Ceiec Electric PMC-1302 ESG User manual

PMC-1302 ESG
Ethernet Serial Gateway
User Manual
Version: V1.0A
06/21/2012
Ceiec Electric Technology

2
Ceiec Electric Technology
This manual may not be reproduced in whole or in part by any means without the express
written permission from Ceiec Electric Technology (CET).
The information contained in this Manual is believed to be accurate at the time of
publication; however, CET assumes no responsibility for any errors which may appear here
and reserves the right to make changes without notice. Please consult CET or your local
representative for latest product specifications.

3
Ceiec Electric Technology
Limited warranty
Ceiec Electric Technology (CET) offers the customer a minimum of 12-month
functional warranty on the device for faulty parts or workmanship from the date
of dispatch from the distributor. This warranty is on a return to factory for
repair basis.
CET does not accept liability for any damage caused by device malfunctions.
CET accepts no responsibility for the suitability of the device to the application
for which it was purchased.
Failure to install, set up or operate the device according to the instructions
herein will void the warranty.
Only CET’s duly authorized representative may open your device. The unit
should only be opened in a fully anti-static environment. Failure to do so may
damage the electronic components and will void the warranty.

4
Ceiec Electric Technology
Table of Contents
Chapter 1 Introduction...............................................................................................................5
1.1 Overview ...................................................................................................................... 5
1.2 Features........................................................................................................................ 5
1.3 Applications.................................................................................................................. 5
1.4 Getting more information............................................................................................ 5
Chapter 2 Installation .................................................................................................................6
2.1 Appearance .................................................................................................................. 6
2.2 Unit Dimensions........................................................................................................... 6
2.3 Mounting ..................................................................................................................... 7
2.4 RS-485 Wiring .............................................................................................................. 8
2.5 RS-422 Wiring .............................................................................................................. 8
2.6 Ethernet Wiring ........................................................................................................... 9
2.6.1 Straight through Connection............................................................................. 9
2.6.2 Cross-over Connection ...................................................................................... 9
2.7 Power Supply Wiring.................................................................................................. 10
2.8 Chassis Ground Wiring............................................................................................... 10
Chapter 3 Operating the PMC-1302 ESG................................................................................. 11
3.1 Front Panel LED Indicators ......................................................................................... 11
3.2 Reset Button............................................................................................................... 11
3.3 Typical Application ..................................................................................................... 11
Chapter 4 Configuring the PMC-1302 ESG via Web Interface................................................. 12
4.1 Web Console Login..................................................................................................... 12
4.2 Basic Settings ............................................................................................................. 13
4.3 Device Information .................................................................................................... 14
4.4 Change Password ....................................................................................................... 14
4.5 Restart ........................................................................................................................ 15
4.6 Exit 15
Chapter 5 Communications through the PMC-1302 ESG........................................................ 16
5.1 Topological Graph ...................................................................................................... 16
5.2 Configuring the PMC-1302 ESG ................................................................................. 16
5.3 Configuring PecStar.................................................................................................... 17
Appendix A - Technical Specifications ..................................................................................... 20
Appendix B - Standards Compliance ....................................................................................... 21
Appendix C - Ordering Guide................................................................................................... 22
Contact us................................................................................................................................ 22

5
Ceiec Electric Technology
Chapter 1 Introduction
This chapter provides an overview of the PMC-1302 ESG and summarizes many of its key features.
1.1 Overview
The PMC-1302 ESG is an Industrial Ethernet Serial Gateway which provides one 10/100BaseT Ethernet
port, one RS-485 port and one RS-485/RS-422 port. It is the ideal equipment for connecting RS-485
or RS-422 enabled serial devices to an IP-based Ethernet LAN, making it possible to access serial
devices over your Ethernet network for any SCADA or Automation applications. The PMC-1302 ESG
has been specifically designed with industrial automation in mind and therefore provides
un-surpassed performance and reliability under the harshest industrial or commercial environments.
1.2 Features
1x10/100BaseT, 1xRS-485 port and 1xRS-485/RS-422 port
8 kV ESD protection
1.5 kV isolation protection for Ethernet port
3kV isolation protection for RS-485 and RS-422
Simple configuration via its built-in web interface
DIN-Rail or Wall Mount
Extended operating temperature
1.3 Applications
The PMC-1302 ESG supports the efficient transfer of serial packets between the upstream
network-based applications and the downstream RS-485 / RS-422 serial devices via a TCP/IP
connection. Instead of using a Windows based "Virtual COM" driver with a port-mapping utility,
which is often plagued with driver incompatibility among the many different Windows versions, the
PMC-1302 ESG allows applications to directly connect to it via a TCP/IP connection for the transfer of
serial packets inside TCP/IP frames to and from downstream serial devices. Perfectly suited for
communicating with industrial devices that have timing sensitive protocols, the PMC-1302 ESG
provides a reliable interface which allows SCADA or similar applications that already support direct
connection with Ethernet Gateway to communicate with serial devices independent of the serial
protocols used.
1.4 Getting more information
Additional information is available from CET via the following sources:
Visit www.ceiec-electric.com
Contact your local representative
Contact CET directly via email or telephone

6
Ceiec Electric Technology
Chapter 2 Installation
2.1 Appearance
Figure 2-1 Appearance
2.2 Unit Dimensions
Figure 2-2 Dimensions

7
Ceiec Electric Technology
2.3 Mounting
The PMC-1302 ESG should be installed in a dry environment with no dust and kept away from heat,
radiation and electrical noise sources.
Installation steps:
Wall Mounting
Pre-drill four mounting holes on the back plate according to the diagram below.
Remove the two mounting plates (top and bottom) from the back of the PMC-1302 ESG by first
removing the screws that fix the mounting plates in place.
Re-position the mounting plates by sliding the top plate upward and the bottom plate downward
such that the area with the mounting holes protrude from the device's body and re-install the
screws that hold the mounting plates in place.
The PMC-1302 ESG package comes with four additional mounting screws in a little plastic bag.
Use these screws to mount the PMC-1302 ESG on to the back plate.
A Philips screw driver with a long shaft will ease the mounting process.
Figure 2-3-1 Wall Mounting
DIN-Rail Mounting
Before installation, make sure that the DIN rail is already in place
Align the top of the mounting clip at the back of the PMC-1302 ESG at an angle against the top of
the DIN rail as shown in the figure below
Rotate the bottom of the PMC-1302 ESG towards the back while applying a slight pressure to
make sure that the mounting clip is completely and securely fixed on to the DIN rail

8
Ceiec Electric Technology
Figure 2-3-2 DIN-Rail Mounting
2.4 RS-485 Wiring
The PMC-1302 ESG provides one RS-485 port (P2) and one RS-485 / RS-422 port (P3). Up to 32
devices can be connected on a RS-485 bus. The overall length of the RS-485 cable connecting all
devices should not exceed 1200m.
The following figure illustrates the RS-485 communications connections on the PMC-1302 ESG:
Figure 2-4 RS485 Communications Connections
2.5 RS-422 Wiring
The following figure illustrates the RS422 communications connections on the PMC-1302 ESG:
Figure 2-5 RS422 Communications Connections

9
Ceiec Electric Technology
2.6 Ethernet Wiring
2.6.1 Straight through Connection
The following figure illustrates the definition of an 8-pin RJ45 straight through cable. The wiring
sequence from pin 1 to pin 8 is orange-white, orange, green-white, blue, blue-white, green,
brown-white and brown.
Pin1: Orange-White Pin1: Orange-White
Pin 2: Orange Pin 2: Orange
Pin 3: Green-white Pin 3: Green-white
Pin 4: Blue Pin 4: Blue
Pin 5: Blue-White Pin 5: Blue-White
Pin 6: Green Pin 6: Green
Pin 7: Brown-White Pin 7: Brown-White
Pin 8: Brown Pin 8: Brown
Figure 2-6 Straight through Connection
2.6.2 Cross-over Connection
The following figure illustrates the definition of an 8-pin RJ45 cross-over cable. The wiring sequence
from pin 1 to pin 8 is orange-white, orange, green-white, blue, blue-white, green, brown-white and
brown for the RJ45 connector on the left and green-white, green, orange-white, blue, blue-white,
orange, brown-white and brown for the RJ45 connector on the right.
Pin 1: Orange-White Pin 1: Green-White
Pin 2: Orange Pin 2: Green
Pin 3: Green-white Pin 3: Orange-White
Pin 4: Blue Pin 4: Blue
Pin 5: Blue-White Pin 5: Blue-White
Pin 6: Green Pin 6: Orange
Pin 7: Brown-White Pin 7: Brown-White
Pin 8: Brown Pin 8: Brown
Figure 2-7 Cross-over Connection

10
Ceiec Electric Technology
2.7 Power Supply Wiring
For AC supply, connect the live wire to the L/+ terminal and the neutral wire to the N/- terminal. For
DC supply, connect the positive wire to the L/+ terminal and the negative wire to the
N/- terminal. Connect the GND terminal to ground.
Figure 2-8 Power Supply Connections
2.8 Chassis Ground Wiring
Installation:
Connect one end of the ground wire to the Chassis Ground terminal on the PMC-1380 using a
spade connector
Connect the other end of the ground wire to an Earth ground
Figure 2-9 Chassis Ground connection

11
Ceiec Electric Technology
Chapter 3 Operating the PMC-1302 ESG
3.1 Front Panel LED Indicators
There are several LED indicators on the PMC-1302 ESG’s front panel as described in the following
table.
LED Indicator
Color
Status
Function
Run
Green
Blinking
Power is on and system is running normally
P1
Yellow
On
Ethernet network connection
Blinking
Network activity indication
P2 (Rx)
Green
Blinking
P2 is receiving data
P2 (Tx)
Yellow
Blinking
P2 is transmitting data
P3 (Rx)
Green
Blinking
P3 is receiving data
P3 (Tx)
Yellow
Blinking
P3 is transmitting data
Table 3-1 LED Indicators
3.2 Reset Button
There is a Reset button at bottom of PMC-1302 ESG. Use a pointed object, such as a straightened
paper clip or the tip of a ball-point pen to press the Reset button. Pressing and holding the Reset
button for 1 second will cause the PMC-1302 ESG to initiate a reboot sequence. The reboot process
would be completed in approximately 30 seconds.
3.3 Typical Application
The following figure shows the typical application for the PMC-1302 ESG.
Figure 3-1 Typical Application

12
Ceiec Electric Technology
Chapter 4 Configuring the PMC-1302 ESG via Web Interface
4.1 Web Console Login
1) Open your Internet Explorer with the scripting function enabled. To enable scripting for your
browser, right click on your Internet Explorer icon and then select Properties from the pop-up
dialog box. The Internet Options window appears. Select the Security tab and then click on
the Custom Level button near the bottom of the window. The Security Settings window
appears. Enable the three options as shown below and then click OK.
2) The default IP Addresses of the PMC-1302 ESG’s two Ethernet Ports are 192.168.0.127.
Configure the IP Address and the Subnet Mask of the PC as 192.168.0.100 and 255.255.255.0 as
shown below.
3) Enter the IP Address of the PMC-1302 ESG in the Address input box of the Internet Explorer and
then press <Enter>. The default IP address is 192.168.0.127.

13
Ceiec Electric Technology
4) The PMC-1302 ESG’s Web Console Login page appears. Enter the User Name and Password.
The default user name is “user”, and the default password is “123456”.
5) Once the log-in credentials are confirmed, the following page appears.
4.2 Basic Settings
The Basic Settings page is divided into 3 areas: Network Settings, P2 Settings and P3 Settings.
1) Network Settings (P1)
The Network Settings for the Ethernet port can be modified here based on the actual situation. Click
Apply to save your changes. Please be reminded that the IP addresses for the Ethernet port and
Default Gateway should be in the same subnet.

14
Ceiec Electric Technology
2) P2 and P3 Settings
P2 is a standard RS485 port, and P3 is a RS485/RS422 port. All setup parameters such as Baud rate,
Data bits, Parity, Stop bits, IP Port and Timeout can be modified here. Please be reminded that the IP
Port number for P2 (default = 20000) and P3 (default = 20001) should be different. Click Apply to
save your changes. The following table shows the setup parameters for P2 and P3. Most setup
parameters are basic and self-explanatory. Please note that the Timeout parameter refers to the
timeout setting for the IP connection instead of the serial connection, meaning that the IP connection
will be closed if there are no activities between the application software and the PMC-1302 ESG for
the specified amount of time. This is to prevent a potential lock up of the IP connection at the
PMC-1302 ESG if the application software fails to close the IP connection for some unknown reasons.
It is recommended that the default Timeout of 300 seconds be used.
Items
Description
Options
Default
Baud rate
Baud rate
1,200 to 57,600 bps
9600
Data bits
# of Data bits
5 / 6 / 7 / 8 bits
8
Parity
# of Parity bits
None/Even/Odd/Mark/Space
Even
Stop bits
# of Stop bits
1 / 1.5 / 2 bits
2
IP Port Number
IP Port Number
20000 to 60000
P2 = 20000
P3 = 20001
Timeout
Timeout parameter
1 to 60000 (s)
300 (s)
Table 4-1 P2 and P3 Settings
4.3 Device Information
Click on Device Information on the left-hand pane and the following screen appears on the right-hand
pane. Click Apply to save your changes or click Cancel to cancel your changes.
4.4 Change Password
Click on Change Password on the left-hand pane and the following screen appears on the right-hand
pane where the username and password can be changed. Click Apply to save your changes or click
Cancel to cancel your changes.

15
Ceiec Electric Technology
4.5 Restart
Configuration changes will not take effect until the Restart operation has been executed. Click
Restart on the left-hand pane and the following screen appears on the right-hand pane. Click on the
Restart button to save your changes into memory. After restart, the user needs to re-enter the user
name and password to log back into the PMC-1302 ESG’s Web Console.
4.6 Exit
Click on the Quit button near the top right-hand corner as shown in the above figure to exit the Web
Console.

16
Ceiec Electric Technology
Chapter 5 Communications through the PMC-1302 ESG
This section provides details on how to communicate with a PMC-660V1.2 meter (Unit ID = 100) via
the PMC-1302 ESG.
5.1 Topological Graph
In this example, P2 on the PMC-1302 ESG is used. The default IP address for P1 is 192.168.0.127.
5.2 Configuring the PMC-1302 ESG
To configure the PMC-1302 ESG, the user can log on to its Web Console page via the Internet Explorer
by entering the IP address of the PMC-1302 ESG’s Ethernet port in the browser’s address bar. For
example, type http://192.168.0.127/ at the address bar and then press <Enter>.
Enter the default user name “user”, the default password “123456” and then click on the Login button
to open the PMC-1302 ESG’s Web Console.

17
Ceiec Electric Technology
In this example, P2 of the PMC-1302 ESG is used. The PMC-660’s serial port has been configured
with the following parameters:
1. Type = RS-485
2. Baud rate = 9600
3. Data Bits = 8
4. Parity = Even
5. Stop Bits = 1
It is important for the communications parameters of the PMC-1302 ESG’s P2 to be programmed to
match those of the PMC-660V1.2. The IP Port Number for P2 is 20000.
After the P2 settings of the PMC-1302 ESG has been correctly configured, click Restart menu item on
the left-hand pane to open the page and then click on the Restart button to complete the PMC-1302
ESG programming. The PMC-1302 ESG will perform a reboot operation with the new configuration.
When the Log-In page returns, the PMC-1302 ESG is now ready.
5.3 Configuring PecStar
In PecStar’s Systemconfig interface, select Site 1 on the left-hand pane and then click on the

18
Ceiec Electric Technology
Properties icon to bring up the Site Properties dialog box.
In this example, P1 of the PMC-1302 ESG is used, and Site 1 has been configured with the following
parameters:
1. Drive Type = MODBUS - RTU Protocol Master Site Driver,
2. Polling Mode = Serial
3. Port Type = Ethernet
4. IP = 192.168.0.127
5. Port = 20000 (for P2 of PMC-1302ESG)
Select PMC-660 on the right-hand pane under the Device Name column and then click on the
Properties icon on the Tool Bar to bring up the Device Node Properties dialog box. Change Type to
PMC660, Comm ID to 100 and then click OK to save and exit the dialog box.

19
Ceiec Electric Technology
Right click on Device 1 on the left-hand pane, click Import SNF file, and then select the appropriate
SNF file from the pop-up dialog box.
Click on the Save icon on the Tool Bar to save the current configuration into PecStar’s database. The
PecStar software is now ready to communicate with the PMC-660 via P2 of the PMC-1302 ESG.

20
Ceiec Electric Technology
Appendix A - Technical Specifications
10/100BaseT Ethernet Port (P1)
Speed
Connector
Cable
10/100 Mbps
RJ45
CAT5, CAT5e with a maximum 100m distance
Serial Ports (P2, P3)
P2
P3
RS-485 (D+, D-, SH)
RS-485 (D+, D-, SH) / RS-422 (Tx+, Rx+, Tx-, Rx-, SH)
Front Panel LED Indicators
Run (Green)
Blinking - System is running normally
P1 (Yellow)
On - Ethernet network connection
Blinking - Network activity indication
Rx (P2/P3) (Green)
Blinking - Receiving activity
Tx (P2/P3) (Yellow)
Blinking - Transmitting activity
Protocol
Protocol
TCP, UDP, HTTP
Power Supply (L/+, N/-)
Standard
Burden
95-250VAC/DC, 47-440Hz
<3W
Protection
ESD Protection
Isolation Protection
8kV
3kV for RS485 and RS422
1.5kV for Ethernet Port
Environmental Conditions
Operating Temp.
Storage Temp.
Humidity
Atmospheric pressure
-25°C to +70°C
-40°C to +85°C
5% to 95% non-condensing
70 kPa to 110kPa
Mechanical Characteristics
Casing
Unit Dimensions
Shipping Weight
Shipping Dimensions
Mounting
IP Rating
Galvanized Iron
36x110x75mm
0.6kg
105x130x95mm
DIN-Rail and Wall Mounting
30
Table of contents
Popular Gateway manuals by other brands

Sun Power
Sun Power PVS6 installation instructions

Planet
Planet VCG-1500WG-LTE Quick installation guide

NetComm Wireless
NetComm Wireless NF3ADV Setup guide

Watchguard
Watchguard Firebox X1000 quick start guide

2-Wire
2-Wire HomePortal 5012NV installation guide

3One data
3One data GW1114 Series Quick installation guide