Carrier UPC Open Quick setup guide

U
UP
PC
C
O
Op
pe
en
n
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
a
an
nd
d
I
In
nt
te
eg
gr
ra
at
ti
io
on
n
G
Gu
ui
id
de
e
CARRIER CORPORATION ©2017
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-468-01 · 6/1/2017

Verify that you have the most current version of this document from www.hvacpartners.com or your local Carrier
office.
Important changes are listed in Document revision history at the end of this document.
CARRIER CORPORATION ©2017. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier
Corporation. All other trademarks are the property of their respective owners.

Contents
UPC Open overview and specifications...................................................................................................................... 1
What is the UPC Open?........................................................................................................................................1
Specifications ........................................................................................................................................................2
Safety considerations...........................................................................................................................................3
Installing the UPC Open .............................................................................................................................................. 4
Mounting the UPC Open ......................................................................................................................................4
Wiring the UPC Open for power..........................................................................................................................4
To wire for power................................................................................................................................... 5
Addressing the UPC Open....................................................................................................................................5
Wiring for communications.................................................................................................................................5
Wiring specifications for BACnet MS/TP and ARC156........................................................................ 6
To wire the controller to the BACnet network
...................................................................................... 6
Wiring the UPC Open to the CCN network ........................................................................................................7
Wiring specifications for CCN ............................................................................................................... 7
To wire the CCN equipment to the UPC Open...................................................................................... 8
Wiring devices to the UPC Open's Rnet port ....................................................................................................8
Rnet wiring specifications..................................................................................................................... 8
ZS Sensor overview ............................................................................................................................... 9
SPT sensor overview ............................................................................................................................. 9
To wire the ZS or SPT sensor to the UPC Open .................................................................................10
Wireless sensor overview ...................................................................................................................10
To install the Wireless Adapter for wireless sensors.........................................................................11
To wire an Equipment Touch to the UPC Open..................................................................................12
Start-up.......................................................................................................................................................................14
Select or create a custom control program and graphic for the UPC Open............................................. 14
To install the UPC Open into an i-Vu® Control System................................................................................ 15
Configure the UPC Open's properties ............................................................................................................. 16
Troubleshooting .........................................................................................................................................................18
LED's .................................................................................................................................................................... 18
To get the serial number .................................................................................................................................. 19
To restore defaults............................................................................................................................................. 20
To replace the UPC Open's battery ................................................................................................................. 20
Compliance ................................................................................................................................................................21
FCC Compliance................................................................................................................................................. 21
CE Compliance ................................................................................................................................................... 21
BACnet Compliance........................................................................................................................................... 21
Appendix: Single Point Linkage and Device Address Binding ...............................................................................22
Single Point Linkage ......................................................................................................................................... 22
Device Address Binding .................................................................................................................................... 23
Document revision history ........................................................................................................................................24


UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
1
What is the UPC Open?
The UPC Open (Universal Protocol Converter) is a general purpose protocol converter. The UPC Open can convert
proprietary equipment data into open protocol data, enabling a stand-alone, single piece of equipment to reside
on a BACnet network, where it can be monitored or controlled by a Building Automation System (BAS).
NOTE A future release of the UPC Open will support installation on a Modbus, N2, or LonWorks network.
UPC Open overview and specifications

UPC Open overview and specifications
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
2
Specifications
Driver
drv_upcopen_x-xxx-xxx
Maximum number of control
programs
2
Maximum number of
BACnet objects*
1050
* Depends on available
memory
Total available memory for application is 551244 bytes.
Obtain available memory information by viewing a Module Status report after the
control program is loaded.
Power
24 Vac ±10%, 50–60 Hz
10 VA power consumption (16 VA with BACview® device attached)
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
We highly recommend using a dedicated transformer to power the UPC Open.
BAS port (Port 1a)
3-pin port supports EIA-485 2-wire communications.
Protocols supported (DIP switch selectable):
○BACnet MS/TP (m)
○BACnet ARC156
○Modbus (RTU) (future)
○Johnson N2 (future)
○LonWorks (future)
This port must be configured as a BAS port.
CCN port (Port 2)
5-pin port supports EIA-485 3-wire connection to a single Carrier CCN controller
LON-OC port
14-pin communication port supports the LonWorks Option Card (future)
Rnet port
The UPC Open only supports ZS sensors, Equipment Touch, and wireless sensors
with the 6.04.xxx or later driver.
Supports:
•Up to 10 ZS sensors (5 per control program)
•One Wireless Adapter that communicates with up to 15 wireless sensors
•One Equipment Touch
•Up to 4 SPT Standard sensors and one SPT Plus, SPT Pro, or SPT Pro-F
sensor.
NOTE ZS sensors, a Wireless Adapter, and an Equipment Touch can share the
Rnet, but not SPT sensors.
Local Access port
For system start-up and controller troubleshooting using Field Assistant or
Equipment Touch
Battery
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties,
schedules, and trends.
Protection
Built-in surge and transient protection circuitry - internal solid state Polyswitches
on the incoming power and network connections.
Real time clock
Battery-backed real time clock keeps track of time in the event of a power failure

UPC Open overview and specifications
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
3
Status indicators
LED's indicate status of communications, running, errors, and power.
Environmental operating
range
-22 to 150°F (-30 to 66°C), 0 to 90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged GE C2950HF Cycoloy plastic
Overall dimensions
A:
B:
5-3/16 in. (13.2 cm)
4-1/8 in. (10.5 cm)
Mounting hole dimensions
C:
D:
E:
4-7/8 in. (12.4 cm)
2-1/20 in. (5.2 cm)
3/16 in. (.5 cm)
Panel depth
2 in. (5.1 cm)
Weight
.44 lbs (.2 kg)
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
Listed by
UL-916, (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15-Subpart B-Class
A
Safety considerations
WARNING Disconnect electrical power to the UPC Open before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
4
1 Mount the controller (page 4).
2 Wire the controller for power (page 4).
3 Set the controller's address (page 5).
4 Wire the controller to the BACnet MS/TP or BACnet ARC156 network (page 5).
5 Wire the controller to the CCN network (page 5).
6 Wire devices to the controller's Rnet port (page 8).
Mounting the UPC Open
WARNING
When you handle the UPC Open:
•Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
•Do not touch components or leads.
•Handle the board by its edges.
•Isolate from high voltage or electrostatic discharge.
•Ensure that you are properly grounded.Screw the UPC Open into an enclosed panel using the mounting slots
on the coverplate. Leave about 2 in. (5 cm) on each side of the controller for wiring. Mounting hole dimensions 4.8
in. (12.2 cm) between mounting slot center lines.
Wiring the UPC Open for power
CAUTION The UPC Open is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present. The UPC Open is a half wave device. Half
wave and full wave devices cannot share power. Examples of a full wave device are a CVC or ICVC in an applied
chiller.
Carrier controllers can share a power supply as long as you:
• Maintain the same polarity
• Use the power supply only for Carrier Open controllers
Installing the UPC Open

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
5
To wire for power
1 Remove power from the power supply.
2 Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
3 Connect the transformer wires to the screw terminal connector.
NOTE If using a grounded transformer, connect the ungrounded lead to the Hot terminal to avoid damaging
the transformer.
4 Apply power to the power supply.
5 Measure the voltage at the UPC Open’s power input terminals to verify that the voltage is within the operating
range of 21.6–26.4 Vac.
6 Insert the screw terminal connector into the UPC Open's power terminals.
7 Verify that the Power LED is on and the Run LED is blinking.
Addressing the UPC Open
EIAYou must give the UPC Open a MAC address that is unique on the MS/TP or ARCNET network. You can address
the UPC Open before or after you wire it for power
1 If the UPC Open has been wired for power, pull the screw terminal connector from the controller's power
terminals labeled Gnd and Hot. The controller reads the address each time you apply power to it.
2 Using the rotary switches, set the controller's address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
CAUTION The factory default setting is 00 and must be changed to successfully install your UPC Open.
Wiring for communications
The UPC Open communicates using BACnet on the following types of network segments:
•MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
•ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
6
Wiring specifications for BACnet MS/TP and ARC156
Cable:
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length:
2000 feet (610 meters)
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
To wire the controller to the BACnet network
1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the controller’s screw terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
4 Set the communication type and baud rate.
For...
Set DIP switches 1 and 2
to...
DIP switch 3
Set DIP switch 4
to...
Set DIP switches 5 through 8 to...
MS/TP (m)
The appropriate baud
rate. See the MS/TP
Baud diagram on the
controller.
N/A
On
Off/Off/Off/Off
ARC156
N/A. Baud rate will be
156 kbps regardless of
the DIP switch settings.
N/A
Off
N/A
NOTE Use the same baud rate for all controllers on the network segment.
5 For MS/TP, verify that the EIA-485 jumpers are set to EIA-485 and 2w.
6 Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.
7 If the UPC Open is at either end of a network segment, connect a BT485 to the UPC Open.
8Insert the power screw terminal connector into the UPC Open's power terminals.
9 Verify communication with the network by viewing a Module Status report in the i-Vu® interface.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
7
Wiring the UPC Open to the CCN network
The UPC Open's CCN Port communicates using EIA RS-485 and supports 9600 bps. Future versions will support
baud rates of 19.2 and 38.4 kbps.
NOTES
•The UPC Open is intended to be wired directly to one piece of Carrier equipment.
NOTE The exception is a Multiple Chiller application, which consists of 2 or 3 chillers configured for
Lead/Lag, with a potential third chiller as a standby chiller. In this application, wire the CCN network between
the UPC Open and chillers in a daisy-chain configuration. All other applications have one network segment
between the UPC Open and the interfaced Carrier equipment.
•Refer to the CCN Installation and Start-up Guide for more details on wiring the CCN bus.
Multiple chiller application only (Lead/Lag, and, possibly, a standby chiller)
Single unit application
Wiring specifications for CCN
Cable:
20 AWG, general purpose, 3-conductor, foil shielded copper wire
Maximum length:
1000 feet (305 meters)

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
8
To wire the CCN equipment to the UPC Open
1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
2 Pull the screw terminal connector from the UPC Open's CCN Port.
3 Check the communications wiring for shorts and grounds.
4 Connect the communications wiring to the CCN Port’s screw terminals labeled Net +, Net -, and Shield.
NOTE Maintain the same polarity.
5 Verify that the EIA-485 jumpers are set to EIA-485 and 2w.
6 Insert the power screw terminal connector into the UPC Open's CCN Port's terminals.
7 Insert the power screw terminal connector into the UPC Open's power terminals.
8 Verify the LED lights TX2 and RX2 are flashing to indicate the UPC Open is communicating on the CCN Port.
NOTE If the CCN target address differs from what the UPC Open is configured for (default 0, 1), then only the
transmit LED flashes about 1 time per second.
Wiring devices to the UPC Open's Rnet port
The UPC Open only supports ZS sensors, Equipment Touch, and wireless sensors using the 6.04.xxx or later
driver.
You can connect communicating zone sensors and/or the Equipment Touch with built-in temperature and
humidity sensors to monitor room temperature.
The Rnet communicates at a rate of 115 kbps.
CAUTIONS
•You cannot have an SPT sensor on the same Rnet as a ZS sensor or an Equipment Touch.
•Do not exceed 200 mA for all Rnet devices.
NOTE The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc if needed.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor
22 AWG (7x0096) bare copper if Rnet has only sensors
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
9
Color Code
Black, white, green, red
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
ZS Sensor overview
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO2, or VOC. ZS
Sensors are wired to the Rnet port on i-Vu® Open controllers.
REQUIREMENTS
•A v6.5 or later i-Vu® system
•v6.04.xxx or later controller drivers
You can use the following ZS sensors:
•ZS Standard
•ZS Plus
•ZS Pro
NOTES
•A control program can use no more than 5 ZS Sensors, so you must use 2 control programs if your Rnet
network has 10 sensors.
•The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on
the Rnet port.
For basic user instructions, see the ZS Sensor User Guide. For detailed installation instructions, see the ZS
Sensors Installation Guide.
SPT sensor overview
The UPC Open is connected to a wall-mounted space temperature sensor to monitor room temperature. Wire SPT
sensors to the UPC Open's Rnet port.
The UPC Open supports the following:
•SPT Standard
•SPT Plus
•SPT Pro
For basic user instructions, see the SPT Sensors Owner Guide. For more detailed instructions, see the Carrier
Sensors Installation Guide.
NOTE If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
10
To wire the ZS or SPT sensor to the UPC Open
1 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)
2 Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE Carrier recommends that you use the following Rnet wiring scheme:
Connect this wire...
To this terminal...
Red
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
Wireless sensor overview
The Carrier wireless sensors, designed for zone control, are low-power wireless devices that use light-harvesting
through solar panels as their primary power source. The wireless line of sensors includes the models shown in the
list below. All are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor-based
temperature sensors that may optionally sense humidity
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
REQUIREMENTS
•A v6.5 or later i-Vu® system
•v6.04-xxx or later controller drivers

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
11
The following is a list of wireless supported devices:
•Standard
•Plus
•Adapter
•Motion/Lux Sensor
•Window/Door Sensor
To configure the control program for the desired user interaction with the sensor, see the Wireless Sensors
Application Guide. For detailed instructions, see the Wireless Sensors Installation Guide.
To install the Wireless Adapter for wireless sensors
WARNING Do not apply line voltage (mains voltage) to the Wireless Adapter.
To wire, power, and mount the Wireless Adapter
NOTES
•The Wireless Adapter requires a 24 Vac or 24 Vdc power supply. It is not powered by the Rnet.
•If the Wireless Adapter will be:
○Daisy-chained on the Rnet with ZS sensors or an Equipment Touch, use the standard 4-conductor Rnet
wiring.
○The only device on the Rnet, you can use a 3-conductor cable instead of the standard 4-conductor Rnet
cable.
1 Turn off the power to the controller that the Wireless Adapter will be wired to.
2 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Inner insul
ation
Outer jacket
Foil shield
.25 in.
(.6 cm)
Shield wire
3 Strip about .25 inch (.6 cm) of the inner insulation from each wire.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
12
4 Wire the Rnet +, Rnet -, and Gnd terminals on the controller's Rnet port to the terminals of the same name on
the Wireless Adapter's Rnet connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
5 Wire the 24 Vac external power supply to the Wireless Adapter's power connector.
6 Mount the Wireless Adapter by inserting 2 screws through the mounting tabs on each end of the Wireless
Adapter.
7 Apply power to the external power supply.
8 Verify that the LED on top of the Wireless Adapter is blinking. See "LED" below.
9 Turn on the controller's power.
LED
The blue LED on the top of the Wireless Adapter indicates the following:
If the LED is...
Then the device...
Off
Is not powered or there is a problem.
Blinking
Is working properly.
Steadily on
Has a problem. Do one of the following:
•Cycle power to the device.
•Insert a small screwdriver or paper clip into the hole next to the LED to reboot the
device.
To wire an Equipment Touch to the UPC Open
NOTE The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
CAUTION Carrier controllers can share a power supply as long as you:
•Maintain the same polarity.
○Use the power supply only for Carrier controllers.

Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
13
If the Equipment Touch will be:
•Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet wiring
and follow the wiring instructions To wire a ZS or SPT sensor to the UPC Open (page 10).
•The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet cable
and follow the instructions below.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
1 Turn off the UPC Open's power.
2 Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
3 Strip about .25 inch (.6 cm) of the inner insulation from each wire.
4 Wire the UPC Open's Rnet+ and Rnet-terminals to the terminals of the same name on the Equipment Touch's
connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
5 Turn on the UPC Open's power.
6 Turn on the Equipment Touch.

Start-up
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
14
Use one of the following interfaces to start up, access information, read sensor values, and test the controller.
This interface...
Provides a...
Field Assistant application -
Runs on a laptop that connects to controller's Local Access port 1
Temporary interface
Equipment Touch device -
Connects to controller's Rnet port 2
Temporary or permanent
interface
i-Vu® application
Available for BACnet systems only
Permanent interface
System Touch device
Available only for BACnet MS/TP systems.
Wire to a BACnet MS/TP network connector and a 24 Vac power supply 3
Temporary or permanent
interface
1Requires a USB Link (Part #USB-L).
2See the Equipment Touch Installation and Setup Guide for detailed instructions.
3See the System Touch Installation and Setup Guide for detailed instructions.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
Select or create a custom control program and graphic for the UPC Open
The field-installed UPC Open does not come from the factory with a control program or graphic. You must load a
control program and graphic as part of the installation/commissioning of the UPC Open. You can select a control
program and graphic from EquipmentBuilder that has all the configurations that are currently available on a
factory-installed UPC Open. You can also create a custom control program using Snap. See Snap Help for details.
NOTES
•You MUST have installed the February 2017 or later cumulative update and the 6.04.xxx or later driver to be
able to create custom control programs, .view files, or .touch files for the ZS sensors, wireless sensors, or
touchscreen.
•Third party mapping information for current Carrier PIC products, whether on a factory-installed UPC Open or
selected from EquipmentBuilder, can be found on the Carrier Control Systems Support Site
http://www.hvacpartners.com/ under Support Center > Controls Support > Controls Product Information.
Start-up

Start-up
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
15
Consider the following before creating your program in Snap:
•Is the equipment already available in EquipmentBuilder?
•Which points from the Carrier equipment are to be mapped in the UPC Open?
•What type of Carrier microblock does each point require?
•Do you need to create custom Property pages for the equipment?
•Are there any special microblocks you may need, such as Communication Device, Schedule, Alarms?
To create your control program in Snap, you must:
•Obtain your CCN points list from the equipment or CCN database.
•Know what points need to be mapped in the control program to the equipment.
•Load a separate control program if Airside Linkage is needed and the UPC Open is used on a rooftop unit. An
Airside Linkage equipment file can be selected in EquipmentBuilder.
After creating your control program, you can create a custom graphic using ViewBuilder. See To install the UPC
Open into an i-Vu® Control System (page 15) to load your control program and graphic into the controller.
To install the UPC Open into an i-Vu® Control System
You must complete the following procedures to successfully install your UPC Open into an i-Vu® Control System.
Use the Help in the referenced software for detailed descriptions of these procedures.
EquipmentBuilder or Snap
1 Use EquipmentBuilder or Snap to create control program(s) for your UPC Open.
2 If applicable, print the Sequence of Operation, which includes the points list.
NOTE You can create a points list under Reports in the i-Vu® application or Field Assistant after installing
your control program.
The i-Vu® or Field Assistant application
1 Upload the controller to the database by selecting the router in the navigation tree.
2 Select Devices > Manage tab.
3 Select the controller in the list on the page.
4 If you are adding a new control program, click . A dialog window appears.
5 Enter a name for your control program in Display Name and select your controller in the Controller drop-down
list.
NOTES
○If you already have the maximum number of control programs for a controller, it will not appear in the
list.
○Optional: You can change the control program's Reference Name if needed.

Start-up
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
16
6 Do one of the following:
If the control program is...
In the Control Program drop-down list
Select the control program.
Not in the Control Program drop-down list
a. Click Add New.
b. Browse to select the control program.
c. Click Open.
d. Click Continue.
e. Click Close.
7 To upload a graphic, click Add New under Views and browse to your .view file.
8 Click Continue. When message appears File added successfully, click Close.
9 Click Close again.
10 Right-click on the programmable controller in the controller list and select Check Status from the list. The
status of the controller should say File Mismatch.
11 Click the Download All Content button.
12 Assign channel numbers to the physical points by selecting the controller in the navigation tree and going to
Properties page > I/O Points tab.
○Enter your channel numbers under Num, using your wire list.
○Enter your expander address under Exp, if applicable.
○Select the appropriate value under Sensor/Actuator Type, if applicable.
13 Configure the controller on the Properties page > Control Program tab.
14 Check out and commission the equipment.
Configure the UPC Open's properties
To start up the UPC Open, set the following properties:
Navigation:
i-Vu® / Field Assistant:
BACview®:
Properties > Control Program > Status
CCN
Point Name/Description
Default/Range
Element Comm Stat - The UPC Open's current status of communication to the CCN
equipment. Click the Element Comm Stat microblock link to change the CCN
equipment target address - bus and element number.
NOTE If more than one UPC Open is connected to a CCN bus for a Multiple Chiller
Application, you must change the CCN controller's address in this object's Summary
tab.
D:
R:
0, 1
Bus: 0.1 - 239
Element: 1 - 239
Other manuals for UPC Open
1
Table of contents
Other Carrier Media Converter manuals