Carbolite 3508 P1 User manual

1 MC19-1.22
Operating Instructions
Temperature Controller
Type 3508
English
Ack
3508
1200
EUROTHERM
23
RUN/HOLD
RUN/HLD
OP1
°C
%
96.0
A/MAN

3508 Controller
2
MC19-1.22
Note: For the purposes of this manual the Eurotherm 3504 range is functionally identical to
the 3508 range.

3508 Controller
3
MC19-1.22
Contents
1.1 Using This Manual 4
1.2 PID Control 4
2Basic Operation 5
2.1 Controller Layout (Home display) 5
2.2 Keys 5
3Quick Start Guide 6
3.1 Operation as a simple controller 6
3.2 Changing the Setpoint 6
3.3 Resetting the programmer 6
3.4 Operating the current program 6
3.5 Understanding User Levels 6
4Setting up the controller 8
4.1 Maximum output power setting 8
4.2 Customer ID. 8
4.3 Units 8
4.4 Language 8
5Programming 9
5.1 Programming Notes 9
5.2 Holdback 9
5.3 Wait Segments 10
5.4 Program Cycling 10
5.5 Creating a Program 11
5.6 Running a Program 12
5.7 To pause (hold) a program 12
5.8 To stop and reset a program 12
5.9 To run a different program (P10 and P25) 12
5.10 Program Status 13
5.11 Power Failure Recovery 13
5.12 Alarms 14
5.13 Program Example 1 14
5.14 Program Example 2 16
6Options 17
6.1 Digital Communications –RS232 17
6.2 Digital Communications –RS485 17
6.3 Comms Address 17
6.4 Alarm Option 18
6.5 Remote Input and Output (Analogue Communications) 18
6.6 Program segment output 18
7Navigation Diagrams 19
7.1 Operator Level 1 - No Program Running 19
7.2 Operator Level 1 - Program Running 20
7.3 Supervisor Level 2 21
8Controller Fault 22
8.1 Fault Code Diagnostic Table 22
9Glossary of Terms 22

3508 Controller
4
MC19-1.22
Introduction to the Controller and Manual
1.1 Using This Manual
This manual aims to explain how to set up and operate the Eurotherm 3508 series of
controllers; it must be read in conjunction with the product main manual.
Due to the complex nature of furnace or oven control the use of technical terms throughout
this manual is unavoidable. Explanations of these terms can be found in the ‘Glossary of
Terms’ at the back of this manual.
This manual covers the operation of:
3508 P1 –Controller/Programmer
The 3508 P1 is a digital temperature controller which uses PID algorithms to give excellent
temperature control when properly set. This controller can store and run a single program of
up to 20 segments. The 3508P1 can also be used as a simple temperature controller.
3508P10 –Controller/Programmer
The 3508 P10 is a digital temperature controller which uses PID algorithms to give excellent
temperature control when properly set. This controller can store 10 programs of up to 50
segments each. Programs can be run individually or linked by a Call parameter as sub-
programs or to form single long programs. The 3508P10 can also be used as a simple
temperature controller.
3508P25 –Controller/Programmer
The 3508 P25 is a digital temperature controller which uses PID algorithms to give excellent
temperature control when properly set. This controller has a maximum of 500 segments or
25 programs; each program has a maximum of 50 segments. For example a 3508P25 could
store 10 programs with 50 segments or 25 programs with 20 segments. Programs can be
run individually or linked by a Call parameter as sub-programs or to form single long
programs. The 3508P25 can also be used as a simple temperature controller.
The 3508 does not contain a real-time calendar.
1.2 PID Control
The 3508 series of controllers use PID (Proportional Integral Derivative) temperature
control. This type of control uses a complex mathematical control system to adjust the
power being sent to the elements and hold the furnace or oven at the desired temperature.

Basic Operation
5 MC19-1.22
2 Basic Operation
2.1 Controller Layout (Home display)
2.2 Keys
A/Man
-
Disabled
RUN/HOLD
-
Runs, Holds or Resets the current program. Hold
down for 3 seconds to Reset.
Page key
Scrolls through the page headings. Hold down for 3
seconds to access further levels, pass codes are
required.
Scroll key
Scrolls through parameters listed on pages.
Arrow keys
&
Adjust parameter values
Page and
scroll
together
+
Press together to return to the home display or to
acknowledge an alarm
Page and up
arrow
together
+
Press together quickly to scroll back up the page
headings
Scroll and up
arrow
together
+
Press together quickly to scroll back up a parameter
list
Pressing any other combination of keys together has no effect
Note: If no keys are pressed for 1 minute, the display returns to Home.
Power output
indicator
Measurement units
Measured temperature
Program Setpoint temperature (PSP)
when a program is running
Power output
percentage
Program status
indicators.
Setpoint temperature (SP)
when basic controlling
Not used
Page
Scroll
Down
Up
Runs, Holds,
Resets the current
program
OP1
°C
23
1200
%
96.0
RUN HLD
EUROTHERM
A/MAN
RUN/HOLD
3508
Ack
ALM
Alarm indicator

Quick Start Guide
6 MC19-1.22
3 Quick Start Guide
3.1 Operation as a simple controller
When switched on the controller goes through a short test routine and then shows the
measured temperature. Below it is shown the setpoint temperature (SP) and percentage of
power output.
3.2 Changing the Setpoint
Press up down to select the required SP. If the SP is higher than the measured
temperature, the OP1 indicator will illuminate at the top of the display, indicating that the
controller is calling for power (giving an output).
The controller will immediately attempt to reach the set temperature and maintain it.
3.3 Resetting the programmer
To reset the programmer to simple controller mode, press RUN/HOLD for 2 seconds.
3.4 Operating the current program
To avoid unwanted heating at the end of a program, set the SP temperature to zero
before running a program.
Ensure the programmer is reset to simple controller mode before starting a program,
by pressing RUN/HOLD for 2 seconds.
To start the program, press RUN/HOLD twice, RUN will light up on the display.
The displayed Program Setpoint (PSP) follows ramps, dwells and steps as the program
runs. The SP temperature of the controller does not apply when a program is running.
To pause the program, press RUN/HOLD.
To stop the program and return to simple controlling (reset), press RUN/HOLD for 2
seconds.
When the program ends, the programmer will either:
Automatically reset to operation as a simple controller.
Dwell at the last temperature of the program (with the RUN indicator flashing), until
the operator presses RUN/HOLD for 2 seconds to manually reset, or presses
RUN/HOLD once to restart the program.
Turn power to the elements down to zero.
3.5 Understanding User Levels
There are two levels in the controller; Level 1(Operator) and Level 2 (Supervisor).
Level 1 (Operator) is for the day-to-day operation of the controller and parameters are not
protected by a security code. There are 3 pages at this level. Page 1, Customer Identity,
can only be altered in level 2. Page 2 shows the current program status. Page 3 is for
writing and viewing programs.
Level 2 (Supervisor) provides access to additional parameters and access to these is
protected by a security code. A further 4 pages are accessible in this level as follows;
Customer identity, Control Output Hi percentage, Units.
To Enter Level 2:
1. Press and hold page for 3 seconds. The display will show “Access Goto Level 1”

Quick Start Guide
7
MC19-1.22
2. Press up to select level 2. After a short pause the display will show “Access Pass
code”.
3. Press up or down to enter the pass code 9, Pass is momentarily displayed. After
a short pause the display will return to home, the controller is now in level 2.
When Level 2 operations have been completed the supervisor must return to Level 1
manually. It is not necessary to enter a code when going from a higher level to a lower level.
To Return to Level 1:
1. Press and hold page for 3 seconds. The display will show “Access Goto Level 2.
2. Press down to go to level 1. After a short pause the display will revert to home, the
controller is now in level 1.

Quick Start Guide
8 MC19-1.22
4 Setting up the controller
Before using the controller (or during its lifetime) certain parameters may have to be set,
depending on specific requirements. To do this the Controller must be set to supervisor
Level 2, see section 3.5.
4.1 Maximum output power setting
Press page until Control Output Hi is displayed. Press up or down to adjust the value.
Depending on the furnace or oven model, the maximum power output setting may be
accessible or locked.
For Silicon Carbide heated furnaces the parameter is accessible to allow compensation for
element ageing. Refer to the product manual for details.
In many models the maximum power output setting depends on the supply voltage, refer to
the product manual for details.
4.2 Customer ID.
A furnace or oven identity number can be entered if required. This may be used to identify
one of many units, for production or quality control systems.
Press page until Customer Identity is displayed. Press up or down to select a number.
4.3 Units
Press page until Units is displayed. Press up or down to select:
C Celsius
F Fahrenheit
K Kelvin
4.4 Language
The text on the 3508 can be shown in different languages, this can only be set at the factory
and therefore must be specified at the time of placing an order.

Programming
9 MC19-1.22
5 Programming
5.1 Programming Notes
Programs can be created in Level 1 or Level 2 of the 3508.
For the P10 and P25, new programs can be created while the current program is running.
To avoid unwanted heating at the end of a program, set the controller SP temperature to
zero before running a program.
All new unused programs show only 1 segment of type End.
The minimum number of segments for a program is 2. The second being an End type.
Ramp-to-setpoint control. To achieve this, create a two segment program. Set the first
segment type as Rate or Time. Set the second segment type End type Dwell.
For the P10 and P25, programs can be linked together using a “Call” segment. However a
lower number program can not be called and a program can not be ended with a call
segment.
A program can be ended in four ways:
1. With End segment set to S.OP the power to the elements is turned down to 0%, no
matter what the Setpoint temperature is.
2. With End segment set to Reset and the Setpoint temperature turned down to zero,
power to the elements will be 0%. To do this set the Setpoint temperature to the
minimum possible. For type B thermocouples this will be bellow zero.
3. With the End segment set to Reset. The controller will try to reach and maintain the
Setpoint temperature.
4. With the End segment set to Dwell. The controller will dwell at the PSP of the last
segment (RUN indicator flashes), until it is reset.
To reduce the number of segments in a program, change the last required segment to an
End type. You will be asked to press to cancel or for OK.
To cancel all segments in a program, change the first segment to an End type.
To alter parameters or segments of a running program, this program must be held or reset.
Press RUN/HOLD to pause the program, or press RUN/HOLD for 2 seconds to reset.
5.2 Holdback
Holdback can be used to prevent the program from running ahead of the actual heating or
cooling.
The Holdback value is the amount, in degrees, by which the Program Setpoint can run
ahead of the measured temperature before Holdback operates. The value applies to a
whole program.
To set the value press page twice, press scroll until Holdback Value appears and press
up or down to set.
Holdback can be used in Rate, Time and Step segments.

Programming
10
MC19-1.22
For Rate and Time segments Holdback will operate during the segment.
For a Step segment Holdback delays continuation to the next segment until the step
target is reached.
The Holdback Type can be set as follows:
Low Applies to heating only
High Applies to cooling only
Band Applies to both heating and cooling
Off Holdback is off
To set the Holdback type press page twice, then press scroll until the display shows
Holdback Type for each segment and press up or down to set.
The default setting for Holdback is Off.
5.3 Wait Segments
Wait prevents the program proceeding to the next segment, in a similar way to Holdback,
until the selected ‘Wait-For’ parameter has been met. There are 5 ‘Wait For’ parameters.
The first 4 only work if there are configured inputs to the controller.
1 PrgIn1 Wait until Input 1 is true
2 PrgIn2 Wait until Input 2 is true
3 PrgIn 1&2 Wait until Inputs 1 AND 2 are true
4 PrgIn 1or2 Wait until Inputs 1 OR 2 is true
5 PVWaitIP Wait until the measured temperature reaches a threshold value before
continuing. It can operate in one of 4 ways:
5.1 ‘Abs Hi’ Wait until the measured temperature is greater than or equal to a
value ‘WaitVal’ set for that segment.
5.2 ’Abs Lo’ Wait until the measured temperature is less than or equal to a value
‘WaitVal’ set for that segment.
5.3 ‘Dev Hi’ Wait until the measured temperature exceeds a fixed* threshold by
an amount ‘WaitVal’ set for that segment.
5.4 ‘Dev Lo’ Wait until the measured temperature drops below a fixed* threshold
by an amount ‘WaitVal’ set for that segment.
* The fixed threshold used by deviation parameters is set in the configuration level of the
programmer and if required should be requested when purchasing a furnace from Carbolite
Gero.
5.4 Program Cycling
The Cycles parameter sets the number of times the program will run.
The default setting is 1 cycle.
shows Prog Cycles, then press up to set a finite number of cycles up to 999. Or press
down to set cycling to continuous.

Programming
11
MC19-1.20
5.5 Creating a Program
From the home display, press page three times to get to the programming page, the
display will show “ProgEdit 1”.
Program number
On P10 or P25 models press up or down to select a new program number. The display
will show that new programs have only one segment.
Holdback Value
Press scroll until the display shows “Holdback Value”. If required: Press up or down to
set a value. This value will be used in any segment where a Holdback Type is set.
Ramp Units
These apply to Rate segments only. Press scroll until the display shows “Ramp Units”.
Press up or down to select the ramp units of degrees per Hour, Min or Sec.
Number of program cycles
Press scroll until the display shows “Cycles”. Press up or down to select more than
one cycle.
Now create all the segments for your program, finishing with an End segment. When
parameters for each segment have been entered the display goes to the next segment
number.
Segment Type
Press scroll until the display shows “Segment Type”. Press up or down to select Rate,
Time, Dwell, Step, Wait, GoBack, Call or End.
Holdback Type
Press scroll until the display shows “Holdback Type”. If required, press up or down to
select Off, Low, High or Band.
Target Setpoint (Visible only for Rate, Time and Step segments)
Press scroll until the display shows “Target SP”. Press up or down to set a value.
Ramp Rate (Visible only for Rate segments)
Press scroll until the display shows “Ramp Rate”. Press up or down to set the number
of degrees per Ramp Unit as set above.
Duration (Visible only for Time and Dwell segments)
Press scroll until the display shows “Duration”. Press up or down to set a value.
Wait For (Visible only for Wait segments)
Press scroll until the display shows “Wait For”. Press up or down to select:
PrgIn1, PrgIn2, PrgIn1In2, PrgIn1orIn2, PVWaitIP.
GoBack to segment number (visible only for GoBack segments)
Press scroll until the display shows “GoBack Seg”. Press down to select a segment
number to go back to.

Programming
12
MC19-1.22
GoBack Cycles (visible only for GoBack segments)
Press scroll until the display shows “GoBack Cycles”. Press up or down to set a
value.
Call Cycles (Visible only for call segments)
Press scroll until the display shows “Call Cycles”. Press up or down to set a value.
End Type (Visible only for End segments)
Press scroll until the display shows “End Type”. Press up or down to select Reset,
Dwell or SafeOp.
5.6 Running a Program
The current program can be started from the home display by pressing RUN/HOLD. Or by
pressing page once, then scroll once (twice for P10 and P25), then press up or down
5.7 To pause (hold) a program
Press RUN/HOLD
or
Press page until Program Status Reset appears
Press scroll until the cursor moves to Reset
Press up or down to select Hold
RUN/HLD will be displayed
5.8 To stop and reset a program
Press and hold RUN/HOLD
or
Press page until Program Status Reset appears
Press scroll until the cursor moves to Reset
Press up or down to select Reset
5.9 To run a different program (P10 and P25)
To select a program
Press page until Program Status Reset appears
Press scroll then up or down to select a program number
To run the program
Press RUN/HOLD
or
Press scroll until the cursor moves to Reset
Press up or down to select Run
Run will be displayed

Programming
13
MC19-1.20
5.10 Program Status
While a program is running the home display shows 3 values:
Top: Measured temperature
Centre: Program setpoint (PSP)
Bottom: Power output percentage
To see more detail:
Press page once to go to the program status page. The top and centre values from the
home page remain on the display. The lower half of the screen now shows:
Current program number (P10 and P25 only)
Current segment number
Time remaining for that segment
Further presses of the scroll key while a program is running will reveal additional
information:
Status. This can be changed to Hold, Reset or Run by pressing up or down .
Program setpoint (PSP)
Current Segment Type. Step and Call segments are instant, so are only flashed on the
screen, unless Holdback is operating on that segment.
Target Setpoint
Segment Rate For Rate, Time and Step segments only
Cycles left
Program Time Left
Program hold with holdback
If a holdback value has been set (see “Programming”) and the program goes into a hold
state, the green HLD indicator will flash, until the measured temperature catches up.
If while in this condition the program itself is put into hold by pressing the RUN/HLD button,
the “HLD” indicator will stop flashing and remain on with the “RUN” indicator. When the
program is started again by pressing the “RUN/HLD” button, the “HLD” indicator will flash
again if the measured temperature has not caught up with the program.
Programming note:
For P10 and P25 models you can create or change other programs while the current
program is running, go to operator Page 3.
5.11 Power Failure Recovery
If there is a power interruption to the controller during a program, when power is restored
the controller pauses the program, then ramps the temperature back up to the current
Program Setpoint (PSP) before continuing the program.
Power fail during ramp segments: The ramp rate will be that of the current ramp
segment.
Power fail during Dwell segments: The ramp rate will be that of the previous ramp
segment. If a previous ramp segment does not exist, then the dwell will continue at
the current measured temperature.

Programming
14
MC19-1.22
Power fail during Time-to-target segments: The ramp rate will be that of the current
segment. The ramp rate is maintained, but the time remaining is recalculated.
If there is a power interruption while controlling to Setpoint, when power is restored the
controller automatically calls for maximum power.
5.12 Alarms
Alarms are used to alert the operator when a pre-set level has been exceeded or a function
error has occurred such as a sensor break. They are indicated by a flashing red ALM
(Alarm) indicator. The alarm may also switch an output –usually a relay to allow external
devices to operate when an alarm occurs. Alarms only operate if they have been configured
and are dependent on customer requirements.
How to acknowledge an alarm will depend on the type of latching which has been
configured. A non-latched alarm will reset itself when the alarm condition is removed. A
latched alarm requires acknowledgement with the “ACK” function (section 2.1) before it is
reset.
If an alarm has been activated the red “ALM” indicator will flash and the text will indicate the
type of alarm.
To acknowledge an alarm and cancel the “ALM” indicator, press and together.
5.13 Program Example 1
The following sequence of entries creates and runs the program shown graphically below.
1. Turn the controller SP down to ‘0’ by pressing down .
2. Press page until Prog, Segments Used is displayed. On P10 or P25 models press
up or down to select a new program number, (a program with only 1 segment).
3. Press scroll until Holdback Value is displayed. Default ‘0’ degrees.
4. Press scroll until Ramp Units is displayed. Press up or down to set to ‘Min’
5. Press scroll until Cycles is displayed. Default ‘1’
6. Press scroll until Segment 1 is displayed
7. Press scroll until Segment Type is displayed. Press up or down to select ‘Rate’
8. Press scroll until Holdback Type is displayed. Default ‘Off’
9. Press scroll until Target SP is displayed. Press up or down to set to ‘400’
degrees.
10. Press scroll until Ramp Rate is displayed. Press up or down to set to ‘5.0’
degrees per minute.
Repeat steps 6 to 10 for 4 more segments. Set Holdback to the default ‘Off’. Enter the
following parameters and values:
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Step Target SP ‘600’ degrees
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Time Target SP ‘200’ degrees, Duration ‘2:00:0’ hours

Programming
15
MC19-1.20
Finish the program with an End segment:
11. Press scroll until Segment Type is displayed. Press up or down to select ‘End’
12. Press scroll until End Type is displayed. Press up or down to select ‘Reset’
13. Press page and scroll together to return to the home display.
To run the program either press RUN/HOLD or:
14. Press page until Program Status is displayed
15. Press scroll until the cursor moves to the program status of ‘Reset’
16. Press to select ‘Run’.
Segment 1
Type ‘Rate’
Target 400°
Rate 5.0°/Min
Segment 2
Type ‘Dwell’
Duration
30min
Segment 3
Type ‘Step’
Target 600°
Segment 4
Type ‘Dwell’
Duration
30min
Segment 5
Type ‘Time’
Target 200°
Time 2 hours
Segment 6
Type ‘End’
End type
‘Reset’
400°C
600°C
200°C
5°C/m
30min
30min
2 hours
Time display examples
10:05.3 Min / Sec / 10th Sec
24:10:05 Hour / Min / Sec
196:10 Hour / Min

Programming
16
MC19-1.22
5.14 Program Example 2
The following sequence of entries creates and runs the program shown graphically below.
1. Turn the Setpoint to ‘0’ by Pressing down
2. Press page until Prog, Segments Used is displayed. On P10 and P25 models press up
or downto select a new program number, (a program with only 1 segment).
3. Press scroll until Holdback Value is displayed. Press up or downto set to ‘5’
degrees
4. Press scroll until Ramp Units is displayed. Press up or downto set to ‘Min’
5. Press scroll until Cycles is displayed. Default ‘1’
6. Press scroll until Segment 1 is displayed
7. Press scroll until Segment Type is displayed. Press up or downto select ‘Time’
8. Press scroll until Holdback Type is displayed. Default ‘Off’
9. Press scroll until Target SP is displayed. Press up or downto set to ‘600’ degrees
10. Press scroll until Duration is displayed. Press up or downto set to ’30:00.0’
minutes
Repeat steps 6 to 10 for 4 more segments. Enter the following parameters and values: Note:
Call segments are not available on single program models.
Segment Type Rate Target SP ‘400’ degrees. Ramp Rate ‘2.0’ degrees per minute
Segment Type Step Target SP ‘200’ degrees
Segment Type Dwell Holdback ‘High’. Duration ’30:00.0’ minutes
Segment Type Call Call Prog ‘next number’. Call Cycles ‘2’
Finish the program with an End segment:
11. Press scroll until Segment Type is displayed. Press up or downto select ‘End’
12. Press scroll until End Type is displayed. Press up or downto select ‘Dwell’
Repeat the sequence to create a short program ‘3’ as suggested in the diagram.
13. Press page and scroll together to return to the home display
To run the program either press RUN/HOLD or
14. Press page until Program Status is displayed
15. Press scroll until the cursor moves to the program status of ‘Reset’
16. Press to select ‘Run’
Segment 1
Type ‘Time’
‘Target’ 600°
‘Duration’
30min
Segment 2
Type ‘Rate’
‘Target’ 400°
‘Rate’ 2°C/m
Segment 3
Type ‘Step’
‘Target’ 200°
Segment 5
Type ‘Call’
Call prog 3
Call cycles 2
Segment 6
Type ‘End’
End type
‘Dwell’
400°C
600°C
200°C
2°C/m
30min
Segment 4
Type ‘Dwell’
‘Duration’
30min
‘H’back type’
‘High’
200°C
Program 3
Example
30min
Seg 4 ‘Holdback
Value’ 5°C
200°C
400°C
P10 and
P25 only

Options
17 MC19-1.22
6 Options
Because options can be ordered in a variety of combinations and for a variety of purposes,
exact instructions are not given here. The full Eurotherm manual may be required to
determine customer parameter settings. To reveal or hide parameters in the controllers it is
necessary to go into configuration modes, a security code is needed. Please consult
Carbolite Gero.
6.1 Digital Communications –RS232
If the RS232 option is supplied, then the furnace or oven is fitted with one subminiature D-
socket connected to the controller communications (comms) module. RS232 is suitable for
direct connection to a personal computer (PC), using a “straight through” cable as follows
(the linked pins at the computer end are recommended but may not be necessary). The
cable is usually 9-pin at the furnace or oven end and 9-pin at the computer, but other
alternatives are shown in parentheses.
Furnace end of cable
RS232 Cable: furnace to PC
Computer end of cable
female 9-pin (25-pin)
9-pin (25-pin) male
Rx
3 (2)
3 (2)
Tx
Tx
2 (3)
2 (3)
Rx
Com
5 (7)
5 (7)
Com
7,8 (4,5)
Link
together
1,4,6 (6,8,20)
Link
together
6.2 Digital Communications –RS485
If an RS485 option is supplied, then the furnace is fitted with two D-sockets. Connection
between products is by “straight” cable as follows:
RS485 cable: furnace to
furnace
female 9-pin (25-
pin)
9-pin (25-pin) female
3 (2)
3 (2)
+
2 (3)
2 (3)
+
Co
m
5 (7)
5 (7)
Com
If a boxed KD485 RS485 to RS232 converter is supplied, then the connection cable from
furnace to KD485 should be a “straight” cable, the same as the furnace-to-furnace cable.
The connection between the KD485 and the PC should be a “crossover” cable, the same as
the Furnace to PC cable in section 6.1.
6.3 Comms Address
Typically the comms address is set to 1, but this can be changed. In the case of RS485 and
multiple instruments it is necessary to set different addresses.

Programming
18
MC19-1.22
To change the address value access the level 2 list. In level 2 press the page key until the
COMMS parameter is displayed. Press up
6.4 Alarm Option
When an alarm board is fitted with free contacts for customer use, the contacts are taken to
a panel plug on the control panel, wired as indicated:
The purpose of the 2 amp fuse is to protect the internal circuitry from excess electrical
current.
The instrument configuration, and parameters available to the operator, depend on the
customer requirements.
6.5 Remote Input and Output (Analogue Communications)
When analogue communications are fitted, the contacts are taken to “banana plug” sockets
on the control panel.
Controller configuration depends on customer requirements.
Remote input (when specified) may be switched on and off using the Remote setpoint
enable parameter in the controller level 2, if this was made available for a particular
application. In level 2 press page until ‘REM SP Enable’ is displayed, press up or down
to select SP1 (the normal controller setpoint) or SP2 (the remote input setpoint), ‘SPX’ will
appear in the top left corner of the display.
Remote output does not require switching on and off.
6.6 Program segment output
When the customer requirement is for program segment output, an extra parameter is
revealed in the PROG list. For each program segment, after the segment type and settings,
the parameter EVENT OUTS appears. This has values on and off. If the value is set to
on, then the relay closes during the segment and a small 1 appears in the top left of the
screen.
If more than one program segment output is fitted, then there are extra boxes depending on
how many event outputs there are.
Controller
2A fuse
supply
load
n/o contacts
controller

Navigation
19 MC19-1.22
7 Navigation Diagrams
7.1 Operator Level 1 - No Program Running
Current
program
page
Programming
Page
Home
display
ProgStat
Program
number
ProgEdit
Segments
used
Program
Status
Holdback
value
Program
Setpoint
Ramp units
Prog
cycles
Prog
segment
Segment
type
Rate
Time
Dwell
Step
Call
End
Segment
target
Segment
target
Duration
Segment
target
Call
Program
End
Type
Ramp rate
Duration
Call
Cycles
Visible parameters depend on Segment Type
Customer
Identity
Controller
Identity
when
using more
than one
Read
only
Program
number
Wait
Wait For
options
GoBack
Segment
GoBack
GoBack
Cycles
Holdback
Type
Holdback
Type
Holdback
Type

Navigation
20
MC19-1.22
7.2 Operator Level 1 - Program Running
Current
program page
Programming
Page
Home
display
Customer
Identity
ProgStat
program nr
See
previous
diagram
Read only
Segment nr
& type
Change
program
status
Program
Setpoint
Current
Segment
Type
Rate Time Dwell Wait
Segment
Target
Segment
Target
Segment
Rate
Segment
Rate
Cycles Left
Program
Time Left
Controller
identity
when using
more than
one
Segment time
remaining
&
program
status
Visible parameters
depend on Segment
Type
This manual suits for next models
2
Table of contents
Other Carbolite Controllers manuals