.3. SA – Technical assistance settings
To enter password is required (see paragraph 10.1.)
N° Description Standard Modifications Note
SA01
SA02
SA03 Pressure PID (Proportional gain) 2,8
SA04 Pressure PID (Integral time constant) 5,5
SA05 Pressure PID (Derivative time constant) 5,0
SA06 Min. run frequency ( z) 30
SA07 Max frequency ( z) 60
SA08 Set point pressure step up (bar) 0,3
SA09 Pressure step up time (s) 3
SA10 Pressure step up ramp (bar/s) 0,3
SA11 Set point control ramp (bar/s) 0,4
SA12 Carrier frequency 7010
SA13 Singlephase starting frequency ( z) 80
SA14 Singlephase starting voltage (V) 195
SA15 Nominal voltage (V) 220
9.2.4. MAn – Fixed speed mode activation
To enter password is required (see paragraph 10.1.)
N° Description Standard Modifications Note
MAn1 Fixed speed mode activation oFF
MAn2 Working frequency [MAn2 ≤ UP03] ( z) 45
a
9.3. Alarms
N° Displayed alarm Causes
Er01 Blockage due to no water The device is in failure due to no water.
The system try to restart automatically.
- One attempt every 10 minutes for 6 times.
- One attempt every hour for 24 times.
- One attempt every 24hours for 30 times.
Er02 Pressure transducer fault Not connected cable, broken connection, pressure
transducer spoiled.
Er03 Blockage due to low supply voltage Supply voltage lower than 190V.
- The system automatically restart when the clamp
voltage is higher than 190V.
Er04 Blockage due to high rectified voltage Supply voltage higher than 250V.
- The system automatically restart when the clamp
voltage is lower than 250V.
Er05 Blockage for memory failure
Er06 Blockage due to overcurrent in the electro
pump motor
Er07 Blockage due to overcurrent in the
frequency converter
Er08 Blockage due to direct short circuit between
the phases of output terminals
Er09 Blockage due to overheating
Er10
Blockage due to overheating of the power module
Er11 Blockage due to low voltage 24 V
Er12 Stop for float switch intervention The system will restart with a delay defined by AP19
from the state variation of the float switch. The control
panel for remote alarm not report this alarm.
Er13 Internal hardware error Contact the technical assistance
Er14 Cascade mode communication error Check the RS 485 connection or that both pumps
are enabled.
In case of multiple fault, scroll with the buttons (plus) or (minus) to visualize the fault sequence.
In case of thermal block it is advised to check the causes that have created the problem before
restart the pump operation. 25
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 25

10. Programming
To enter programming, select (menu). Use
the buttons (plus) or (minus) to move to the
programming parameter to be modified and select
(enter) to confirm. Use the buttons (plus)
or (minus) to move to the parameter to be
modified and select (enter) to confirm, with
the buttons (plus) or (minus) increase or
decrease the value. From this moment the set-up
icon start blinking until the value is confirmed
with (enter).
To exit the program, push (menu) until when
you arrive on the basic display.
When you go in the set-up mode appear the icon
.
Example of parameter variation.
In order to modify the set point pressure from 3.0
bars to a 2.8 bars:
select (menu) and then with the buttons
(plus) or (minus) until you move to
programming parameter UP. Confirm with
(enter) and then with the buttons (plus) or
(minus) move to the parameter UP05. Confirm
with (enter) and then with the buttons
(plus) or (minus) change the value up to the
desired value. From this moment the set-up icon
start blinking until the value is confirmed with
(enter).
To exit the program, push (menu) until you
arrive on the basic video, when you are out from
the set-up mode the icon disappear .
10.1. PASSWO D insertion
To enter on a menu with password, four numbers
appear on the display, the number to insert is
blinking. By pushing buttons (plus) or
(minus) you can change the blinking value. If you
confirm with (enter) the next number start
blinking.
If the password is correct you can enter on the
MENU, if the password is wrong the first number
restart blinking.
To exit the program, push (menu) until you
arrive on the basic display, when you are out from
the set-up mode the icon disappear .
password value
user 1959
Technical assistance contact the technical
assistance
11. Parameters to check when
starting up the unit
There are 4 programming parameters that need
to be checked when the unit is started up:
• arameter U 02 NOMINAL UM CURRENT
The nominal current of the pump must be set.
If the value input is inappropriate there is
the risk of pump damage or to have an
unexpected overcurrent alarm.
• arameter U 03 NOMINAL UM
FREQUENCY
The nominal frequency of the pump must be set.
If the value input is inappropriate there is
the risk of higher current absorption or
pump damage.
• arameter U 05 SET OINT RESSURE
The working pressure of the pump must be set.
If the value input is inappropriate for the needs
of the system, the value can be increased or
decreased using the (plus) or (minus)
keys.
If during the first start-up of the unit, filling
the system takes longer than 1 minute and
the unit signals a dry-running alarm,
Increase the parameter AP06, until the
pressure rises above the set value and the
pump remain on. (Make sure the pump
are primed).
11.1. Vessel pressure
Once the new working pressure is entered,
the tank pre-loaded pressure must be
changed to be 2/3 of the working pressure
(i.e. 4 bar working pressure,tanks to be
pre-loaded at 2.7 bar).
26
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 26

12. Plant starting
ATTENTION: never run the pump dry
not even for a short trial run. Start the
pump after filling completely with liquid.
After completing hydraulic and electrical
connection and checked the preloaded pressure
(for booster set with membrane tank), start the
plant as indicated below:
Prime the pumps (see the pumps instructions).
ump with suction lift:
- Fill the suction pipe and the pump body by
means of the plug hole located close to the
delivery port of the pump.
- Fill the suction tube by pouring water through
the plug hole on the suction manifold of the
pump.
ump with positive suction head:
- Open the gate-valve in the suction
pipeline.With sufficient head, the water will
overcome the resistance of the non-return
valve fitted in the suction side of the pump and
will fill the pump body. Otherwise, prime the
pump with the plug hole near the delivery port.
Never run the pump or more than ive
minutes with closed gate valve.
Starting pump
When the freqeuncy converter is switched on, the
pump are not operating and on the screen
appears OFF.
Press the button (play) to change the pump
status from STOP to run. The pump starts up with
the acceleration ramp set to reach the wished
pressure.
When the motor starts turning, check
the direction of rotation.
If the pump has been primed correctly, after a few
seconds the pressure will begin to increase on the
display.
If, after a few seconds‚ operation the pressure
remains at 0.0, stop the pump by selecting
(stop) as priming has not been carried out
correctly and the pump is idling. Re-prime the
pump and repeat the starting up procedure.
12.1. Inversion of the direction
of rotation
To change the direction of rotation of the motor,
push the button (menù) and then with the
button (plus) move up to the programming
parameter UP. Confirm with (enter) and with
the button (plus) move up to the parameter
UP04, confirm with enter (enter) and by
pushing of the button (plus) change the value,
confirm with (enter). To exit the program,
push (menù) until you arrive on the basic
display, when you are out from the set-up mode
the icon disappear .
13. Operations
The frequency converter is programmed to
manage the automatic operation of 1 or 2 pumps,
all at variable speed.
Depending on user consumption, the pumps start
to guarantee the amount of water necessary at
the set pressure.
When one pump has reached 50 z and water
requirements increase, the second pump will
begin operations.
The pumps are protected against:
- operation when dry, by means of a floating
switch and level sensor,
- over/under voltage (frequency converter),
- thermal overload (frequency converter).
13.1. Quick set point modification
If the frequency converter is operating in constant
pressure mode it is possible to change the set
point pressure without enter on the user
parameter (UP menu). Pushing the button
(enter) for more than 5 seconds you will enter
directly to the set point pressure (UP05
parameter).
By pushing of the buttons (plus) or
(minus) change the pressure value and confirm
with (enter).
By pushing of the button (menu) the system will
return to the basic display (see paragraph 9.1.).
27
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 27

14. Use of megaohmeter
Megging of an installation incorporating the
frequency converter is not allowed, because the
electronics may be damaged. If megging is
necessary, disconnect the frequency converter
and use the megaohmeter directly on the terminal
box of the pump.
15. Maintenance
Inspect the tank pre-loaded pressure
of the delivery vessel periodically.
16. Accessories
16.1. A 100
Control panel for remote alarm.
Dimensions: 110x150x70
Power supply: 220-230 V single-phase
Signals all pump assembly malfunctions detected:
- No water intake.
- Assembly malfunction.
- Converter failure.
5-Watt flashing red light plus 75 dB - 3600 z
acoustic alarm, for use in areas of loud noise,
positioned in such a way as to be visible from a
distance.
The control panel is fitted to an energized panel
led and an alarm reset pushbutton.
A 100
16.2. Pipe housings kit
Pipe housings for G1, G1 1/4 and G1 1/2 pipes.
For the G1 1/2 version of the EASYMAT it is
required change the screws assembled on the
heatsink with the screws provided with the G1 1/2
pipe housing kit.
16.3. Unions kit
Steel pipe with unions and pressure transducer
arrangement.
17. Disposal
Observe the local regulations and dispose of any
control gear accordingly. This product contains
electrical and electronic components and should be
disposed of accordingly.
28
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 28

29
Modifica parametro - Change parameter - Changement de paramètre
Cambio de parámetros - Parameterwert ändern - изменение параметра
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.49 Pagina 29

4.93.414.1
4.93.414.2
4.93.414.3
Max. ø 4,5 mm
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
90
20. Schemi collegamento elettrico
Electrical connection scheme
Schémas du branchement électrique
Esquemas de conexión eléctrica
Schemata der elektrischen Anschlüsse
Электрические схемы
макс ø 4,5 мм
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.50 Pagina 90

91
4.93.414.6
4.93.414.5
4.93.414.4
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.50 Pagina 91

92
4.93.414.5
4.93.414.5
4.93.414.5
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.50 Pagina 92

4.93.412.2
4.93.412.3
4.93.412.6
22. Schema installazione pompa
Pump installation scheme
Schéma de l’installation de la pompe
Esquema de instalación de la bomba
Installationsschema der Pumpe
Схемы установки насоса
22.1. Schemi installazione ad 1 pompa
One pump installation scheme
Schémas de l’installation à 1 pompe
Esquema de instalación a 1 bomba
Installationsschema mit 1 Pumpe
Схема установки с 1 насосом
21. Schema conversione impianto
Plant conversion scheme
Schéma de modification de l’installation
Esquema de conversión de la instalación
Konversionsschema der Anlage
Схема переоснастки системы
93
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.50 Pagina 93

22.2. Schemi installazione a 2 pompe
Two pump installation scheme
Schémas de l’installation à 2 pompes
Esquema de instalación a 2 bombas
Installationsschema mit 2 Pumpen
Схема установки с 2 насосами
4.93.412.4
94
istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444 29/08/14 15.50 Pagina 94
Other manuals for EASYMAT 5MM
2
This manual suits for next models
4
Table of contents
Popular DC Drive manuals by other brands

Delta
Delta VFD-EL-W Series user manual

Phase Technologies
Phase Technologies Essential Series Operation & installation manual

Delta
Delta VFD-E user manual

Oriental motor
Oriental motor BLH Series user manual

AutomationDirect
AutomationDirect IRONHORSE GSD4A Series user manual

M-Elec
M-Elec GD-5510-01 user manual