Carrier i-Vu Open Link Installation manual

i
i-
-V
Vu
u
O
Op
pe
en
n
L
Li
in
nk
k
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
a
an
nd
d
S
St
ta
ar
rt
t-
-u
up
p
G
Gu
ui
id
de
e
CARRIER CORPORATION ©2010
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-462-01 · 11/19/2010


i-Vu Open Link i
Table of Contents
Introduction.................................................................................................................................................................. 1
What is the i-Vu Open Link? ................................................................................................................................1
Specifications ........................................................................................................................................................2
Safety considerations...........................................................................................................................................3
Installation ................................................................................................................................................................... 4
To mount the i-Vu Open Link...............................................................................................................................4
To wire for power ..................................................................................................................................................5
Wiring for communications.................................................................................................................................5
Wiring specifications ............................................................................................................................. 6
To connect the i-Vu Open Link to the Ethernet.................................................................................... 6
To wire the MS/TP network on Port S1................................................................................................ 6
To wire Modbus or LonWorks devices on Port S2 ............................................................................... 6
Addressing the i-Vu Open Link............................................................................................................................7
To set the i-Vu Open Link address on the Open network.................................................................... 8
To choose an IP addressing scheme ................................................................................................... 9
To obtain an IP address using DHCP ................................................................................................... 9
To assign a custom IP address............................................................................................................. 9
Configuring BACnet device instance and network number ........................................................................ 12
Driver....................................................................................................................................................13
To set up BACnet Broadcast Management Devices (BBMDs)...............................................15
Configuring i-Vu Open Link Driver Properties ..........................................................................................................18
Device .................................................................................................................................................................. 18
Notification Class #1 ......................................................................................................................................... 18
Calendars ............................................................................................................................................................ 20
Common and Specific Alarms ......................................................................................................................... 20
BACnet router properties.................................................................................................................................. 20
Alarm Store/Forward ........................................................................................................................................ 21
Configuring Router Properties using BACview.............................................................................................. 21
Troubleshooting .........................................................................................................................................................22
LED's .................................................................................................................................................................... 22
Replacing the i-Vu Open Link's battery .......................................................................................................... 23
Serial number..................................................................................................................................................... 24
Compliance ................................................................................................................................................................25
FCC Compliance................................................................................................................................................. 25
CE Compliance ................................................................................................................................................... 25
BACnet Compliance........................................................................................................................................... 25
Appendix A: BACnet Protocol Implementation Conformance Statement ............................................................26


i-Vu Open Link 1
What is the i-Vu Open Link?
The i-Vu Open Link is a BACnet device router that acts as a gateway between the BACnet IP network and a
BACnet MS/TP network. The i-Vu Open Link increases the capacity of an Open system, allowing individual
MS/TP networks (with up to 60 Open controllers each) to be connected via a common BACnet/IP backbone.
The i-Vu Open Link can also integrate third-party equipment, supporting BACnet MS/TP, BACnet/IP, Modbus
RTU, Modbus/IP, and LON FT-10 protocols. The i-Vu Open Link has one EIA-485 port for connecting to the
Open or third-party MS/TP bus, and one jumper-configurable EIA-232/EIA-485 port for connecting to a
Modbus or LonWorks network. It also has one 10/100 Base-T Ethernet port for connecting to the building
LAN and integrating to third-party IP control networks.
Introduction

Introduction
2 i-Vu Open Link
Specifications
Driver drv_ivuopenlink_lon
Maximum number of Open
(MS/TP) controllers
supported
60
Maximum number of control
programs
199
Power 24 Vac ±10%, 50–60 Hz
24 VA power consumption (30 VA with BACview
Third-party integration
points
attached)
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
500
Communication ports
Port E1
•For Ethernet LAN, BACnet IP, and Modbus TCP/IP
communication at 10 or 100 Mbps, half duplex
(10/100 BaseT Ethernet):
•Both
Assigned
(default) and
DHCP
IP addressing are supported
and DIP switch selectable
Port S1
(BACnet MS/TP):
•For communication with Open and third-party controllers via
BACnet MS/TP at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8
kbps (DIP switch selectable). Default is 76.8k bps.
•A
BT485
may need to be installed on
Port S1
if the i-Vu Open
Link is at the beginning or end of a network segment. The
BT485
adds bias and terminates a network segment.
Port S2
(Configurable EIA-485/EIA-232 port for third-party network
connections, including):
•Modbus (RTU) - 9600 bps, 19.2 kbps, 38. 4 kbps
•LonWorks (requires SLTA-10 adapter)
Local Access
(115.2k bps port):
•For i-Vu Open Link configuration using a terminal program
(such as Windows Hyperterminal) via RS-232
•For system start-up and troubleshooting using Carrier tools via
Rnet
Real time clock Battery-backed real-time clock keeps track of time in event of
power failure
Battery 10-year Lithium CR123A battery provides a maximum of 720 hours
data retention during power outages. The battery retains time,
trend data, alarm data, configuration data, and operating
parameters in the event of power failure.To conserve battery life,
battery backup turns off after a specified number of days defined in
the controller driver.

i-Vu Open Link 3
Protection Incoming power and network connections are protected by non-
replaceable internal solid-state polyswitches that reset themselves
when the condition that causes a fault returns to normal. The power
and network connections are also protected against voltage
transient and surge events.
Status indicators LED status indicators for
Port S1
and
S2
communication,
Ethernet
Port E1
Environmental operating
range
communication, and low battery status. Seven segment
status display for running, error, power status, archive valid, and
brownout.
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-
condensing
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-
condensing
Physical Rugged aluminum cover, removable, screw-type terminal blocks
Overall dimensions A:
B:
7-1/2 in. (19.1 cm)
11-3/8 in. (28.9 cm)
Mounting dimensions C:
D:
E:
F:
5 in. (12.7 cm)
10-7/8 in. (27.6 cm)
1-1/4 in. (3.2 cm)
1/4 in. (12.7 cm)
Mount with 6-32 by 1/2 in. mounting screws
Panel depth 2 in. (5.1 cm)
Weight 1.4 lbs (0.64 kg)
Listed by
UL916 (Canadian Std C22.2 No. 205-M1983, CE, FCC Part 15 -
Subpart B - Class A
Safety considerations
Disconnect electrical power to the i-Vu Open Link before wiring it. Failure to follow this warning could cause
electrical shock, personal injury, or damage to the controller.

Installation
4 i-Vu Open Link
To install the i-Vu Open Link:
1 Mount the i-Vu Open Link. (page 4)
2 Wire for power. (page 5)
3 Wire for communications (page 5).
4 Connect the i-Vu Open Link to the Ethernet (page 6).
5 Set the i-Vu Open Link's address and IP address. (page 7)
To mount the i-Vu Open Link
When you handle the i-Vu Open Link:
•Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
•Do not touch components or leads.
•Handle the board by its edges.
•Isolate from high voltage or electrostatic discharge.
•Ensure that you are properly grounded.
Screw the i-Vu Open Link into an enclosed panel using the mounting slots on the cover plate. Leave about 2
in. (5 cm) on each side of the controller for wiring.
Mounting hole dimensions:
•11.25" (27.64cm) width
•1.25" (31.75mm) top edge to center of first hole
•3.75" (63.5mm) top edge to center of second hole
Installation

i-Vu Open Link 5
To wire for power
1 Make sure the i-Vu Open Link’s power switch is in the OFF position to prevent it from powering up before
you can verify the correct voltage.
2 Remove power from the power supply.
3 Pull the screw terminal connector from the controller's power terminals labeled 24V ac/dc and Ground.
4 Connect the transformer wires to the screw terminal connector.
5 Apply power to the power supply.
6 Measure the voltage at the i-Vu Open Link’s power input terminals to verify that the voltage is within the
operating range of 21.6 – 26.4 Vac or 23.4 - 28.6 Vdc.
7 Insert the screw terminal connector into the i-Vu Open Link's power terminals.
8 Turn on the i-Vu Open Link's power.
9 Verify that the Run LED (a dot in the lower right corner of the Module Status LED) begins blinking. The
Module Status LED will display 8 for about 5 seconds and then reverts to 0, until Open controllers have
been discovered and uploaded. There is a chase pattern when the controller is running with no errors.
Wiring for communications
The i-Vu Open Link has multiple ports. See table below for port descriptions.
Port
Protocol
Port
type(s)
Baud rate(s)
Use for
BACnet/IP
Ethernet
Port E1
Ethernet 10 Mbps
100 Mbps
LAN connection
S1
BACnet MS/TP EIA-485
(2-wire)
DIP Switch selectable:
•9600 bps
•19.2 kbps
•38.4 kbps
•76.8 kbps (default)
Open network connection
S2
Modbus
LonWorks
EIA-485
EIA-232
DIP switch selectable Third-party communication
N/A
Local
Access
Rnet 115.2 kbps •Router configuration
•System start-up and
troubleshooting with
Carrier Tools

Installation
6 i-Vu Open Link
Wiring specifications
For...
Use...
Ethernet
Maximum Length
CAT5e or higher Ethernet cable 328 feet (100 meters)
MS/TP 22 or 24 AWG, low-capacitance, twisted,
stranded, shielded copper wire
* 2000 feet (610 meters)
* See the MS/TP Networking and Wiring Installation Guide
.
To connect the i-Vu Open Link to the Ethernet
Connect an Ethernet cable to the Ethernet Port E1.
To wire the MS/TP network on Port S1
1 Turn the i-Vu Open Link's power off.
2 Check the communications wiring for shorts and grounds.
3 Verify that the Port S1 jumpers are set to 485-2w.
4 Set the MS/TP baud rate DIP switches 1and 2to match the baud rate of the Open network. The default
is 76.8k.
5 Connect the i-Vu Open Link's Port S1 to the Open/MS/TP network. Use the same polarity throughout the
network segment.
Wire this
Port S1 terminal
To this Open
controller terminal
Shield (Pin 1)
Shield
Net- (Pin 4)
Net-
Net+ (Pin 5)
Net+
6 Turn the i-Vu Open Link's power on.
To wire Modbus or LonWorks devices on Port S2
1 Turn off the i-Vu Open Link's power.
2 Check the communications wiring for shorts and grounds.
3 Wire the i-Vu Open Link's Port S2 to the third-party device, then set the S2 jumper. See table and notes
below.

i-Vu Open Link 7
4 Turn on the i-Vu Open Link's power.
For...
Use i-Vu Open Link
port...
Wire Carrier
terminal...
...to third-
party device
terminal
EIA-232
Set the port's
jumper(s) on i-Vu
Open Link
S2 TX
Rx
Signal Ground
Rx
Tx
Gnd
EIA-232
EIA-485,
2-wire
S2 Net+
Net-
+
-
EIA-485
2-wire
NOTES
•If you cannot determine the media type or connections of the third-party device, contact your third-party
representative.
•Use the same polarity throughout the network segment.
•Repeaters are required for more than 31 devices. See your third-party device manufacturer's
recommendations.
•To reduce communication and data errors, terminate each end of an EIA-485 network with a resistor
whose value equals the network's characteristic impedance. Some third-party manufacturers provide a
built-in resistor that you enable or disable with a jumper. Make sure that only devices at the end of a
network have termination enabled.
EXAMPLE If an EIA-485 2-wire network's characteristic impedance is 120 Ohms, terminate one pair by
placing a 120 Ohm resistor across the Net+ and NET-connectors of the i-Vu Open Link. Terminate the
other pair by placing a 120 Ohm resistor across the + and -connectors of the furthest third-party
controller.
•A solid receive light on the i-Vu Open Link indicates a wiring or polarity problem.
Addressing the i-Vu Open Link
i-Vu Open Control hardware, when used in conjunction with i-Vu Open routers (i-Vu Open Link and i-Vu Open
Router), has a convenient feature of automatic addressing. To address the i-Vu Open Link for third-party
integration, using i-Vu/Field Assistant, go to Driver Properties > Protocols > Properties tab. Refer to the
appropriate protocol Integration Guide for further details.
The i-Vu Open Link needs two addresses, one for the Open network and one for the IP Network.

Installation
8 i-Vu Open Link
The i-Vu Open Link
needs...
That is unique
on the...
Notes
A router address Open network You set the i-Vu Open Link address on the
controller's rotary switches. (1 - 99)
NOTES
•The i-Vu Open Link address is also used to
auto-generate the BACnet device
instance/name for the router and the
MS/TP network number for the connected
Open network. See Configuring BACnet
device instance and network number.
An IP address IP Network Use the IP Address DIP switch to choose one of
the following:
•Use DHCP to obtain an IP address
•Assign a
custom
The default IP settings are:
IP address (default)
•192.168.168x, where x = router address
•subnet mask = 255.255.255.0
•default gateway = 192.168.168.254
To set the i-Vu Open Link address on the Open network
CAUTION The router address must be unique on the IP and Open network.
1 If wired for power, turn off the controller's power. The controller reads the address each time you turn it
on.
2 Use the rotary switches to set the address. Set the Tens (10's) switch to the tens digit of the address,
and set the Ones (1's) switch to the ones digit. Valid addresses are 1 - 99.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow
on the Ones (1's) switch to 5.
10's 1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
3 Turn on the i-Vu Open Link's power.
NOTE The factory default setting is "00" and must be changed to successfully install your i-Vu Open Link.

i-Vu Open Link 9
To choose an IP addressing scheme
Carefully plan your addressing scheme to avoid duplicating addresses.
•If there is a DHCP server on the network, and, if you have a single i-Vu Open Link or multiple i-Vu Open
Links that exist on the SAME subnet, use DHCP addressing. Skip to the section To obtain an IP address
using DHCP (page 9).
•If you have multiple i-Vu Open Links that reside on different subnets, you cannot use DHCP addressing.
Instead, give each i-Vu Open Link an assigned IP address. Skip to the section To assign a custom IP
address (page 9).
NOTE This network configuration also requires that you configure IP Broadcast Management Devices
(BBMDs. See To set up BACnet Broadcast Management Devices. (page 15)
By default, the i-Vu Open Link is set up for assigned IP addressing. The default IP address settings are as
follows:
•IP address = 192.168.168.x, where x = i-Vu Open Link address (rotary switch settings)
•Subnet Mask = 255.255.255.0
•Default Gateway = 192.168.168.254
To obtain an IP address using DHCP
1 Turn the i-Vu Open Link's power off.
2 Set the IP Addr DIP switch to OFF (DHCP).
3 Turn the i-Vu Open Link's power on. The DHCP server assigns an IP address to the i-Vu Open Link.
To assign a custom IP address
1 Obtain the IP address, subnet mask, and default gateway address for your router from the facility
network administrator.
2 Turn the i-Vu Open Link's power off.
3 Set the i-Vu Open Link's IP Addr DIP switch to ON. (Assigned)
4 Configure the i-Vu Open Link by setting the Router Config Mode DIP switch to (Console):
○ON if you use a terminal program, such as Hyperterminal
○OFF if you use Carrier software, such as BACview
NOTE The DIP switch on older models was labeled Hyperterminal.
5 Turn the i-Vu Open Link's power on.

Installation
10 i-Vu Open Link
Connecting to the i-Vu Open Link
You can connect a PC to the i-Vu Open Link through the Local Access port or through Port S2. See below for
details.
Using Local Access port
PREREQUISITES
•A computer with a USB port
•A USB Link (Part #USB-L)
1 If using the USB Link with your computer for the first time, install the USB Link's driver before you
connect the cable to the computer.
a) Put the USB Link Driver CD into your computer.
b) Run CP210x_VCP_Win2K_XP_S2K3.exe
2 Connect the laptop to the local access port of the controller using the USB Link cable(s).
. Accept all of the wizard's default settings.
73/4 in.
USB Link
Connect to
Local Access port
12 ft
Connect to
USB port
3 Note which COM port has been assigned to the USB Link.
Windows XP or Vista
a) If using Classic desktop, right-click on My Computer and select Manage. If using Standard desktop,
select Start, right-click on My Computer and select Manage
b) In the
.
Computer Management window, select Device Manager and expand Ports (COM & LPT).
4 Ensure that i-Vu Open Link's Router Config Mode DIP switch is ON (Console).
Note
which COM port has been assigned to the ‘CP210x USB to UART Bridge Controller (COMx)’.
NOTES
○The DIP switch on older models was labeled Hyperterminal.
○You must cycle power on the router for DIP switch settings to be accepted.
5 Launch a terminal program, such as Window's Hyperterminal, by browsing to Start > Programs >
Accessories > Communications.
6 Type a name for the local access port in the Name field (example: Access port).
NOTE If you do not see the Name field, select File > New Connection.
7 Select an icon for this connection file, then click OK.
8 Set the Connect using field to COMX in the Connect to dialog box, where X is the number of the
computer's COM port that is connected to the USB Link, then click OK.
9 In the Com Properties dialog box, set the Port Settings for your local access port connection, then click
OK.

i-Vu Open Link 11
10 Click Enter to view the Router Configuration screen. See example below.
11 Type 3to change the IP Address. Click Enter.
12 Type the new IP Address. Click Enter. This IP address will now show up on the Router Configuration
screen.
13 Type 4 to change the Subnet Mask. Click Enter.
14 Type the new Subnet Mask. Click Enter. This Subnet Mask will now show up on the Router Configuration
screen.
15 Type 5to change the Default Gateway. Click Enter.
16 Type in the new Default Gateway. Click Enter. This Default Gateway will now show up on the Router
Configuration screen.
17 After entering your settings, type 1 to reset and click Enter.
18 Verify that you can communicate with the i-Vu Open Link by issuing a PING command to the IP address
specified in step 12.
NOTE Your PC must be on the same subnet as the Router for the PING command to work.
19 When finished, set the i-Vu Open Link's Router Config Mode DIP switch to OFF to restore normal
functionality to the Local Access port.
20 Cycle the i-Vu Open Link's power to accept the Router Config Mode changes.

Installation
12 i-Vu Open Link
Using Port S2
Prerequisite Computer must have a standard serial port.
1 Make sure that the Port S2 jumper is set for EIA-232.
2 Obtain a standard 9-pin serial cable. There are two different ways to connect the serial cable to Port S2:
○Connect an S2-DB9 converter (part# S2-DB9) into Port S2. Plug the 9-pin end of the serial cable
directly into the DB9 connector of the S2-DB9.
○Trim one end of the serial cable to expose the wires to be connected directly to Port S2 of the i-Vu
Open Link.
3 If you are using a trimmed cable, then terminate the TX, RX, and Ground wires of the 9-pin serial cable to
Port S2 on the i-Vu Open Link. See table below.
Serial Cable (9 pin)
Port S2
TX (pin 3) RX (pin 2)
RX (pin 2) TX (pin 1)
Ground (pin 5) Ground (pin 5)
4 Follow steps 4 - 19 above to launch a terminal program and access the Router Configuration screen to
set the IP parameters.
5 Reset the Port S2 jumper to the EIA-485 position.
6 Cycle the i-Vu Open Link's power to accept the DIP switch settings.
Configuring BACnet device instance and network number
All BACnet Open controllers must have a unique device instance and name. These BACnet addresses are
automatically generated and usually do not require modification. However, sometimes you need to override
the automatic addressing assignments.
Autogenerated Addressing Scheme:
The i-Vu Open Link's rotary address setting determines the automatic BACnet addressing scheme for the
connected Open network.
Legend
16 = Carrier's BACnet Vendor ID
xx = Router's rotary address (router address)
yy = Open controller's rotary address (MS/TP MAC address)
For the router:
•BACnet Device Instance Number = 1600xx
•BACnet Device Instance Name = device1600xx

i-Vu Open Link 13
•BACnet IP Network Number = 1600
•BACnet MS/TP Network Number = 161xx
•Port S1 MS/TP MAC Address = 0 (fixed)
For the connected Open controllers:
•BACnet Device Instance Number = 161xxyy
•BACnet Device Instance Name = device161xxyy
•MS/TP MAC Address = yy
•BACnet MS/TP Network Number = 161xx (actually learned from the router, defaults to 16101 if no i-Vu
Open Link is operating)
If the BACnet automatic settings need to be changed, launch the Router Configuration utility using a terminal
program. See To assign a custom IP address (page 9) for instructions on connecting to and using a terminal
program.
To change the BACnet settings:
1 Enter the BACnet selection# from the menu. Type the new setting and click Enter. The new setting will
appear on the Router Configuration screen.
2 Cycle power to the router for the new settings to effect.
NOTE If the BACnet MS/TP network number of the router is assigned and not auto-generated, and the
Open controllers connected to that router are set such that their BACnet settings are auto-generated,
then the Open controller BACnet settings will be auto-generated based on the assigned MS/TP network
number in the Router:
Example A router's BACnet MS/TP network has been assigned to 200.
If the connected Open Controllers are using the auto-generate scheme, then their settings will be:
BACnet MS/TP Network Number = 200
BACnet Device Instance Number = 200xxyy
BACnet Device Instance Name = device200xxyy
MS/TP MAC Address = yy
Driver
On the Driver page, you can change the following properties:
•Backup battery conservation settings. See table below.
•BACview inactivity timeout and user password. See table below.
•Module clock synchronization and failure. See table below.

Installation
14 i-Vu Open Link
Backup Battery
How long backup battery should run after power loss.
Turn off internal backup
battery after ___ days to
conserve battery life (shutoff
date/time)
TIP
Verify the
Downloading memory activates the battery backup. This
conserves battery life when you know the i-Vu Open Link will be
without power for an extended period after downloading (for
example, during shipment):
Archive Valid
After you install the i-Vu Open Link and apply power, enter a
number greater than 0.
LED is lit, then set this field to 0.
BACview Control
Yes
—Every memory download includes
Daylight Saving Time
properties from the
System Options
tab and overwrites changes to
these properties made from BACview.
Overwrite Daylight Saving
parameters set in BACview?
No
—Download
Daylight Saving Time
properties during first
download. You must make subsequent changes from BACview.
End the user session, turn off the backlight, and display the
standby screen after this period of inactivity.
Keypad inactivity timeout
(minutes)
Numeric password user must enter to access system through
BACview.
Keypad user-level password
Module Clock
Date and time control program uses when controller's real-time
clock is invalid.
Clock Fail Date and Time
TIP
Use an occupied date and time (such as a Tuesday at 10
a.m.) so the equipment does not operate in unoccupied mode if
the controller loses power during occupancy.
On a Time Synch signal, update the controller clock only if the
controller time differs from the signal time by more than this
value.
Time Synch Sensitivity
(seconds)
BACnet COV Throttling
Under normal circumstances, COV Throttling should be enabled to
prevent excessive network traffic if an object's COV Increment is
set too low. See EXCEPTION below.
Enable COV Throttling
When enabled, if an object generates excessive COV broadcasts
(5 updates in 3 seconds), the module driver automatically throttles
the broadcasts to 1 per second. Also, if the object's value updates
excessively for 30 seconds, an alarm is sent to i-Vu/Field Assistant
listing all objects that are updating excessively. A Return-to-normal
alarm is sent only after all objects have stopped updating
excessively.
EXCEPTION
In rare circumstances, such as process control, a
subscribing object may require COV updates more frequently than
once per second. For these situations, clear this checkbox, but
make sure that your network can support the increased traffic.
You also need to disable the
Excessive COV
alarms under the
driver's
Common Alarms
.

i-Vu Open Link 15
To set up BACnet Broadcast Management Devices (BBMDs)
If your system has multiple routers that reside on different IP subnets, you must set up one router on each IP
subnet as a BACnet/IP Broadcast Management Device (BBMD).
Every subnet with a router must have a BBMD configured in order for broadcasts from controllers on that
subnet to reach the rest of the routers on the network.
NOTE If the i-Vu appliance is on a separate subnet than the rest of the routers, the internal router must be
assigned an IP address and configured as a BBMD.
Use the BBMD Configuration Tool to:
•Define the Broadcast Distribution Table (BDT) in each BBMD
•Enable an i-Vu Open Control System to find routers that are on different subnets
•Allow controllers on one subnet to communicate with controllers on other subnets
•Enable i-Vu to see, upload, or configure controllers on different subnets
NOTE In this document, the term "router" refers to the i-Vu Open Router or the i-Vu Open Link.
1 Assign an IP address, subnet mask, and default gateway for each i-Vu Open Link on the IP network. See
Addressing the i-Vu Open Link (page
To set up BBMDs using the BBMD Configuration Tool
7).
2 Acquire the BBMD Configuration Tool from the Tech Tools DVD or from the Carrier Control Systems
Support Site http://www.hvacpartners.com/. This is a stand-alone executable file and no installation is
necessary.
3 Make a list of the IP addresses for each router that will function as a BBMD in your system.
In the above illustration, the i-Vu Open Link, address 172.18.1.2, must be configured as a BBMD for the
172.18 subnet, while the i-Vu Open Link, address 172.16.1.15, must be configured as a BBMD for the
172.16 subnet.

Installation
16 i-Vu Open Link
CAUTIONS
○Multiple BBMD's on an IP subnet disrupt BACnet communications. Define only one BBMD per
subnet.
○Unless explicitly modified, the UDP Port for BACnet/IP is 0xBAC0 (47808). Do not change this
parameter unless you made a change in the router.
4 In a text editor such as Notepad, create a list of the routers that will be BBMD's. List each IP address on
a separate line. (Maximum of 50 IP addresses per file)
5 Save the file to your folder of choice with a .bdt extension instead of .txt.
NOTE ".bdt" is a Broadcast Distribution Table file.
6 Open the BBMD Configuration Tool.
7 In the IP Address or Host Name field, type the IP address of the router that functions as the BBMD
(BACnet Broadcast Management Device) for its subnet.
8 To check if the router has an existing BBMD table, click Broadcast Distribution Table Read button.
9 If the Broadcast Distribution Table contains IP addresses that are not in your .bdt file, verify that they are
valid BBMD's and, if so, add them to your .bdt file.
NOTES
○The BDT's in each BBMD must be identical. Be sure to repeat this entire process whenever a BBMD
is added.
○If needed, disable the checkbox next to Show Broadcast to limit the amount of scrolling text that is
displayed.
10 Click the Broadcast Distribution Table Browse button and select the .bdt file that you made in step 4.
11 Verify that the appropriate IP address is still in the IP Address or Host Name field.
12 Click the Broadcast Distribution Table Write button.
13 Click Read again to verify that the new .bdt file was written to the router. See example below.
Other manuals for i-Vu Open Link
1
Table of contents
Other Carrier Network Router manuals