manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CentriPro
  6. •
  7. Controllers
  8. •
  9. CentriPro Aquavar IPC User manual

CentriPro Aquavar IPC User manual

Other CentriPro Controllers manuals

CentriPro Aquavar  SPD PLUS User manual

CentriPro

CentriPro Aquavar SPD PLUS User manual

CentriPro AQUAVAR CPC User manual

CentriPro

CentriPro AQUAVAR CPC User manual

CentriPro Aquavar SPD series Troubleshooting guide

CentriPro

CentriPro Aquavar SPD series Troubleshooting guide

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Aquavar® IPC
QUICK START-UP GUIDE FOR ADVANCED IPC
QUICK START GUIDE
IM311
FOR FULL IOM,
SCAN BELOW
PAGE 2
Aquavar IPC Start-Up Genie
CentriPro
INDEX
Safety and Instructions ……………………………………………………………………………………………………… 3
Input and Motor Wiring ……………………………………………………………………………………………………… 4
Control Wiring (Single and Multi-Pump)…………………………………………………………………………………… 5
Multi-Pump Connections …………………………………………………………………………………………………… 6
Single Pump Programming ………………………………………………………………………………………………… 7
Multi-Pump Programming ……………………………………………………………………………………………………13
Performing No Flow Power Calibration ……………………………………………………………………………………16
Support Contact Information ………………………………………………………………………………………………23
PAGE 3
Aquavar IPC Start-Up Genie
CentriPro
SAFETY AND INSTRUCTIONS
OVERVIEW
This guide provides a quick reference for installing the
Technologic Intelligent Pump Controller.
NOTE: This guide does not provide safety, detailed
installation or operational instructions. Refer to the
P2003509 Technologic Intelligent Pump Controller
Installation, Operation, and Maintenance (IOM)
Manual (current version) for complete information.
WARNING
• High Voltage Failure to comply could result in death
or serious injury.
• Discharge Time Failure to wait the specied time
after power has been removed before performing
service or repair could result in death or serious
injury.
• Leakage Current Hazard Failure to ground the
drive properly could result in death or serious injury.
• Unintended Start Failure to comply could result
in death, serious injury, equipment, or property
damage.
• Equipment Hazard Failure to follow the guidelines
could result in death or serious injury.
• Internal Failure Hazard Failure to follow the
guidelines could result in serious injury.
Refer to chapter 1 Introduction and Safety in the
P2003509 Technologic Intelligent Pump Controller
IOM for details of safety.
PREPARE FOR INSTALLATION
WARNING! Installation must be
performed by a qualied technician.
• Suitable Environment – Ensure installation is indoors
and the site temperature range is 0ºC (32ºF) to 40ºC
(104ºF).
• Ensure properly sized safety devices are installed in
the system such as pressure relief valves, compression
tanks, pressure controls, temperature controls and ow
controls.
• Ensure proper guards are installed when the system
has potential to operate at extreme temperatures and/
or pressures.
UNPACK THE UNIT
Remove all packing materials from the product.
Inspect the product to determine if any parts have
been damaged or are missing. Contact your sales
representative if anything is out of order.
PREPARE THE MOUNTING LOCATION
• Ensure adequate supports are utilized to handle the
weight of the system, piping and uid.
• Ensure the suction and discharge pipes are supported
independently by use of pipe hangers near the pump.
• Ensure there is adequate space around the unit to
ensure proper cooling and allow for maintenance and
service.
MOUNT THE UNIT
• Ensure the unit is properly lifted according to the pump
Installation, Operation and Maintenance manual.
• Ensure all ange bolts are adequately torqued.
• For vertically mounted installations with the motor
and controller in the horizontal position, ensure that
adequate support for the motor and controller is
provided.
• Refer to chapter 4 Mechanical Installations in the
P2003509 Technologic Intelligent Pump Controller
IOM for details of installations.
INSTALL WIRING
Electrical Hazard. Dangerous voltage.
Ensure all input power disconnects and
circuit breakers are locked in the off position prior to
installing the input power wiring.
NOTE: External fusing is required for units without a
built in fused disconnect.
Electrical Hazard
Ensure power wiring and fusing is installed according
to NEC/CEC, state, local or municipal codes.
Remove the front cover to gain
access to the power and control
wiring terminals. Connect conduit
runs from the disconnect or service
panel to the drive and route the
power wires through the conduit.
Refer to chapter 5 Electrical
installation and chapter 10 Technical
Specications in the P2003509
Technologic Intelligent Pump Controller IOM for
details on wiring and routing.
PAGE 4
Aquavar IPC Start-Up Genie
CentriPro
INPUT (MAINS) WIRING 3-PHASE:
Connect 3–phase AC input power wiring to terminals
L1, L2, and L3.
Input Terminals
WIRING
OUTPUT WIRING TO MOTORS:
Connect output motor wires to terminal block labeled
U, V, W
Ground
1 Phase
Power
Input
91 (L1)
92 (L2)
93 (L3)
95 PE
SINGLE PHASE INPUT DRIVES:
Connect single phase power wiring to L1 & L2.
Check IOM for specic frame size considerations
PAGE 5
Aquavar IPC Start-Up Genie
CentriPro
Install Jumper wires on:
✔Terminal 12 and 18
The IPC requires a start command on
terminal 18. To apply a start signal connect
a jumper wire between terminals 18 (DI 18,
parameter 5-10) and 12 (24V dc). A start
command is given to the controller when
terminal 18 is connected to 24V.
Install Transducer cable on:
✔Brown on terminal 12 (24V)
✔White on terminal 53 (4-20MA)
✔Place ground shield between spring clip
and shielded cable.
SINGLE AND MULTI-PUMP CONTROL WIRING
PAGE 6
Aquavar IPC Start-Up Genie
CentriPro
Carefully remove
the plastic cover by
unlocking the tab on
the top of the drive and
releasing.
Carefully remove
bottom cover by
unlocking tab
Terminal #5 to Terminal #5
Terminal #7 to Terminal #7
If using more than two controllers,
follow the same wiring instructions
for the additional drive.
Refer to the IOM for
additional multi-control wiring
congurations.
Re-install covers and keypad and
begin commissioning
Connect Wires
MULTI-PUMP CONNECTIONS
Connect communication
wires to the bottom of
this card
PAGE 7
Aquavar IPC Start-Up Genie
CentriPro
COMMISSIONING STEPS
1. Power on drive(s)
2. Complete Programming.
Select Quick Menu
Select Parameter 04
“Start-Up Genie”
You are now able to start the Start-Up
Genie
For Regional Settings Select North America
or International
PAGE 8
Aquavar IPC Start-Up Genie
CentriPro
Select English US as Language and proceed
with the down arrow
Select Booster for Application type
Select Motor Horsepower
Select Motor Voltage
Select Motor Frequency
Select Motor Nominal Speed
✔Input
Motor
Current
✔Input
Current Limit -
SFA/FLA
Example:
SFA is 11.42, FLA is 10.38
Current Limit: 11.42/10.38 = 1.10
Carry over the decimal 2 places to
the right to ensure your Current Limit
percentage = 110%
For Submersible motors we input
SFA and use current limit at 100%
PAGE 9
Aquavar IPC Start-Up Genie
CentriPro
Select Motor Type
Select Sleep Frequency Low Limit
Select Filter Type
• None for no lter
• Reactor-Line Load Reactor (KLR Type)
• Dv/Dt (for V1K Type)
• Sinewave for sinewave
(Please refer to the IOM for further
instructions)
Select Yes to Continue to the Application
Setup
PAGE 10
Aquavar IPC Start-Up Genie
CentriPro
Select either Single Pump or Multi-Pump
Control. Follow the programming for single
pump application below.
For Multi-Pump Programming, continue to
page 13.
Select Constant Pressure for Application type
Select PSI for pressure control units
FOR SINGLE PUMP PROGRAMMING