Carrier 50CD User manual

Single-Package
Cooling
Units
SAFETY
CONSIDERATIONS
Installation
and
servicing
of
air
conditioning
equipment
can
be
hazardous
due
to
system
pressure
and
electrical
components.
Only
trained
and
quali¬
fied
service
personnel
should
install,
repair
or
service
air
conditioning
equipment.
Untrained
personnel
can
perform
basic
mainte¬
nance
functions
of
cleaning
coils
and
filters
and
replacing
filters.
All
other
operations
should
be
per¬
formed
by
trained
service
personnel.
When
working
on
air
conditioning
equipment,
observe
precautions
in
the
literature,
tags
and
labels
attached
to
the
unit
and
other
safety
precautions
that
may
apply.
Follow
all
safety
codes.
Wear
safety
glasses
and
work
gloves.
Use
quenching
cloth
for
unbrazing
operations.
Have
fire
extinguisher
available
for
all
brazing
operations.
INSTALLATION
Unit
Rigging
and
Placement
—
Inspect
for
trans¬
portation
damage.
File
any
claim
with
transporta¬
tion
agency.
Spreader
bars
are
not
required
if
top
crating
is
left
on
unit.
Keep
unit
upright.
Do
not
drop
unit
(see
Fig.
1).
Rollers
may
be
used
to
move
unit
across
a
roof.
Level
by
using
frame
as
a
refer¬
ence.
Leveling
tolerance
is
±
1/
16-in.
per
linear
foot
in
any
direction.
This
is
necessary
for
condensate
drain
to
function
properly.
Table
1
shows
unit
weight.
See
Fig.
1
for
rigging
details.
Fig.
1
—
Rigging
Details
©
Carrier
Corporation
1983
Form
50CD-23SI

Table
1
—
Physical
Data
UNIT
SIZE
50CD/CH008
OPERATING
WEIGHT
(lb)
Unit
730
With
Economizer*
790
Roof
Curb*
—
14
in.
120
COMPRESSOR
No.
...Type
1
—
BRE2
Copeland
Oil
(oz)
124
REFRIGERANT
(Capillary
Control)
R-22
Charge
(lb)
105
CONDENSER
COIL
Copper
Tubes,
Aluminum
Fins
Rows
2
Fins/in.
13
9
Total
Face
Area
(sq
ft)
15
6
CONDENSER
AIR
FAN
Nominal
Cfm
4100
No.
...Diameter
(in.)
1
22
Motor
Hp
(1075
Rpm)
1/2
Hp
EVAPORATOR
COIL
Copper
Tubes,
Aluminum
Fins
Rows
3
Fins/in.
13
9
Total
Face
Area
(sq
ft)
8
2
EVAPORATOR
AIR
FAN
Quantity...Size
(in
)
1
12x9
Nominal
Cfm
3000
Minimum
and
Maximum
Cfm
(Standard
Motor)
2250
-
3650
(Optional
Motor)
2250
-
3750
Rpm
Range
Maximum
Allowable
Rpm
Motor
Pulley
Pitch
Diameter
(in.)
Fan
Pulley
Pitch
Diameter
(in
)
Belt
No.
...Type
Speed
Change
per
Full
Turn
of
652
-
924
924
2
4-3
4
12
7
1
A51
54
Moveable
Pulley
Flange
(Rpm)
Moveable
Pulley
Maximum
Full
Turns
from
Closed
Position
Factory
Setting
—
Full
Turns
Open
3
Factory
Speed
Setting
(Rpm)
760
Motor
Hp
(Service
Factor)
Standard
1
Hp
(1
4)
Optional
1
5
Hp
(1
3)
HIGH-PRESSURE
SWITCH
Cutout
(psig)
426
±
7
Reset
(psig)
320
±
20
LOW-PRESSURE
SWITCH
(Liquid
Line)
Cutout
(psig)
27
±
4
Reset
(psig)
67
±
7
OUTDOOR
AIR
INLET
SCREENS*
Economizer,
No
.
Size
(in
)
2
19x31x1/2
—
None
on
50CH008
RETURN
AIR
FILTERS*
(Type)
Disposable
—
None
on
50CH008
No.
...Size
(in.)
2
16
x
20
x
1
2
20
x
20
x
1
*50CD008
only
Accessory
Roof
Curb
(50CD008)
—
See
Fig.
2.
Assemble
and
install
in
accordance
with
instructions
shipped
with
curb.
Install
insulation,
cant
strips,
roofing
and
flashing
as
required.
Ductwork
must
be
attached
to
curb.
Unit
gasketing
to
roof
curb
is
critical
for
water
integrity.
Make
sure
that
gasketing
material
shipped
with
the
roof
curb
has
been
properly
installed
as
indicated
in
Fig.
2.
Roof
Mount
—
Check
building
codes
for
weight
distribution
requirements.
Table
1
shows
unit
weight.
Slab
Mount
(50CH008)
—
Provide
a
level
con¬
crete
slab
the
same
width
as
unit
that
extends
to
ends
of
base
rails
only.
The
slab
should
be
8
in.
thick
with
4
in.
above
grade.
Install
a
gravel
apron
in
front
of
outdoor
air
inlet
to
prevent
grass
and
foliage
from
obstructing
airflow.
Allow
a
minimum
of
6
in.
under
outdoor
coil
for
condensate
drainage.
In
areas
where
prolonged
sub-freezing
temperatures
or
heavy
snow
occur,
increase
clearance
to
12
in.
mini¬
mum,
18
in.
maximum.
Positioning
—
Position
unit
to
prevent
snowdrifts
from
blocking
condenser
coil
and
outdoor
air
intake
(50CD008).
Provide
clearance
around
and
above
unit
for
airflow,
safety
and
service
access.
Do
not
install
unit
in
an
indoor
location.
Do
not
locate
unit
air
inlets
near
exhaust
vents
or
other
sources
of
contaminated
air.
Although
unit
is
weatherproof,
guard
against
water
from
higher
level
runoff
and
overhangs.
©
2

50CD008
Roof
Curb
Dimensions
and
Details


Fig.
4
—
50CH008
Base
Unit
Dimensions
5

Outdoor
Air
Intake
(50CD008)
—
The
50CD
can
be
equipped
with
an
optional
outdoor
air
damper
or
an
economizer
that
mixes
outdoor
air
with
return
air.
Field-Fabricated
Ductwork
50CD
—
See
Fig.
3.
Secure
all
ducts
to
roof
curb
and
building
structure
before
unit
is
placed
on
curb.
Do
not
connect
ductwork
to
unit.
Cabinet
return
air
static
shall
not
exceed
0.35
in.
with
economzier
or
0.40
in.
without
economizer.
50CH
—
See
Fig.
4.
Secure
all
ductwork
to
flanges
on
unit
supply
air
and
return
air
openings
and
building
structure.
50CD/CH
—
Insulate
and
weatherproof
all
ex¬
ternal
ductwork,
joints
and
roof/
wall
openings
with
flashing
and
mastic
in
accordance
with
applicable
codes.
Insulate
ducts
passing
thru
an
unconditioned
space
and
cover
with
a
vapor
barrier.
A
minimum
clearance
is
not
required
for
any
air
duct
installation.
Optional
Manual
Outdoor
Air
Damper
(50CD
008)
—
Optional
outdoor
air
damper
is
shipped
with
hood
broken
down
in
unit
filter
section.
See
Fig.
5.
ASSEMBLY
1.
Remove
protective
polyethylene
cover
from
unit.
See
Fig.
5.
2.
Remove
upper
filter
access
panel
(save
screws).
See
Fig.
5.
3.
Remove
hood
parts
from
unit
evaporator
fan
and
filter
area.
Assemble
hood
top
and
side
plates
as
shown
in
Fig.
6.
Do
not
attach
hood
to
unit
at
this
time.
4.
Adjust
outdoor
air
damper
blade
to
desired
setting
for
outside
air
intake
by
releasing
linkage
rod
setscrew
and
adjusting
linkage
rod.
See
Fig.
7.
Secure
damper
blade
in
desired
position
with
setscrew.
5.
Remove
screws
holding
manual
outdoor
air
damper
to
unit.
See
Fig.
8.
6.
Install
outdoor
air
hood
assembly,
using
screws
from
step
5.
These
screws
secure
the
manual
outdoor
air
damper
assembly
and
the
outdoor
air
hood
to
unit.
See
Fig.
9.
7.
Slide
outdoor
air
inlet
screens
into
screen
tracks
on
hood
side
plates.
While
holding
screens
in
place,
fasten
screen
retainer
to
hood
using
screw
provided.
Make
sure
bottom
edge
of
screens
rest
inside
base
rail
as
shown
in
Fig.
9.
8.
Replace
upper
access
panel
with
screws
saved
from
step
2.
9.
To
check
percentage
of
ventilation
air
entering
unit,
proceed
as
follows:
a.
If
unit
power
is
on,
turn
it
off.
b.
Jumper
red
and
black
wires
in
24-v
barrier
in
main
control
box.
See
Fig.
10.
c.
Turn
on
unit
power
to
energize
evaporator
(indoor)
fan.
Fig.
6
—
Outdoor
Air
Hood
Details
d.
Check
percentage
of
ventilation
air
entering
unit.
If
percentage
varies
from
that
specified,
remove
upper
filter
access
panel
and
adjust
damper
blade
as
described
in
step
4.
Proce¬
dure
may
have
to
be
repeated
until
proper
percentage
of
ventilation
air
is
attained.
e.
Turn
off
power.
Remove
jumper
between
red
and
black
wires.
f.
Replace
upper
filter
access
panel.
50CH008
Unit
Assembly
—
Remove
packaging
and
tape
from
evaporator
fan
drive
system.
Evaporator
Air
Fan
—
Evaporator
fan
uses
a
belt-
drive
motor
which
provides
high
static
at
nominal
airflow.
The
standard
motor
provides
approxi¬
mately
0.95
in.
static
at
nominal
cfm
and
the
alter¬
nate
motor
provides
1.0
in.
static
at
nominal
cfm.
6

Fig.
7
—
Damper
Blade
Adjustment
Fig.
8
—
Manual
Outdoor
Air
Damper
SCREW
AIR
SCREENS
BASE
RAIL
Fig.
9
—
Outdoor
Air
Hood
Assembled
to
Base
Unit
{50
Series
Shown)
Condenser
Air
Fan
and
Motor
are
factory
set.
Refer
to
Service,
Condenser
Air
Fan
Adjustment,
as
required.
Condensate
Drain
—
See
Fig.
3
and
4
for
drain
location.
A
7/8-in.
ID
preformed
drain
hose
is
shipped
clamped
to
the
evaporator
basepan.
At
installation,
reroute
hose
so
that
it
passes
thru
the
hole
in
the
evaporator
basepan
and
the
unit
base
rail.
When
installed
properly,
the
hose
protrudes
thru
the
base
rail
about
3
in.
on
the
50CD008.
On
the
50CH008,
hose
protrudes
thru
the
side
of
the
base
rail
about
1
inch.
Replace
clamp
over
the
hose
where
it
passes
thru
the
basepan.
This
keeps
the
hose
level.
Use
a
trap
at
least
4
in.
deep
and
provide
protection
for
trap
against
freeze-up.
Field
Power
Supply
—
See
Fig.
11
and
Table
2.
Unit
is
factory
wired
for
voltage
shown
on
name¬
plate.
On
208-volt
installations,
reconnect
all
trans¬
formers
to
208-
(200-)
volt
tap.
Refer
to
unit
label
diagrams.
Pigtails
are
provided
for
field
service
on
units
without
electric
heat
(use
factory-supplied
splices
or
UL-approved
copper/
aluminum
con¬
nector).
Units
with
electric
heat
are
provided
with
terminal
block
in
single
point
box.
All
field
wiring
must
comply
with
National
Elec¬
trical
Code
and
local
requirements.
Run
power
lines
thru
condenser
coil
end
panel
to
terminal
connections
as
shown
on
unit
wiring
diagram
and
in
Fig.
3
and
Fig.
4.
->
Operating
voltage
to
compressor
must
be
within
voltage
range
indicated
on
unit
nameplate.
On
3-
phase
units,
voltages
between
phases
must
be
balanced
within
2%
and
the
current
must
be
bal¬
anced
within
10%.
Use
the
following
formula
to
determine
the
%
voltage
unbalance.
%
Voltage
Unbalance
max
voltage
deviation
from
average
voltage
x
average
voltage
7

WITHOUT
ELECTRIC
HEAT
UNIT
CONTROL
BOX
C
—
Contactor
Comp
—
Compressor
Gnd'
P
Equipment
Ground
Fu
—
Fuse
TB
—
Terminal
Block
_Factory
Wiring
_
Field
Power
Wiring
Field
Splice
WITH
ELECTRIC
HEAT
SINGLE
POINT
BOX
Fig.
11
—
Field
Power
Wiring
Connections
Table
2
—
Electrical
Data
50CD/CH008
NOMINAL
V-PH-HZ
VOLTAGE
RANGE
COMPR
OFM
IFM
ELECTRIC
HEATERS
POWER
SUPPLY
50CD008
50CH008
|
50CD008
50CH008
Kw
p—
FLA
Kw
FLA
Min
Ckt
i
MOCP
Arr
Min
Ckt
J
MOCP
ips
Min
Max
RLA
LRA
|
FLA
Hp
FLA
|
208/230-3-60
j
187
254
I
I
32
5
j
183
29
j
1
80
1
-
.
L_.-_
55/55
i
60/60*
55/55
60/60*
93]
20-23
93
20-23
55/55
60/60
55/55
60/60
186
j
40-46
158
33-38
60/70
“60/70"]
55/60
60/60
28
1
|
59-68
31
5
j
68-76
85/95
80/90
|
95/105
|
90/100
460-3-60
i
414
508
15
2
|
91
1
:
1
5
;
1
1
2
9
r
r
-
i
25
35
*
;
25
|
35*
97
j
11
7
97
11
7
25
35
i
25
35
160
i
193
16
0
j
19
3
30
35
j
30
35
19
4
23
4
31
5
:
37
9
40
35
55
45
29
6
35
7
50
_
4
5
.
.
.
i
FLA
—
Full
Load
Amps
Hp
—
Horsepower
IFM
—
Indoor
Fan
Motor
LRA
—
Locked
Rotor
Amps
MOCP
—
Maximum
Overcurrent
Protection
OFM
—
Outdoor
Fan
Motor
RLA
—
Rated
Load
Amps
*Fuse
only
Example:
Supply
voltage
is
460-3-60.
abc
AB
=
452
volts
BC
=
464
volts
AC
=
455
volts
Average
Voltage
452
+
464
+
455
1371
=
457
Determine
maximum
deviation
from
average
voltage:
(AB)
457
-
452
=
5
volts
(BC)
464
-
457
=
7
volts
(AC)
457
-
455
=
2
volts
Maximum
deviation
is
7
volts
Determine
%
voltage
unbalance:
%
Voltage
Unbalance
=
100
x
~=j
-
1.53%
This
amount
of
phase
unbalance
is
satisfactory
as
it
is
below
the
maximum
allowable
2%.
8

THERMOSTAT
ASSEMBLY
LOW-VOLTAGE
THERMOSTAT
CONNECTIONS
IN
UNIT
CONTROL
BOX
->
Fig.
12
—
Field
Control
Thermostat
Wiring
Unit
failure
as
a
result
of
operation
on
improper
line
voltage
or
excessive
phase
imbalance
constitutes
abuse
and
may
cause
damage
to
electrical
compo¬
nents.
Such
operation
would
invalidate
any
appli¬
cable
Carrier
warranty.
UNITS
WITH
ELECTRIC
HEAT
—
When
elec¬
tric
heat
is
installed,
connect
the
field
power
wires
to
terminal
block
located
in
the
single
point
box.
The
single
point
box
is
attached
to
the
corner
post,
directly
below
the
control
box.
DISCONNECTS
—
A
fused
disconnect
is
required
only
on
units
without
electric
heat.
When
electric
heat
is
installed,
use
a
NEC
disconnect
of
adequate
size.
Provide
fusing
for
disconnect
if
required
by
local
codes.
The
unit
informative
nameplate
and
Table
2
list
electric
heat
fuse
and
wire
amperage.
Field
Control
Wiring
—
Install
a
Carrier-approved
accessory
thermostat
assembly
according
to
instal¬
lation
instructions
included
with
accessory.
Locate
thermostat
assembly
on
a
solid
wall
in
the
condi¬
tioned
space
to
sense
average
temperature.
THERMOSTAT
WIRES
—
Use
18
gage
for
0-
to
50-ft
long
wires,
16
gage
for
50-
to
75-ft
wire
lengths.
Route
the
control
wires
thru
hole
provided
in
the
corner
post
(see
Fig.
3
and
4)
and
then
feed
wires
thru
a
raceway
built
into
the
corner
post.
Route
wires
from
the
raceway
into
the
24-v
barrier
located
on
the
left
side
of
the
control
box.
Make
connections
as
shown
in
Fig.
12.
Set
heat
anticipator
settings
as
indicated
below.
Heat
Anticipator
Settings
1st
Stage
9
2nd
Stage
with
2
Heaters
and
2-Stage
Heat
Thermostat*
3
*Applies
only
to
50CD
Settings
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
a
particular
installation.
Refer
to
accessory
remote
control
panel
instruc¬
tions
as
required.
Return
Air
Filters
(50CD008)
—
Make
sure
correct
filters
are
installed
in
filter
tracks.
See
Table
1.
Do
not
operate
unit
without
return
air
filters.
Outdoor
Air
Inlet
Screens
(50CD008)
—
Out¬
door
air
inlet
screen(s)
must
be
in
place
before
operating
unit.
Economizer
Section
(50CD008)
—
Optional
economizer
is
shipped
with
hood
broken
down
in
unit
filter
section.
See
Fig.
13.
Fig.
13
—
Access
Panel
Location
ASSEMBLY
1.
Remove
protective
polyethylene
cover
from
unit.
See
Fig.
13.
2.
Remove
upper
filter
access
panel
(save
screws).
See
Fig.
13.
3.
Remove
hood
parts
from
unit
evaporator
fan
and
filter
area.
Assemble
hood
top
and
side
plates
as
shown
in
Fig.
14.
Do
not
attach
hood
to
unit
at
this
time.
Put
aside
baffle,
screen
retainer
and
retainer
screw
for
later
assembly.
4.
Determine
if
vent
air
is
required
in
building
to
be
conditioned.
If
so,
check
for
percentage
of
9

vent
air
needed
and
record
quantity
for
vent
adjustment
in
step
11.
5.
R
e
move
jumper
plug
from
base
unit
receptacle
and
discard.
Insert
economizer
plug
into
recep¬
tacle.
See
Fig.
15.
Steps
6
thru
8
involve
releasing
and
adjusting
indoor
damper
blades
from
factory
set
position.
Fig.
14
—
Outdoor
Air
Hood
Details
ECONOMIZER
PLUG
CLS
—
Cooling
Lockout
Switch
EC
—
Enthalpy
Control
OAT.
—
Outdoor
Air
Thermostat
OUTDOOR
AIR
INLET
SCREENS
(2)
Fig.
15
—
Economizer
Installed
in
Unit
6.
R
e
lease
indoor
blades’
drive
linkage
by
loosen¬
ing
linkage
connector
setscrew
at
indoor
crank-
arm
on
drive
shaft.
See
Fig.
16.
Remove
pink
wire
from
economizer
damper
motor
terminal
D
and
temporarily
tape
bare
wire
end.
Remove
violet
wire
from
economizer
damper
motor
and
connect
to
terminal
D
on
economizer
damper
motor.
See
Fig.
17.
OUTDOOR
BLADES(2)
DRIVE
SHAFT
OUTDOOR
DRIVE
LINKAGE
Fig.
16
INDOOR
BLADES
(3)
Economizer
Details
ECONOMIZER
DAMPER
MOTOR
PINK
WIRE
VIOLET
WIRE
TERMINAL
D
Fig.
17
—
Economizer
Motor
Connections
7.
Jumper
red
(base
unit
24-v
power)
and
black
(evaporator
fan
motor)
wires
in
24-volt
control
box
compartment.
See
Fig.
10.
Turn
on
base
unit
power
to
energize
evap¬
orator
fan.
The
economizer’s
outdoor
blades
should
open
completely.
8.
Adjust
the
indoor
blades’
drive
linkage
so
that
indoor
blades
are
fully
closed.
Tighten
the
linkage
connector
setscrew.
Turn
off
base
unit
power.
Reconnect
pink
and
violet
wires
to
economizer
motor,
as
shown
in
Fig.
17.
9.
If
vent
air
is
required,
leave
red
and
black
wires
jumpered.
If
vent
air
is
not
needed,
remove
jumper
between
red
and
black
wires.
10.
Fasten
baffle
to
left
side
of
damper
plate
with
round
head
screws
provided.
See
Fig.
18.
10

Fig.
18
—
Baffle
Installation
Details
Fig.
19
—
Vent
Position
Setting
Details
11.
If
vent
air
is
not
required,
go
on
to
step
12.
If
vent
air
is
required,
proceed
as
follows:
a.
Turn
on
base
unit
power.
This
energizes
the
evaporator
fan
motor.
b.
Slide
economizer
out
of
unit
so
that
access
hole
to
vent
position
setscrew
is
visible
See
Fig.
19.
c.
Adjust
vent
opening
by
loosening
vent
posi¬
tion
setscrew
on
left
side
of
economizer
damper
motor
and
setting
vent
position
lever
to
adjust
damper.
See
Fig.
19.
Move
vent
position
lever
back
toward
evaporator
coil
to
close
damper
or
forward
to
open
damper.
When
adjustment
is
completed,
retighten
setscrew.
d.
1
urn
off
base
unit
power
and
remove
jumper
from
red
and
black
wires.
e.
Slide
economizer
assembly
back
into
unit.
12.
Remove
tape
from
outdoor
air
thermostat
(OAT.)
and
cooling
lockout
switch
(CLS),
and
fasten
to
inside
of
hood
with
screws
and
speed
clips
provided.
Make
sure
terminals
on
OAT
are
up.
See
Fig.
20.
Fig.
20
—
Outdoor
Air
Thermostat/
Enthalpy
Control
and
Cooling
Lockout
Switch
Installation
11

13.
Fasten
hood
top
and
side
plate
assembly
(Fig.
9)
and
economizer
to
unit
with
screws
supplied.
Before
attaching,
make
sure
bottom
of
hood
assembly
is
resting
on
top
of
unit
base
rail.
14.
Place
knob
supplied
with
accessory
economizer
on
OAT.
See
Fig.
20.
Set
for
3
degrees
below
indoor
room
thermostat
setting.
If
accessory
enthalpy
control
(EC)
(Fig.
20)
is
used
in
lieu
of
OAT.,
refer
to
instructions
shipped
with
accessory
enthalpy
control
for
installation
and
adjustment.
15.
Connect
OAT./EC
and
CLS
per
unit
label.
See
Fig.
21.
Connect
2
economizer
wires
to
each
switch
with
quick-connects.
Unit
connecting
wires
are
shipped
taped
on
outdoor
blade.
See
Fig.
15.
16.
Slide
outdoor
air
inlet
screens
in
hood
screen
tracks.
Secure
screens
with
screen
retainer
across
hood
front.
Secure
screen
retainer
with
screw
provided.
See
Fig.
22.
17.
Replace
upper
filter
access
panel
with
screws
saved
from
step
2.
18.
Turn
base
unit
power
on.
CLS
CLS
—
Cooling
Lockout
Switch
EC
—
Enthalpy
Control
OAT.
—
Outdoor
Air
Thermostat
NOTE:
When
Enthalpy
Control
(EC)
is
installed,
outdoor
air
thermo¬
stat
(OAT
)
is
removed
from
economizer
Fig.
21
—
Wiring
Connections
for
Outdoor
Air
Thermostat/or
Enthalpy
Control
and
Cooling
Lockout
Switch
AIR
INLET
SCREEN
OUTDOOR
AIR
.BASE
UNIT
RETAINER
HOOD
/
Fig.
22
—
Economizer
and
Outdoor
Air
Hood
Assembled
to
Unit
START-UP
Unit
Preparation
—
Make
sure
unit
has
been
installed
in
accordance
with
installation
instruc¬
tions
and
applicable
codes.
Compressor
Mounting
—
Compressors
are
inter¬
nally
spring
mounted.
Do
not
loosen
or
remove
compressor
holddown
bolts.
Internal
Wiring
—
Check
all
electrical
connections
in
unit
control
boxes.
.
.tighten
as
required.
Refrigerant
Service
Valves
—
Each
unit
system
has
2
Schrader
type
service
ports,
one
on
the
suction
line
and
one
on
the
compressor
discharge
line.
Be
sure
that
caps
on
the
ports
are
tight.
Crankcase
Heater{s)
are
energized
as
long
as
there
is
power
to
the
unit.
Energize
heater(s)
24
hours
prior
to
base
unit
start-up.
Cooling
—
To
start
unit,
turn
on
main
power
supply.
Set
system
selector
switch
to
COOL
and
fan
switch
at
AUTO.
Adjust
thermostat
to
a
setting
below
room
temperature.
Compressor
starts
on
closure
of
contactor.
Check
cooling
effects
at
a
setting
above
room
temperature.
Check
unit
charge.
Refer
to
Refrig¬
eration
Charge
in
Service
section.
Reset
thermostat
at
a
position
above
room
tem¬
perature.
Compressor
will
shut
off.
TO
SHUT
OFF
UNIT
—
Set
system
selector
switch
at
OFF
position
or
reset
thermostat
at
a
position
above
room
temperature.
Units
are
equipped
with
Cycle-LOC
™
protection
device.
Unit
shuts
down
on
any
safety
trip,
and
indicator
light
on
thermostat
comes
on.
Check
reason
for
safety
trip.
Compressor
restart
is
accomplished
by
manual
reset
at
the
thermostat
by
turning
the
selector
switch
to
OFF
and
then
to
ON.
Heating
—
To
start
unit,
turn
on
main
power
supply.
Refer
to
Crankcase
Heaters.
Set
thermostat
at
HEAT
and
a
setting
above
room
temperature,
fan
at
AUTO.
First
stage
of
thermostat
energizes
the
first-stage
electric
heater;
second-stage
electric
heater
elements
if
installed.
Check
heating
effects
at
air
supply
grille(s).
TO
SHUT
OFF
UNIT
—
Set
system
selector
switch
at
OFF
or
set
heating
selector
lever
below
room
temperature.
Ventilation
(Continuous
Fan)
—
Set
fan
and
sys¬
tem
selector
switches
at
ON
and
OFF,
respectively.
Evaporator
air
fan
operates
continuously
to
provide
constant
air
circulation.
Economizer
Operation
(50CD008)
—
See
pages
9
thru
12
for
start-up
and
checkout
proce¬
dures.
If
unit
is
equipped
with
modulating
out¬
door
air
control
(economizer),
it
should
operate
as
follows:
COOLING
MODE
—
Evaporator
and
condenser
fans
and
compressor
energize
when
there
is
a
call
12

for
cooling
and
outdoor
ambient
temperature
is
above
outdoor
air
thermostat
setting.
The
econo¬
mizer
damper
moves
to
VENT
position.
Evaporator
fan
starts
and
economizer
damper
opens
fully
upon
a
first-stage
call
for
cooling
when
outdoor
ambient
temperature
is
below
the
outdoor
air
thermostat
setting.
Compressor
remains
off.
Compressor
is
energized
and
mechanical
cooling
integrates
with
economizer
cooling
upon
a
second-
stage
call
for
cooling.
Mechanical
cooling
is
locked
out
when
ambient
temperature
is
below
50
F.
Economizer
damper
modulates
when
mixed
air
temperature
is
below
mixed
air
thermostat
(non-
adjustable)
setting.
An
economizer
control
thermostat
(ECT)
is
located
on
the
evaporator
coil.
This
thermostat
guards
against
abnormally
low
suction
tempera¬
tures
while
operating
mechanical
cooling
in
con¬
junction
with
economizer.
Low
suction
tempera¬
tures
can
lead
to
frosting
on
the
evaporator
coil.
If
frost
buildup
is
detected,
thermostat
turns
off
economizer,
thus
closing
the
outdoor
air
damper.
This
raises
air
temperature
entering
the
evaporator
coil
and
melts
frost.
Once
frost
is
melted,
the
economizer
is
re-energized.
During
unoccupied
periods,
if
a
field-supplied
night
switch
is
used
and
is
opened,
the
outdoor
air
damper
closes.
HEATING
MODE
Outdoor
air
damper
stays
at
VENT
position
while
evaporator
air
fan
runs.
If
field-supplied
night
switch
is
used,
the
outdoor
air
damper
closes
when
switch
is
open.
SERVICE
Cleaning
—
Inspect
unit
interior
at
the
beginning
of
each
heating
and
cooling
season
or
as
operating
conditions
require.
Remove
unit
side
panels
for
access
to
unit
interior.
EVAPORATOR
COIL
1.
Turn
unit
power
off.
2.
Disconnect
evaporator
motor
and
electric
heater(s)
from
main
control
box.
3.
Remove
top
panel
screws
shown
in
Fig.
23.
4.
Remove
screws
from
base
of
evaporator
fan
housing
and
electric
heater
plate.
5.
Pry
up
top
panel
to
clear
top
of
evaporator
fan
housing.
See
Fig.
23.
6.
Remove
evaporator
fan
housing,
heaters
and
heater
plate
from
unit.
7.
Use
commercial
coil
cleaner
(Oakite
164),
or
dishwasher
detergent
in
a
pressurized
spray
cannister.
Wash
both
sides
of
coil
and
flush
with
clear
water.
For
best
results,
backflush
towards
return
air
section
to
remove
foreign
material.
Flush
condensate
pan
after
completion.
8.
Replace
evaporator
fan
housing,
electric
heater(s)
and
all
wires.
Fig.
23
—
Removing
Top
Panel
Fig.
24
—
Cleaning
Condenser
Coil
CONDENSER
COIL
—
Inspect
coil
monthly.
Clean
condenser
coil
annually,
or
as
required
by
location
or
outdoor
air
conditions.
Fins
are
not
continuous
thru
coil
sections.
Dirt
and
debris
may
pass
thru
first
section,
become
trapped
between
the
2
rows
of
fins,
and
restrict
con¬
denser
airflow.
Shine
flashlight
thru
coil
to
deter¬
mine
if
dirt
or
debris
has
collected
between
coil
sections.
13

Clean
coil
as
follows:
1.
Turn
off
unit
power.
2.
Remove
top
panel
screws
on
condenser
end
of
unit.
Remove
screws
from
coil
side
of
coil
center
post.
Do
not
remove
center
post.
3.
Remove
condenser
coil
corner
post.
See
Fig.
24.
To
hold
top
panel
open,
place
coil
corner
post
between
top
panel
and
center
baffle.
See
Fig.
25.
4.
Remove
device
holding
coil
sections
together
at
return
end
of
condenser
coil.
Carefully
separate
the
outer
coil
section
3
to
4
in.
from
the
inner
coil
section.
See
Fig.
26.
5.
Use
a
water
hose
or
other
suitable
equipment
to
flush
down
between
the
2
coil
sections
to
remove
dirt
and
debris.
Clean
the
outer
surfaces
with
a
stiff
brush
in
the
normal
manner.
6.
Reposition
the
outer
coil
section,
remove
the
coil
corner
post
from
between
the
top
panel
and
center
baffle.
Secure
the
sections
together.
Install
the
corner
post,
coil
center
post
and
replace
all
screws.
Fig.
25
—
Propping
Up
Top
Panel
Fig.
26
—
Separating
Coil
Sections
CONDENSATE
DRAIN
—
Check
and
clean
each
year
at
start
of
cooling
season.
In
winter,
keep
drain
and
trap
dry
or
protect
against
freeze-up.
FILTERS
—
Clean
or
replace
at
start
of
each
heat¬
ing
and
cooling
season,
or
more
often
if
operating
conditions
require
it.
OUTDOOR
AIR
INLET
SCREENS
(50CD008)
—
Clean
screens
with
steam
or
hot
water
and
a
mild
detergent.
Do
not
use
throwaway
filters
in
place
of
screens.
Lubrication
COMPRESSORS
—
Each
compressor
is
charged
with
correct
amount
of
oil
at
the
factory.
FAN
MOTOR
BEARINGS
—
No
lubrication
of
condenser
or
evaporator
fan
motors
is
required
for
first
5
years
of
operation.
Annually
thereafter,
clean
and
repack
bearings
with
a
suitable
bearing
grease.
Condenser
Air
Fan
Adjustment
(Fig.
27)
—
Shut
off
unit
power
supply.
Remove
condenser
fan
assembly
(grille,
motor,
motor
cover
and
fan)
and
loosen
fan
hub
setscrews.
Adjust
fan
height
as
shown
in
Fig.
27.
Tighten
setscrews
and
replace
condenser
fan
assembly.
Fig.
27
—
Condenser
Air
Fan
Adjustment
Manual
Outdoor
Air
Damper
(50CD008)
—
If
outdoor
air
damper
blade
adjustment
is
required,
see
Optional
Manual
Outdoor
Air
Damper
section
on
page
6.
Economizer
Adjustment
(50CD008)
—
Refer
to
Economizer
section
under
Installation.
Refrigerant
Charge
—
Amount
of
refrigerant
charge
is
listed
on
unit
nameplate
(also
refer
to
Table
1).
Refer
to
Carrier
Standard
Service
Tech¬
niques
Manual,
Chapter
1,
Refrigerants.
Unit
panels
must
be
in
place
when
unit
is
oper¬
ating
during
charging
procedure.
14

NO
CHARGE
—
Use
standard
evacuating
tech¬
niques.
After
evacuating
system,
weigh
in
the
specified
amount
of
refrigerant.
(Refer
to
Table
1.)
LOW
CHARGE,
COOLING
—
Using
Cooling
Charging
Chart,
Fig.
28,
vary
refrigerant
until
the
conditions
of
the
chart
are
met.
Note
the
charging
chart
is
different
from
type
normally
used.
Chart
is
based
on
charging
the
units
to
the
correct
superheat
for
the
various
operating
conditions.
Accurate
pres¬
sure
gage
and
temperature
sensing
device
are
re¬
quired.
Connect
the
pressure
gage
to
the
service
port
on
the
suction
line.
Mount
the
temperature
sensing
device
on
the
suction
line
and
insulate
it
so
that
outdoor
ambient
temperature
does
not
affect
the
reading.
Indoor
air
cfm
must
be
within
the
normal
operating
range
of
the
unit.
TO
USE
COOLING
CHARGING
CHART
—
Take
the
outdoor
ambient
temperature
and
read
the
suction
pressure
gage.
Refer
to
chart
to
determine
what
suction
temperature
should
be.
If
suction
tem¬
perature
is
high,
add
refrigerant.
If
suction
tempera¬
ture
is
low,
carefully
blow
some
of
the
charge.
Re¬
check
the
suction
pressure
as
charge
is
adjusted.
Example:
50CD/CH008
(Fig.
28)
Outdoor
Temperature.85
F
Suction
Pressure.
70
psig
Suction
Temperature
should
be.52
F
(Suction
Temperature
may
vary
±
5
F.)
20
30
40
50
SUCTION
LINE
TEMPERATURE
60
(
F)
70
80
-7
-i
-4
10
16
SUCTION
LINE
TEMPERATURE
(C
)
21
27
Fig.
28
—
50CD/CH008
Cooling
Charging
Chart
If
Chargemaster®
charging
device
is
used,
tem¬
perature
and
pressure
readings
must
be
accom¬
plished
using
the
charging
chart.
15

For
replacement
items
use
Carrier
Specified
Parts
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.
Book
1
4
Tab
1b
6b
Form
50CD-23SI
Supersedes
50CD-13SI
Printed
in
U
S
A
5-83
PC
111
Catalog
No
565-018
This manual suits for next models
1
Table of contents
Other Carrier Freezer manuals

Carrier
Carrier PH61 User manual

Carrier
Carrier Taylor 632 User manual

Carrier
Carrier WeatherMaster Series User manual

Carrier
Carrier Transicold 69NT40-561-199 Operation manual

Carrier
Carrier B5 Installation instructions

Carrier
Carrier C708 User manual

Carrier
Carrier C302 NPR User manual

Carrier
Carrier 2SF-13 User manual

Carrier
Carrier 50DPE014 Dimensions and installation guide

Carrier
Carrier NEOS 100S User manual