Cartell CF-2C User manual

CF-2C/CF-3C
CONTROL UNIT ONLY
(Sound & Lights)
INSTALLATION/OPERATION MANUAL
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

Introduction.................................................................................. 3
Serial Number.............................................................................. 3
Location of Control Unit............................................................... 3
Floodlight Relay Wires................................................................. 3
Installing Control Unit .................................................................. 3
Power and Battery Backup .......................................................... 4
Earth Ground ............................................................................... 4
Trip-Test Button .......................................................................... 5
Extra Set of Relay Contacts ........................................................ 5
Hooking to a Security or Home Automation Panel ...................... 5
Using Probe Fault Mode for Testing............................................ 5
Adjusting CT-A1 (formerly FC-9( Exit Delay................................ 6
Adjusting Sounder (Annunciator) Time........................................ 6
Adjusting Re-Trigger Hold-Off ..................................................... 6
Adjusting Floodlight Entry Delay Time......................................... 6
Adjusting Floodlight Time ............................................................ 7
Adjusting Photocell Sensitivity..................................................... 7
Adjusting Probe Sensitivity.......................................................... 7
Adjusting Transient Suppressor .................................................. 7
Field Troubleshooting.................................................................. 7
Warranty Information .................................................. Back Cover
Merchandise Return Information ................................ Back Cover
Technical Specifications............................................. Back Cover
TABLE OF CONTENTS
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

INTRODUCTION
Congratulations on purchasing the most professional vehicle detection system available! It has
been manufactured to give years of trouble-free service. However, if it should need servicing,
please consult the dealer who installed your system.
Read these instructions completely. Each system should be bench-tested by the dealer before installation.
The installer should become acquainted with the CF-2C control unit and sensor probe in the shop; make all
adjustments and settings; and study all system functions. If there are any questions or problems that need to
be discussed, contact the technical staff by calling our 800 number.
SPECIAL NOTE: In this edition, look for new information gleaned from fielding technical calls for over fifteen
years. It is contained under the heading “Special Note” throughout this manual.
SERIAL NUMBER:
Attached to the relay on the circuit board is a sticker with a set of numbers
and letters. This series of numbers and letters reveals the specific unit, its
year of manufacture, its issue number and ends with the serial number (see
illustration).
When calling Preferred for technical help, please have these numbers handy so that your call may be
handled in a timely manner.
LOCATION OF CONTROL UNIT
Install the control unit in a dry, weatherproof building away from heavy electrical motors, radio transmitters,
main power service, or any equipment that may introduce electrical or R. F. noise. Install control unit in a
sealed box when used in a corrosive atmosphere such as an animal barn or chemical plant.
Install in a sealed, weather-proof box when installed outside. The weatherproof box must have a
thermostatically controlled light bulb or heater to maintain temperatures above freezing. Drastic changes in
temperature cause condensation on the board and will make the unit malfunction.
FLOODLIGHT RELAY WIRES
On the CF-2C circuit board is a floodlight relay (normally open, dry contacts) rated 15 amps at 115 VAC.
Two 12 gauge, black wires connected to this relay exit out the back of the CF-2C case. This floodlight relay
can be used to operate three types of systems:
1. The relay can be used to operate up to 1800 watts directly (see Figures 1A, 1B, and 1C and “Installing
Control Unit” below).
2. The relay can be used to operate the coil of an auxiliary relay or contactor to power banks of lights (see
“Installing Control Unit” below).
3. The relay can be used to activate low voltage lighting up to 15 amps maximum or trigger a line carrier
system such as X10 Powerhouse Interface Module or equivalent.
INSTALLING CONTROL UNIT
See Figure 1, top of next page. Install a single-gang electrical box in the wall behind the control unit so that
the black wires from the unit go directly into the electrical box.
With the power to the floodlight switching system off, run a 14-gauge, two-wire Romex cable from the new
single-gang electrical box to the existing floodlight switching system as shown in Figure 1A.
Connect the Romex cable across the switch of a single-switch system as shown in Figure 1B.
Connect the Romex cable across the "A" and "B" screw terminals of any switch in a multiple-switch system
CF-2C CONTROL UNIT MANUAL
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

as shown in Figure 1C.
Connect the black leads from the control unit to the two wires of the Romex cable with wire nuts as shown in
Figure 1A.
Mount the control unit to the wall over the electrical box as shown.
POWER AND BATTERY BACKUP
See Figure 2. The control unit operates on 12 VAC or 12 VDC. Hook up the 12 VAC transformer between
terminals No. 1 and 2 as shown in Figure 2 (NOTE: Do not connect a DC power source to terminals 1 and 2).
A built-in battery charger will keep a 12 volt sealed lead-acid battery (not included) charged for operating the
Sonalerts during power failure. NOTE: The battery back-up is not needed for normal operation of the
CF-2C control. If you choose to purchase a battery, only a sealed lead acid (starved, wet-cell) battery should
be used. DO NOT use a gelled-electrolyte battery. Recommended batteries are made by Yuasa Battery, Inc.;
Gates Energy Products, Inc.; Eagle Picher Industries, Inc.; Panasonic Industries, Co.; or G.S. Battery, Inc.
The positive (RED) lead connected to terminal No. 4 and the negative (BLACK) lead connected to terminal
No. 5 are provided for connections to the battery. When an outside DC power source is being used, connect
to these terminals in place of a battery.
Special note: During initial power-up or power-down and power-up sequence, the “Exit Delay” timer is
automatically activated. Be patient, for the CF-2C control cannot be accessed until the “Exit Delay”
timer times out. It is recommended that when the control unit is first installed that the “Exit Delay”
adjustment (potentiometer “C”) be set at minimum (fully counter-clockwise) until the system is
operational. (See “Adjusting FC-9 Exit Delay” on page 6.)
EARTH-GROUND
See Figure 2. A proper earth-ground is essential. A proper earth-ground is established by using an 8 foot
copper or copper-clad ground rod driven deeply into the earth.
Figure 2
CF-2C HOOK-UP SINGLE SWITCH MULTIPLE SWITCH
Figure 1A Figure 1B Figure 1C
Figure 1
Back to Table of Contents
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

Use a ground wire of at least 12 gauge. Solder wire to ground rod and then clamp it. Tin the other end of
the ground wire and connect it to terminal No. 3 on the control unit.
Special Note: A galvanized ground rod will not give a proper ground for this system.
TRIP-TEST BUTTON
The trip-test button, located center right on the circuit board, is a tool to evaluate most of the control
electronics and to help in setting the relay time. To test the control unit, a working probe must be attached to
terminals No. 17, 18, and 19 (see Figure 2, page 4). If the probe is disabled or not connected, simply connect
a 500 to 1000 ohm resistor between the probe terminals No. 17 and 19. NOTE: The TRIP TEST button will
not work if the PROBE FAULT LED is lit (this indicates a disabled probe).
Set the probe sensitivity potentiometer "G" to the halfway point, i.e., vertically up and down (see Figure 5, p.
6). Push the TRIP-TEST button on and off quickly. DO NOT hold the button on. The signal generated
simulates that of a detected vehicle. No response indicates component failure on the circuit board or failure of
the power supply. It may be that the EXIT DELAY timer has not timed out as well (the EXIT DELAY time may
have been preset anywhere between 50 seconds and 15 minutes (see “Adjusting FC-9 Exit Delay,” p. 6).
EXTRA SET OF RELAY CONTACTS
The annunciator relay has a second set of Form “C” relay contacts on terminals No. 11, 12, and 13. These
contacts may be used to trip an alarm panel, trip a dialer, trip a line carrier interface module such as “X-10”,
trigger a transmitter or trip a door bell. Potentiometer “F” controls the relay time of these contacts.
HOOKING TO ASECURITY OR HOME AUTOMATION PANEL
See Figure 2 on page 2.
The CF-2C has a floating, dry relay contact that can be used in conjunction with any security or home
automation (H. A.) system.
Two things will help you to have a successful installation:
1. The manual for your home automation or security panel
2. A resistor, if required (security or H.A. system manual will tell you if a resistor is required)
Note: Use the power supply that came with the CF-2C to power it rather than relying on the H.A. or security
panel for power.
Hook the CF-2C to two zone inputs on your security or H.A panel. If your system’s contacts are normally
closed, use terminals 11 & 12 on the CF-2C. At your system’s panel, place a resistor (if required) between the
terminals in parallel (see system manual for correct resistor size).
If your security or H.A. contacts are normally open, use terminals 12 & 13 on the CF-2C and place a resistor
(if required) between the terminals in series (see system manual for correct resistor size).
USING PROBE FAULT MODE FOR TESTING
With power applied and the probe wires disconnected, if the LED does not light, there may be power supply
failure. If the LED does light but does not cycle the annunciator(s), the cause may be related to one of three
things:
1. The exit delay timer has not timed out yet (see “Adjusting FC-9 Exit Delay on page 6.)
2. Wiring problems going to terminal No. 9
3. Component failure on the circuit board
Other uses in PROBE FAULT mode:
The cycling of the sounders can be used to set annunciator duration (see page 6), re-trigger hold-off time
(see page 6), and the FC-9 exit delay time (see page 6 ). It may also be used to check all of the sounders
without the need for a vehicle tripping the system.
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

MAKING ADJUSTMENTS
ADJUSTING CT-A1 (FORMERLY FC-9) EXIT DELAY
See Figure 5. The exit-delay time (potentiometer “C”) can be adjusted from 50 seconds to 15 minutes. To
determine the exit delay time, first remove the RED probe wire from terminal No. 17. This will put the CF-2C
into PROBE FAULT mode (see page 6). When the exit delay timer times out the annunciator relay will
constantly cycle on and off.
To activate the exit delay timer on an installed FC-9 annunciator, press the exit delay button on the
annunciator plate. If other devices are being used to activate the exit delay timer (such as an alarm panel,
etc.), take a wire and short the terminals between No. 9 and No. 15 at the CF-2C control panel. Doing this for
2 seconds will trigger the timer. When the timer is activated, the annunciator relay will stop cycling.
Measure the time from when the relay stops and when the relay begins cycling again and you will know the
exit delay time. For longer exit delay time, adjust the potentiometer marked “C” clockwise and repeat until the
desired time is achieved. Re-attach the RED probe wire to terminal No. 17 when finished.
ADJUSTING ANNUNCIATOR TIME
See Figure 5. This function controls the amount of time the customer desires the noisemaker to stay on. It
may be adjusted to stay on anywhere from 1/2 to 30 seconds. To adjust, use the potentiometer marked "F".
Turning it clockwise increases the time. Push the trip-test switch to hear your adjustment. Adjust until the
desired time is achieved.
ADJUSTING RE-TRIGGER HOLD-OFF
See Figure 5. The re-trigger hold-off keeps the system from re-triggering (and thus annunciating) should
multiple cars pass the probe in a caravan. Once the system is tripped, it will time-out but not be able to re-
trigger for an adjustable time period up to 2½ minutes. To adjust this time period, disconnect the RED probe
wire from terminal No. 17 (this puts the control unit in PROBE FAULT mode, see page 5).
The annunciator relay will constantly cycle on and off. To increase the re-trigger hold-off, adjust
potentiometer marked "E". Turn it clockwise for a longer hold-off period of time. Repeat until the desired hold-
off time is achieved. Re-attach the RED probe wire.
ADJUSTING FLOODLIGHT ENTRY DELAY TIME
See Figure 5. This function can be used to delay activation of the floodlight timer after the CF-2C is tripped.
Adjustment time is from 1 second up to 2½ minutes. For long driveways, or if the exact location of the probe
is to be concealed for security reasons, use this feature. The annunciator, however, is not delayed.
To set the desired floodlight entry delay timer, first remove the photocell lead from terminal No. 7 (see
Figure 2 on page 4) on the CF-2C control unit. Push the TRIP TEST button and measure from the moment
the annunciator relay clicks on (a relatively quick click) and the moment the floodlight relay activates (a
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Figure 5
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

relatively loud click).
To increase the delay time, adjust the potentiometer marked “A” clockwise. After the floodlight relay times
out, repeat the cycle until the desired time is achieved. Re-connect the photocell wire to terminal No. 7.
special note: Do not use the MANUAL-ON button on the FC-9 annunciator plate to set the entry delay
time. On the CF-2C (Issue 5), the MANUAL-ON button on the FC-9 instantly activates the floodlight
timer, bypassing the entry delay timer circuit.
ADJUSTING FLOODLIGHT TIME
See Figure 5. The amount of time the floodlights remain on after the system is tripped may be adjusted from
15 seconds to 15 minutes. The normal floodlight time is 5-10 minutes.
To set the floodlight time, remove the photocell wire from terminal No. 7. Push the TRIP-TEST button.
Measure from the moment the floodlight relay clicks on to the moment it clicks off. Adjust potentiometer
"B" (clockwise for time increase) and repeat until desired time is achieved. Reconnect the photocell wire to
terminal No. 7.
ADJUSTING PHOTOCELL SENSITIVITY
See Figure 5. Photocell sensitivity determines the level of outdoor light at which the lights are allowed to
come on. The factory sets the floodlights to come on at dusk.
To set the photocell sensitivity, make all adjustments at the precise moment when the amount of daylight is
visible at which time you want the floodlights to come on. Adjust potentiometer "D" counter clockwise in very
small increments and push the TRIP-TEST button after each adjustment (see page 5). Stop adjusting at the
point where the floodlight relay clicks on. The floodlights will be allowed to turn on at that same daylight level
from then on.
ADJUSTING PROBE SENSITIVITY
See Figure 5. Probe sensitivity is set at the factory and does not usually need to be adjusted. Factory setting
allows a single standard probe to cover a 12 foot wide driveway when installed beside it). Increasing the
sensitivity above the factory setting is not recommended unless the probe is located in a low sensitivity area.
When the probe is placed in the center of a driveway that is 18 feet wide or less, the sensitivity may be
decreased considerably, allowing the probe to be installed close to highway traffic, power lines, etc.
To adjust probe sensitivity, turn the potentiometer "G" clockwise to increase, counter-clockwise to decrease.
A typical setting should be such that the CF-2C reliably detects a small car going 5 MPH. You may increase
sensitivity if necessary. Be aware, increasing sensitivity may cause false alarms.
ADJUSTING TRANSIENT SUPPRESSOR
See Figure 5. The factory setting for the transient suppressor circuit potentiometer "H" is in the "on" position
(fully clockwise). In this setting, short duration transient signals will be ignored. With the circuit activated, false
alarms from lightning will be reduced.
Note: if the probe sensitivity cannot be properly set as described in the "Adjusting Probe Sensitivity" section
above, turn off the transient suppressor by adjusting potentiometer "H" full counter-clockwise.
FIELD TROUBLESHOOTING
Preferred does not provide schematic diagrams or service manuals for our products. However, we try our
best to provide technical support through our 800 number and fast repair service for our products.
Before calling Preferred, refer to the “Special Note” sections under the following headings:
Initial power-up and exit delay, page 4; Purchasing ground rod, page 5; Using Probe Fault Mode to
test circuit board, page 5; Entry delay time, p. 7.
When trouble-shooting a CF-2C system that is false alarming, check the ground system. House electrical
panel grounds can cause transient feedback that could cause false alarms.
To determine if false alarms are board related or probe system related, disconnect the probe and connect a
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]

500 to 1000 ohm resistor across terminals 17 and 19 and leave it connected for a long period of time. If the
board false alarms, it is circuit board related or ground system related. If it does not false alarm with the
resistor installed, then the probe system is suspect.
NOTE: when trouble-shooting the CF-2C, an active cell phone within five feet of the control unit will false
alarm the system.
If either the probe or control unit fails the test, call Preferred's technical staff using the 800 number. Further
instructions will be given or authorization to return the ostensibly defective product for testing and repair. If the
probe is bad there is no way of repairing it. It is recommended that all repairs be returned directly to Preferred
and not be sent through a distributor.
LIMITED FIVE YEAR WARRANTY
All CARTELL products are warranted against defects in material and workmanship for five years. This
warranty does not cover defects caused by, but not limited to: acts of God, improper installation, abuse, fire
and water damage, electrical surges, and damage to cable caused by slicing, pulling, tangling, or improper
splicing. For more information, visit www.cartell.com.
MERCHANDISE RETURN INFORMATION
Before returning products for repair, please call Preferred Technologies Group at (800) 223-4743 for a
Return Merchandise Authorization (R.M.A.) number. Write the R.M.A. number on the return shipping box and
any correspondence included with the defective product.
TECHNICAL SPECIFICATIONS - CONTROL UNIT Back to Table of Contents
POWER REQUIRED: 12 VAC or 12-15 VDC
STANDBY CURRENT: 35 mA
ALARM CURRENT: 180 mA max. with (1) FC-9 or (1) CT-8
ANNUNCIATOR RELAY
CONTACT RATING:
Double Pole, Double Throw
1st Pole: 12 VDC, 200 mA for remotes
2nd Pole: SPDT, 5 amps, 30 VDC
RELAY TIME: 1/2 to 30 seconds
FLOODLIGHT CONTACT SPST, 15 amp, 125 VAC CSA certified (1800 watts)
FLOODLIGHT TIME 15 seconds to 15 minutes
BATTERY CHARGER 13.5 VDC, 5 mA minimum charge (w/ voltage off)
TEMPERATURE RANGE: 35oF. to 140oF.
DIMENSIONS: 7 1/2 in. x 12 3/4 in. x 3 in.
WEIGHT: 5 lbs.
FLOODLIGHT DELAY 1 second to 2 1/2 minutes
Back to Table of Contents
Back to Table of Contents
www.GateOpenerSafety.com | (800) 878-7829 | [email protected]
This manual suits for next models
1
Table of contents
Other Cartell Control Unit manuals
Popular Control Unit manuals by other brands

WAGO
WAGO WAGO-I/O-SYSTEM 750 750-481/003-000 manual

THORLABS
THORLABS SPCM A Series quick start

Delabie
Delabie NT 760 manual

Dakota Digital
Dakota Digital BIM-01-2-FTCH manual

Cameron
Cameron WKM MA Installation, operation and maintenance manual

Microtips Technology
Microtips Technology DEPG0750RWU790F30 user manual