manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CBM
  6. •
  7. UPS
  8. •
  9. CBM 250 User manual

CBM 250 User manual

C B M _ O T Q G _ B U 3 _ 2 0 1 1 0 8 0 9 V 0 2
Page 1
Back-UPS (VA):
Back-UPS PRO (VA): 250, 280, 300, 400, 420, 450, 500, 600, 650
650, 1000, 1100, 1400
Figure 1
Figure 2
Connect the UPS’s Internal batteries (Figure 1):
NOTE: Battery Disconnect/Connector may vary or be
omitted on some models. Figure 1 illustrates some of the
variations in connectors. Please follow the illustration
which best resembles your UPS.
Procedure for Figure 1: (1, 2)
1.1 Remove the two screws holding the battery door.
1.2 Lay the UPS on its side and open the door
1.3 Gently pull the battery out.
1.4 Connect the two wires to the battery
NOTE: Make sure to observe the polarity (Red-to-Red, Black-to-Black)
NOTE: Small sparks at the battery connections are normal.
1.5 Insert the battery in the UPS. Carefully avoid pinching the wires.
1.6 Close the battery compartment door and replace the screws.
OR
Procedure for Figure 1: (A)
1.1 Locate the ‘Battery Disconnect’ on the rear panel of the UPS. It is typically
a Yellow connector.
1.2 If the Battery Disconnect has a metal cover, remove the fastening screws
and move the cover
1.3 Press the yellow connector into the Battery Jack. A snap will be felt as the
connector partially engages the jack. A second snap will be felt as the
connector securely seats in the Battery Jack.
Connect wiring & charge UPS (Figure 2):
NOTE: Ensure equipment is turned off.
2.1 Connect equipment to UPS
2.2 Connect UPS Power Cord to a suitable power receptacle
2.3 Reset the UPS Circuit Breaker by pushing-in the button
(Circuit breakers may differ on some models)
2.4 Power-up the UPS by pressing the button or
Switch.
2.5 Wait for the Self-Test to complete, then Power-up equipment.
2.6 Allow UPS to charge batteries for 24 hours prior to operating
on battery or performing additional Self-Test or Calibration
tests.
STEP
1
:
1
2
STEP
2
:
A
1
2
A
OR
1
2
3
1
2
3
1
C B M _ O T Q G _ B U 3 _ 2 0 1 1 0 8 0 9 V 0 2
Page 2
UPS Front Panel (Figure 3):
NOTE: Symbols & functions may differ on some UPS models.
Figure 4 illustrates some of the variations in displays.
Please use the illustration which best resembles your UPS.
Figure 3
POWER ‘ON/OFF’ &/OR TEST BUTTON -
Button to turn UPS on or off, or perform a self-test.
ONLINE - UPS is supplying utility power to the
connected equipment. If not lit, the UPS is not turned
ON, or is supplying battery power.
POWER ‘ON/OFF’ SWITCH - Switch
to turn UPS
on or off. The switch will illuminate when power is
present on the output receptacles.
ON BATTERY - UPS is supplying battery backup
power to the connected equipment. UPS will beep four
times every 30 seconds.
OVERLOAD - The power demand from the load has
exceeded the capacity of the UPS. A sustained alarm
tone is also emitted.
TEST SWITCH - When operating on Utility
power, the top part of the switch will cause the UPS
to simulate a power outage.
ALARM DISABLE SWITCH - When operating
on battery, the bottom part of the switch will disable
the audible tone.
REPLACE BATTERY - UPS fails a self-test, or
battery is bad. UPS makes short beeps for a minute.
BATTERY DISCONNECTED - Flashes to indicate
the battery is disconnected. UPS will beep every two
seconds.
UPS Outlets (Figure 4):
NOTE: Panel Layout may differ
depending on model.
DB9 Serial Port
Site wiring fault Indicator
Modem/Phone/FAX/Network
surge protection
Circuit breaker/Overload
protection
UPS input
Outlets
Battery Disconnect
Option Switches
Figure 4
Option Switch configuration (Figure 4, reference #8):
NOTE: Option switch may not be included on some models. ‘Shutdown Settings’ function is only available on 500 & 650 VA models.
UTILITY TRANSFER VOLTAGE
Position:
Result:
(NORMAL SETTING) 103V AC
98V AC
93V AC
88V AC
AUDIO SETTING
Position:
Result:
(NORMAL SETTING) AUDIO is enabled.
AUDIO is disabled.
SHUTDOWN SETTINGS
Position:
Result:
(NORMAL SETTING) 2 min. prior toshutdown, UPS will
sound a tone & activate low battery signal on COM port.
Same actions as “NORMAL SETTING”, but delay is
increased to 5 minutes instead of 2 minutes.
1
4
2
5
6
3
7
1
2
3
4
5
6
7
8
2
2
3
1
4
5
6
7
1
5
4
3
2
7
6
4
1
2
3
6
5
8
C B M _ O T Q G _ B U 3 _ 2 0 1 1 0 8 0 9 V 0 2
Page 3
UPS troubleshooting:
NOTE: Troubleshooting procedures may differ depending on UPS model.
Back-UPS troubleshooting
UPS will not turn on
(lamp within power I/O switch is not illuminated), but beeps when power I/O switch
is on
Line cord plug is loose. Check fitting of line cord plug.
Rear panel circuit breaker is tripped. Circuit breaker is tripped when button is extended. Unplug excessive loads
and reset breaker (press button).
Dead wall socket. Check wall socket with a table lamp.
UPS
operates normally, but I/O switch not illuminated)
Lamp inside the I/O switch is blown. You may continue to usethe UPS. It is recommended that the UPS is
serviced.
The UPS operates normally, but the site wiring fault indicator is lit
Building wiring error such as missing ground, hot and neutral polarity
reversal, or overloaded neutral wiring.
A qualified electrician should be summoned to correct the building wiring.
The UPS will not provide rated noise and surge suppression with incorrect
building wiring.
"Cheater" plug or adapter installed onto line cord plug (ground not
connected). Plug the UPS into 2 pole, 3 wire grounding outlet only.
UPS
occasionally emits
a
beep, compu
ter equipment operates normally
The UPS is briefly transferring your equipment to its alternate power
source due to utility voltage sags or spikes.
This operation is normal. The UPS is protecting your computer equipment
from abnormal utility voltages. If the audible alarm becomes annoying, refer
to Option Switch ‘AUDIO SETTING’ section to mute the beeping sound.
UPS
emits
a
beep very often, more
than once or twice and hour. Compu
ter equipment operates normally
Utility voltage is distorted or branch circuits are heavily loaded.
Have your line voltage checked by an electrician. Operating your UPS from
an outlet which is wired to a different branch fuse or circuit breaker may
help. Refer to Option Switch ‘UTILITY TRANSFER VOLTAGE’ section and
lower the transfer voltage if it is known that your equipment will operate
normally at that voltage.
UPS emits loud tone. Power I/O switch is on but computer equipment is not powered.
UPS’s rear panel circuit breaker is tripped (button is extended). Normal utility voltages are known to be present
UPS has shut down due to severe overload. Turn off UPS and unplug excessive loads. Laser printers will overload the
UPS and should be plugged into a quality surge suppressor. Once overload
is removed, reset the circuit breaker (press the button).
Problem:
Solution
:
C B M _ O T Q G _ B U 3 _ 2 0 1 1 0 8 0 9 V 0 2
Page 4
UPS troubleshooting:
NOTE: Troubleshooting procedures may differ depending on UPS model.
Back-UPS PRO troubleshooting
UPS will not turn on
On/off/test button not pushed. Press the on/off/test button to power the UPS and the loads.
UPS input circuit breaker tripped. Reduce the load on the UPS by unplugging equipment and reset the circuit
breaker by pressing the plunger back in.
UPS
will not turn
on or off
Computer interface problem. Disconnect the computer interface. If the UPS now works normally, check
the interface cable and troubleshoot the attached computer.
UPS
operates
on
-
battery even though l
ine voltage is thought to exist
UPS’s input circuit breaker tripped. Reduce the load on the UPS by unplugging equipment and reset the circuit
breaker by pushing the plunger back in.
UPS
beeps occasionally
Normal UPS operation. None. The UPS is protecting the load.
UPS
does no
t provide expected back up time
The UPS’s battery is weak due to recent outage or it is near the end of
its service life.
Charge the battery. The UPS’s batteries require recharging after an
extended outage. Batteries age faster when put into service often and when
operated at elevated temperatures. If the battery is near the end of its
service life, consider replacing the battery even if the replace battery
indicator is not yet lit.
On
-
line and overload indicators are flashing al
ternately
The UPS was shutdown by PowerChute® plus software. None. The UPS will restart automatically when utility power returns.
All indicators are flashing
OR
only the On
-
line and on
-
battery indicators are flashing
Internal UPS fault. Donot attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
The UPS operates normally, but the sit
e wiring fault indicator is lit
Building wiring error such as missing ground, hot and neutral polarity
reversal, or overloaded neutral wiring.
A qualified electrician should be summoned to correct the building wiring.
The UPS will not provide rated noise and surge suppression with incorrect
building wiring.
All indicators are off and the UPS is not operating
The UPS is shutdown and the battery is discharged from an extended
power outage. None. The UPS will return to normal operation when the power is
restored and the battery has a sufficient charge.
The replace battery light is illuminated
Weak batteries. Allow the batteries to rechargefor at least 4 hours. If the problem persists
after recharging, replace the batteries.
Batteries Disconnect or internal battery lugs not connected properly. Confirm the battery connections and battery Disconnect are firmly installed.
The overload light is illuminated or flashing
The UPS is overloaded. Reduce the load on the UPS by unplugging equipment.
For the complete User Manual or comprehensive troubleshooting, please visit the following websites:
APC: http://www.apc.com or CBM: http://www.buyupsonline.com
Problem:
Solution
:

This manual suits for next models

12

Popular UPS manuals by other brands

Eaton Power Xpert 9395P-1100/1100 Installation and operation manual

Eaton

Eaton Power Xpert 9395P-1100/1100 Installation and operation manual

alchemy Pi-UpTime UPS 2.0 manual

alchemy

alchemy Pi-UpTime UPS 2.0 manual

Tecnoware EASY Power 900 user manual

Tecnoware

Tecnoware EASY Power 900 user manual

Powerware 9125 user guide

Powerware

Powerware 9125 user guide

CyberPower 649532016006 Specification sheet

CyberPower

CyberPower 649532016006 Specification sheet

Eaton 93PM IBC-L installation manual

Eaton

Eaton 93PM IBC-L installation manual

MAKELSAN Challenger Series user manual

MAKELSAN

MAKELSAN Challenger Series user manual

Nilox Value 840 user manual

Nilox

Nilox Value 840 user manual

Huawei UPS2000-A Series user manual

Huawei

Huawei UPS2000-A Series user manual

Njoy Alvis Series user manual

Njoy

Njoy Alvis Series user manual

Liebert Series 600 Operation & maintenance manual

Liebert

Liebert Series 600 Operation & maintenance manual

Minuteman Enspire Series user manual

Minuteman

Minuteman Enspire Series user manual

Smartbitt SBOL50KTIII-3 Service manual

Smartbitt

Smartbitt SBOL50KTIII-3 Service manual

Energizer ER-PRO1000 Specifications

Energizer

Energizer ER-PRO1000 Specifications

INFOSEC 5000 VA user guide

INFOSEC

INFOSEC 5000 VA user guide

Orvaldi 600 LCD user manual

Orvaldi

Orvaldi 600 LCD user manual

MGE UPS Systems EXL 1000 installation manual

MGE UPS Systems

MGE UPS Systems EXL 1000 installation manual

Maranello DAYTONA 600 user manual

Maranello

Maranello DAYTONA 600 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.