Canovate 6KS User manual

6-10KVA Rack-mount UPS User Manual Important Safety Instructions
INMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating instructions
before operating the uninterruptible power systems (UPS). Adhere to all warnings on the unit
and in this manual. Follow all operating and user instructions. This equipment can be operated
by individuals without previous training.
This product designed for commercial/industrial use only. It is intended for use with lift support
and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
rating label. The UPS is designed for data processing equipment. If uncertain, consult your
dealer or local representative.
This UPS is designed for use on a properly grounded (earthed), 220/230/240VAC, 50 or 60Hz
supply. The factory default setting is 220VAC/50Hz. Installation instructions and warning
notices are in this manual.
The ups 06-10KVA@220/230/240VAC is designed for use with a three-wire input (L,N,G).
WARNING
THE BATTERY CAN PRESENT A RISK OF ELECTRICAL SHOCK AND HIGH SHORT
CIRCUIT CURRENT. FOLLOWING PRECAUTIONS SHOULD BE OBSERVED BEFORE
REPLACING THE BATTERY.
zWear rubber gloves and boots.
zRemove rings, watches and other metal objects.
zUse tools with insulated handles.
zDo not lay tools or other metal objects on the batteries.
zIf the battery is damaged in any way or shows signs of leakage, contact your local
representative immediately.
zDo not dispose of batteries in a fire. The batteries may explode.
zHandle, transport and recycle batteries in accordance with local representative.
WARNING
ALTHOUGH THE UPS HAS BEEN DESIGNED AND MANUFACTURED TO ENSURE
PERSONAL SAFETY, IMPROPER USE CAN RESULT IN ELECTRICAL SHOCK OR FIRE. TO
ENSURE SAFETY, OBSERVE THE FOLLOWING PRECAUTIONS:

6-10KVA Rack-mount UPS User Manual Important Safety Instructions
zTurn off and unplug the ups before cleaning it.
zClean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
zNever block or insert any objects into the ventilation holes or other openings of the UPS.
zDo not place the ups power cord where it might be damaged.

6-10KVA Rack-mount UPS User Manual Contents
CONTENTS
1. ELECTROMAGNETIC COMPATIBILITY ............................................................ 1
2. INTRODUTION ................................................................................................... 2
3. SYSTEM DESCRIPTION.................................................................................... 6
3.1TransientVoltageSurgeSuppression(TVSS)andEMI/FRIFilters...............................................6
3.2Rectifier/PowerFactorCorrection(PFC)Circuit.........................................................................6
3.3Inverter......................................................................................................................................6
3.4BatteryCharger..........................................................................................................................7
3.5DC‐to‐DCConverter....................................................................................................................7
3.6Battery.......................................................................................................................................7
3.7DynamicBypass.........................................................................................................................7
4. PRODUCT SPECIFICATION And PERFORMANCE .......................................... 8
4.1ModelDescription......................................................................................................................8
4.2ProductSpecificationandPerformance.....................................................................................8
5. INSTALLATION ................................................................................................. 10
5.1UnpackingandInspection........................................................................................................10
5.2Rack‐mountInstallation...........................................................................................................10
5.2ConnectInput/OutputPowerCables.......................................................................................11
5.3OperatingprocedureforconnectingthelongbackuptimemodelUPSwiththeexternal
battery...........................................................................................................................................15
5.4Paralleloperation.....................................................................................................................16
6. CONTROLS And INDICATORS ........................................................................ 19
7. OPERATION ..................................................................................................... 22
7.1OperationMode.......................................................................................................................22
7.2ParallelOperation....................................................................................................................22
8. BATTERY MAINTENANCE............................................................................... 25

6-10KVA Rack-mount UPS User Manual Contents
9. NOTES FOR BATTERY DISPASAL AND REPLACEMENT PROCEDURES.... 26
9.1BatteryDisposal.......................................................................................................................26
9.2ExternalBatteryReplacementProcedures...............................................................................26
9.3InternalBatteryPackReplacementProcedures.......................................................................27
10. TROUBIE SHOOTING .................................................................................... 28
10.1CheckingUPSstatus...............................................................................................................28
10.2Adjustthefactorscausedtheproblem..................................................................................28
Annex A. Intelligent Slot ........................................................................................ 33
Annex B. EPO....................................................................................................... 34

6-10KVA Rack-mount UPS User Manual Electromagnetic Compatibility
1
1. ELECTROMAGNETIC COMPATIBILITY
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission.........IEC/EN 62040-2 Category C3
Radiated Emission............IEC/EN 62040-2 Category C3
*EMS
ESD..................................IEC/EN 61000-4-2 Level 4
RS....................................IEC/EN 61000-4-3 Level 3
EFT..................................IEC/EN 61000-4-4 Level 4
SURGE............................IEC/EN 61000-4-5 Level 4
Low Frequency Signals..............:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restrictions or additional measures may be needed to
prevent disturbances.
NOTICE:
This is a product for restricted sales distribution to informed partners. Installation restrictions or
additional measures may be needed to prevent radio interference.
Operated the UPS in an indoor enviroment only in an ambient temperature range of
0-40°C(32-104°F). Install it in a clean environment, free from moisture, flammable liquids,
gases and corrosive substance.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS on/off
push buttons do not electrically isolate internal parts. Under no circumstance attempt to gain
access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the panel indications are not in accordance with these
operating instructions or the UPS performance alters in use. Refer all fault to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the precautions. Keep unauthorized personnel away from the batteries. Proper
disposal of batteries is required. Refer to your local laws and regulations for disposal
requirement.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the
UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryer or any appliance
using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption. Turn off and
isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.

6-10KVA Rack-mount UPS User Manual Introduction
2
2. INTRODUTION
Congratulations on your choice of the uninterruptible power system(UPS), the series comes in
nominal power ratings of 6000VA,10000VA. It is designed to provide conditioned power to
microcomputers and other sensitive electronic equipment.
When it is generated, alternating current is clean and stable. However, during transmission and
distribution it may be subject to voltage sags, spikes and complete power failure that may
interrupt computer operations, cause data loss and even damage equipment. The series
protects equipment from these disturbances.
The series is a compact, rack-mount, on-line UPS. An on-line UPS continuously conditions and
regulates its output voltage, whether utility power is present or not. It supplies connected
equipment with clean sine wave power. Sensitive electronic equipment operates best from sine
wave power.
For ease of use, the series features a LCD display to indicate all information for UPS, and
provide kinds of function buttons.
The ups contains a removable power distribution box factory-attached that includes a manual
bypass switch allow AC power to continue to flow from the utility input to the load while the box
is removed from the UPS.
Fig 1. Front View of Long Backup Model

6-10KVA Rack-mount UPS User Manual Introduction
3
Fig 2. Front View of standard Model
Fig 3. Rear View of 6KVA Long Backup Model
Fig 4. Rear View of 10KVA Long Backup Model

6-10KVA Rack-mount UPS User Manual Introduction
4
Fig 5. Rear View of Standard Model
USB Port(option)
RS-232 communication port. DB9 type.
EPO Port
Intelligent slot port. SNMP card for network monitoring. Intelligent card or
non-pluggable dry contact card for user extending.
Input circuit breaker
Maintenance Bypass breaker
External battery connector
Parallel kit(option)
Entries for hardwired power input and output cables
intelligent slot for Dry contacts
C13 Output receptacles
C19 Output receptacles
Output circuit breakers

6-10KVA Rack-mount UPS User Manual Introduction
5
Fig 6. The Removable Power Distribution Box factory-attached of long backup model
Fig 7. The Removable Power Distribution Box factory-attached of standard model

6-10KVA Rack-mount UPS User Manual System Description
6
3. SYSTEM DESCRIPTION
3.1 Transient Voltage Surge Suppression (TVSS) and EMI/FRI Filters
These UPS components provide surge protection and filter both electromagnetic interference
(EMI) and radio frequency interference (RFI). They minimize any surge or interference present
in the utility line and keep the sensitive equipment protected.
3.2 Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power
to regulated DC power for use by the inverter while ensuring that the waveform of the input
current used by the UPS is near ideal. Extracting this sine wave input current achieves two
objects:
zThe utility power is used as efficiency as possible by the UPS.
zThe amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being
protected by the ups.
3.3 Inverter
In normal operation, the inverter utilize the DC output of the power factor correction circuit and
inverters it into precise, regulated sine wave AC power. Upon a utility power failure, the inverter
receives its required energy from the battery through the DC-to-DC converter. In both modes of
operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC
output power.

6-10KVA Rack-mount UPS User Manual System Description
7
3.4 Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to
continuously float charge the batteries. The batteries are being charged whenever the ups is
connected to utility power.
3.5 DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to
the optimum operating voltage for the inverter. The converter includes boost circuit which is
also used as PFC.
3.6 Battery
The ups L include value-regulated, non-spoilable, lead acid batteries outside. To maintain
battery design life, operate the UPS in an ambient temperature of 15-25°C.
3.7 Dynamic Bypass
The ups provide an alternate path for utility power to the connected load in the unlikely event of
a UPS malfunction. Should the UPS have an overload, over temperature or any other failure
condition, the ups automatically transfers the connected load to bypass. Bypass operation is
indicated by an audible alarm and illuminated amber Bypass LED. To manually transfer the
connected load from the inverter to bypass, press the ON/OFF button or Manual Bypass button
once.
NOTE:The bypass power path does NOT protect the connected equipment from disturbances
in the utility supply.

6-10KVA Rack-mount UPS User Manual Production Specification and Performance
8
4. PRODUCT SPECIFICATION And PERFORMANCE
4.1 Model Description
This manual is applicable to the following models:
4.2 Product Specification and Performance
1. General Specification
Model Long Standard Long Standard
Power Rating 6KVA/5.4KW 10KVA/9KW
Frequency (Hz) 50/60
Input Voltage (176-275)VAC
Current 34A max 57A max
Battery Voltage 192VDC
Current 37A max 60A max
Output Voltage 220V/230V/240V
Current 27/26/25A 45/43/42A
Dimension
(W*H*D) mm 438*130*680 438*218*680 438*130*680 438*218*680
Weight (kg) 18.5 62 21.5 70.5
2. Electrical Performance
Input
Model Voltage Frequency Power Factor
6KVA and 10KVA Single-phase 40-70Hz >0.99(Full load)
Model No. Type
6KS Standard model
10KS
6KL Long backup model
10KL
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance. Distortion Overload capacity Crest ratio

6-10KVA Rack-mount UPS User Manual Production Specification and Performance
9
3. Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C <95% <1000m 0°C-70°C
NOTE:If the UPS is installed or used in a place where the altitude is above than 1000m, the
output power must be derated in use, please refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67%
±1% 0.9 lag
±0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 10
minutes
130% load: transfers to
Bypass mode after 1 min.
150% load :transfers to
Bypass mode after 30
seconds and shutdown the
output after 1 minute
3:1
maximum

6-10KVA Rack-mount UPS User Manual Installation
10
5. INSTALLATION
The system should be installed and wired only by qualified electricians in accordance with
applicable safety regulations.
NOTE:UPS operation in sustained temperature outside the range of 15-25
°
C (59
°
-77
°
F)
reduces battery life.
5.1 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
●1 UPS
●1 user manual
●2 mounting ears with 8 black screws
●10 terminators for the long backup model
●2 connectors(red and white)for battery with 4 contracts for the long backup model
2) Inspect the appearance of the UPS to see if there is any damage during transportation.
Do not turn on the unit and notify the carrier and dealer immediately if there is any
damage or lacking of some parts.
5.2 Rack-mount Installation
When using the ups in a rack-mount configuration, the UPS must be supported by a slide kit,
fixed rails or a shelf. The adjustable rack-mounting brackets feature retaining latches to prevent
users from inadvertently sliding the UPS or battery cabinet out of the rack.
Step 1: Install the adjustable rack-mount kit or fixed rails in proper rack-mounting position with
the screws like this.
Step 2: Attach mounting ears to the side mounting holes of UPS using the screws provided and
the ears should face forward.

6-10KVA Rack-mount UPS User Manual Installation
11
Step3: Lift the UPS module and slide it into rack enclosure. Attach the UPS module to the rack
with screws, nuts and washers (user-provided) through its mounting ears and into the rack
rails.
NOTE:Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in
the lowest possible rack position.
5.2 Connect Input/Output Power Cables
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least

6-10KVA Rack-mount UPS User Manual Installation
12
0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until the UPS is fully
dried inside out before proceeding installation and use. Otherwise there are hazards
of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and the
following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. Open the battery breaker
for long backup time model (“L” model).
1) Pull out the Distribution Box .then open the terminal block cover located on the left side
of the Removable Power Distribution Box factory-attached; please refer to the
appearance diagram.
2) For 6KVA UPS, it is recommended to select the UL1015 10AWG(6mm2) wire or other
insulated wire which complies with AWG Standard for the UPS input and output
wirings.
3) For 10KVA UPS, it is recommended to select the UL1015 8AWG(10mm2) wire or other
insulated wire which complies with AWG Standard for the UPS input and output
wirings.
NOTE:Do not use the wall receptacle as the input power source for the UPS, as its rated
current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned
and destroyed. For the long backup time modes, make sure that the capacity of batteries is
larger than 24AH to avoid over charging.
4)Loosen the nuts from the thread plastic cable gland . Connect the input and output wires
to the corresponding input and output terminals through the nut and the thread plastic cable
gland according to the following diagram. Tighten the nuts onto the thread plastic cable gland
by hand.

6-10KVA Rack-mount UPS User Manual Installation
13
Fig 8. Input and Output Terminal Block Wiring Diagram of distribution box for standard model

6-10KVA Rack-mount UPS User Manual Installation
14
Fig 9. Input and Output Terminal Block Wiring Diagram of distribution box for standard model
NOTE:You must make sure that the input and output wires and the input and output terminals
are connected tightly.
5) The protective earth ground wire refers to the wire connection between the equipment
which consumes electric equipment and the ground wire. The wire diameter of protective earth
ground wire should be at least as above mentioned for each model and green wire or green
wire with yellow ribbon wire is used.
6)After having completed the installation, make sure the wiring connection is correct.
7) Please install the output breaker between the output terminal and the load, and the
breaker should with leakage current protective function if necessary.
8) To connect the load with the UPS, please turn off all the loads first, then perform the
connection and finally turn on the loads one by one.
9) No matter the UPS is connected to the utility power or not, the output of the UPS may
have electricity. The parts inside the unit may still have hazardous voltage after turning off the
UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility

6-10KVA Rack-mount UPS User Manual Installation
15
power supply.
10) Suggest charging the batteries for 8 hours before use. After connection, turn the input
breaker in the “ON” position, the UPS will charge the batteries automatically. You can also use
the UPS immediately without charging the batteries first, but the backup time may be less than
the standard value.
11) If it is necessary to connect the inductive load such as a monitor or a laser printer to the
UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up
power consumption is too big when it is started.
5.3 Operating procedure for connecting the long backup time model UPS with
the external battery
Fig 10. Battery terminal connection
1. The nominal DC voltage of external battery pack is 192VDC. Each battery pack
consists of 16 pieces of 12V maintenance free batteries in series. To achieve longer
backup time, it is possible to connect multi-battery packs, but the principle of “same
voltage, same type should be strictly followed.
2. The procedure of installing battery bank should be complied with strictly. Otherwise
you may encounter the hazardous of electric shock.
1) A DC breaker must be connected between the battery pack and the UPS. The
capacity of breaker must be not less than the data specified in the general
specification.
2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of
batteries in series.
3) You must connect the external battery cable to the battery first, if you connect
the cable to the UPS first, you may encounter the hazardous of electric shock.
The positive pole of the battery is connected to the UPS with red wire; the

6-10KVA Rack-mount UPS User Manual Installation
16
negative pole of the battery is connected to the UPS with black wire; the green
and yellow ribbon wire is connected to the ground of the battery cabinet.
3. To complete the connection of the external battery cable into the UPS. Do not
attempt to connect any loads to the UPS now. You should connect the input power
wire to the right position first. And then set the breaker of the battery pack in the “ON”
position. After that, set the input breaker in the “ON” position. The UPS begins to
charge the battery packs at the time.
5.4 Parallel operation
1. Brief introduction
As long as the UPS is equipped with parallel cables, up to 3 UPSs can be connected
in parallel to realize output power sharing and power redundancy.
2. Parallel installation
1) Users need to opt two standard 15-pin communication cables which length is
appropriate to be less than 3m.
2) Strictly follow the stand-alone wiring requirement to perform the input wiring of
each UPS.
3) Connect the output wires of each UPS to an output breaker panel.
4) Each UPS need an independent battery pack.
5) Please refer to the wiring diagram in the next page, and opt suitable breaker.
■The requirement of the output wiring is as follows:
●When the distance between the UPSs in parallel and the breaker panel is
less than 20 meters, the difference between the wires of input & output of the
UPSs is required to be less than 20%.
●When the distance between the UPSs in parallel and the breaker panel is
greater than 20 meters, the difference between the wires of input & output of
the UPSs is required to be less than 10%.
The wiring diagram are shown as follows:
This manual suits for next models
3
Table of contents
Popular UPS manuals by other brands

Tripp Lite
Tripp Lite AVR Series Specifications

Delta
Delta VX 600VA Installation & operation guide

Tripp Lite
Tripp Lite SmartPro SMART500RT1U owner's manual

Tripp Lite
Tripp Lite UPS System AVRX550U owner's manual

Tripp Lite
Tripp Lite SmartOnline SU1500RTXL2U owner's manual

Tripp Lite
Tripp Lite BCPERS450 Specification sheet