Ceta 101 User manual

Operating manual
101
Double differential temperature control
Version 1043-22
Art. 0450021015 GB
All manuals and user guides at all-guides.com
all-guides.com

Contents
Scope of delivery .................................................................................................... 3
General ....................................................................................................................................3
Intended use .............................................................................................. 3
Safety .......................................................................................................................................3
General key functions .........................................................................................4
Version display (when starting)..........................................................................4
Basic display ........................................................................................................... 5
Manual mode ……………………………………………………………………………………….....6
Sensor resistance values ....................................................................................7
Menu level .............................................................................................................. 8
Parameter description .................................................................................... 11
Installation ........................................................................................ 19
Connection diagram ......................................................................................... 20
Fault clearance ......................................................................................................21
Declaration of conformity ............................................................................... 22
Technical data .......................................................................................................23
Liability ........................................................................................................................23
Disposal .................................................................................................................................23
© Elektronikbau- und Vertriebs GmbH
Heisterner Weg 8 - 12
D-57299 Burbach
This document may not be reproduced nor disclosed to third parties, particularly competitors, in original
or copy form without our prior explicit consent. The document is subject to our proprietary rights and
copyrights.
All manuals and user guides at all-guides.com

3
Scope of delivery
1. 1x Central unit CETA 101
2. 1x Tank immersion sensor KVT 20/2/6
3. 2x Collector sensor PT1000/6
4. 8x Screw, plate 2,9x19 mm
5. 3x Screw assembly 4x35 mm
6. 3x Plug U6
7. 2 x Cable clamp
General
Systems with 2 heat sources and hot water tanks are controlled via the
differential temperature control. When the heat source temperature exceeds the
tank temperature by the value set on the controller, the circulation pump is
activated by the control and the heat absorbed in the heat source is transported
to the hot water tank.
Intended use
The unit is manufactured in accordance with state of the art technology and
approved safety regulations. Nevertheless, using the unit can cause danger to the
user or third persons, or damage to the unit and other assets. The unit must be
used exclusively as differential temperature controller.
Safety
All electrical connections, safety measures and protections have to be carried out
by an authorised professional electrician according to the valid standards and VDE-
guidelines, as well as the local regulations. The electrical connection must be a
fixed connection according to VDE 0100.
Hazard symbols in this operating manual
Hazard!
This symbol indicates information that warns of possible safety
risks or severe and fatal injuries!
All manuals and user guides at all-guides.com

4
General key functions
1. General key functions
Prog
Change selected submenus
Change (parameter) setting
Save value
+ (Plus) or - (Minus)
Change parameter
Change menu item
Esc
Exit setting
Keep old value
Select next higher menu level
Esc-Lang
Return to basic display
2. Version display (when starting)
c 101= Type designation Ceta 101
24.02= Version display (due to update it can
differ from example shown)
All manuals and user guides at all-guides.com

5
Basic display
3. Basic display
1= Basic display 1
80.5°C= Temperature F3 heat supplier 1
(e.g. collector or solid fuel boiler)
44.0°C= Temperature F1 heat storage tank 1
AT1= Display pump function P1
AT2= Display pump function P2
H-GEN= Display burner block
Use + / - to switch to:
2= Basic display 2
75.5°C= Temperature F4 heat supplier 2
(e.g. collector or solid fuel boiler)
51.5°C= Temperature F2 heat storage tank 2
(if sensor F2 is available)
AT1= Display pump function P1
AT2= Display pump function P2
H-GEN= Display burner block
All manuals and user guides at all-guides.com

6
3b. Mannual switch – on pump
Mannual mode
+ Mannual mode
0... 1 Pump function
— Activated when keep pressed
— Switch – on / switch – off pump
— Escape from mannual mode
Function: Mannual mode pump activation for inspection purposes
0 = Pump off.
1 = Pump on.
Attention!
This function must be used only by the technician. When the
manual mode is on, the safety settings of the CETA 101 are de-
activated! In case of faulty usage, may cause damage to the
installation (e.g stagnation)
All manuals and user guides at all-guides.com
all-guides.com

7
Sensor resistance values
4. Sensor resistance values
Depending on temperature:
PT1000 KVT 20
T (°C) R (kOhm)
40 1.155
50 1.194
60 1.232
70 1.271
80 1.309
90 1.347
100 1.385
110 1.423
120 1.461
130 1.498
140 1.536
150 1.573
160 1.611
170 1.648
180 1.685
190 1.722
200 1.758
210 1.795
220 1.832
230 1.868
240 1.905
250 1.941
T (°C) R (kOhm)
10 1.783
12 1.812
14 1.840
16 1.869
18 1.898
20 1.928
25 2.002
30 2.078
35 2.155
40 2.234
45 2.314
50 2.395
55 2.478
60 2.563
65 2.648
70 2.735
75 2.824
80 2.914
85 3.005
90 3.098
95 3.192
100 3.287
All manuals and user guides at all-guides.com

Menu level
8
5. Menu level
General menu structure Ceta series
Esc
Select menu level
+
+-
+
Prog
Basic display
27
Calibration
28
Relay test
01
Menu 01
02
Menu 02
-
-
Prog
Esc
Set parameter value
02:01
Parameter 01
+
-
Select parameters
+
+
02:02
Parameter 02
Prog
Value n
Value 2
Value1
-
-
Esc
-
+
Return
withou
t
saving
Prog
02:nn
Last parameter
Return
and save
All manuals and user guides at all-guides.com

Menu level
9
Overview of menu level
X1: Only displayed during active heat balancing
X2: F
unction
only in
bus
connecti
on
ESC
+
+
+
+
+
Prog
Basic displa
y
27
Calibration
28
Relay test
03
System
01
Info
08
09
Prog
ES
C
Prog
ES
C
Prog
ES
C
Prog
ES
C
Prog
ES
C
Prog
ES
C
08:
Burner block
Heat generato
r
X1
08:01
Heat capacity
09:
Burner block
Heat generator
27:01
Calib. sensor
F1
03:01
Code entry
28:01
Relay test
Output R1
X1
09:03
Pump sT2
On/Off
8
1
X2
X2
+
+
+
+
+
-
-
-
-
-
X3
03:02
Auto set function
09:
Inhibition Hea
t
generator
08:
Inhibition
Heat generator
X1
09:04
Temperature
Heat supplier 2
27:02
Calib. sensor
F2
X1
08:02
Heat balance
28:02
Relay test
Output R2
8:
Switch-on
differential
10:
Switch-on
differential
X2
X2
X
5
X5
09:05
Temperature
Heat
storage tank 2
08:
Heat balance
On/Off
27:03
Calib. sensor
F3
X3
03:03
Bus address
09:
Switch-off
differential
08:
Switch-off
differential
28:03
Relay test
Output R3
08:03
Pump T1
On/Off
X3
All manuals and user guides at all-guides.com

Menu level
10
X3: Are hidden when activating code 03:09
X5: Option
X3
03:06
Automatic
exit time
X3
03:07 X3
03:09
Code
heating specialist
09:07
Operating hours
Pump
4
T2
09:08
Starts
Pump
4
T2
Anti-blocking
protection Pump
03:10
Reset parameter
08:0
Final switch off
temp. Heat supplier
08:0
Max.temp.
Heat storage tank
08:0
Min.temp.
Heat supplier
08:0
Max.temp.
heat supplier
08:1
Reset counter
09:0
Final switch off
temp. Heat supplier
09:0
Max.temp.
Heat storage tank
08:1
Heat capacity
HT-medium
08:1
Density
HT-medium
09:0
Min.temp.
Heat supplier
09:0
Max.temp.
heat supplier
09:1
Reset counter
27:04
Calib. sensor
F4
09:16 4T2
Changeover
sensor F2
8
Minimum running
time Pump
1
Minimum running
time Pump
08:
Volume flo
w
H
T
-
medium
X5
08:06
Temperature
Return flow
08:04
Temperature
Heat supplier
08:05
Temperature
Heat storage tank
08:07
Operating hours
Pump
08:08
Starts
Pump
All manuals and user guides at all-guides.com

11
Parameter description
6. Parameter description
01 Information level
Display Designation Description
08:01 Heat capacity AT1 Current heat capacity in W X1
08:02 Heat balance AT1 Display of cumulative heat energy in kWh X1
08:03 Display pump 0: Pump is switched off
function AT1 1: Pump is switched on
08:04 Temperature Sensor temperature of heat supplier (e.g. collector, solid fuel
heat supplier AT1 boiler) at input F3
08:05 Temperature
heat storage tank
Sensor temperature of heat storage tank at input F1
AT1
08:06 Temperature
return AT1
Sensor temperature of return at input F2, if available.
X5
08:07 Pump operating
hours AT1
Number of pump operating hours
08:08 Pump starts AT1 Number of pump starts
09:03 Display pump 0: Pump is switched off
function AT2 1: Pump is switched on
09:04 Temperature Sensor temperature of heat supplier (e.g. collector, solid fuel
heat supplier AT2 boiler) at input F4
09:05 Temperature Sensor temperature of heat storage tank at input F1 X5
heat storage tank (or F2, if available)
AT2
09:07 Pump operating
hours AT2
Number of pump operating hours
09:08 Pump starts AT2 Number of pump starts
03 Parameter system
Display Designation Description
03:01
Code entry
Setting range:
0 ... 999
Factory setting: 0
Function:
Show parameters marked with X3.
All manuals and user guides at all-guides.com
all-guides.com

12
Parameter description
Display Designation Description
03:03 Bus address Setting range: 21...25 X3
Factory setting: 21
Function:
If more than one CETA 100 or 101 has to be connected via data
bus within a system, each unit must be set to a unique address.
03:06 Automatic exit time Setting range: 0.5 ... 10 min X3
Factory setting: 0.5 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
03:07 Anti-blocking Setting range: 0 = OFF X3
protection 1 = ON
Factory setting: OFF
Function:
Pump is switched on 20 s daily during extended shutdown
(> 24h) as protection against blocking when function is activated.
03:09 Code heating Setting range: 0 ... 999
specialist Factory setting: 0
Function:
Hide parameters marked with X3.
03:10 Total reset Reset to factory settings
08 Parameter DeltaT1
Display Designation Description
08:01
08:02
Control mode AT1
Switch-on
differential AT1
Setting range:
0 = Delta T OFF
1 = Delta-T without return flow sensor
2 = Delta-T with return flow sensor
3= Thermostat function
Factory setting: 1
Function:
The setting determines whether heat balancing is to be
performed by a return flow sensor (additional parameters)
Setting range: (Switch-off differential + 3K) ... 30K
Factory setting: 10K
Function:
If temperate difference between sensors of heat supplier F3 and
heat storage tank F1 is larger than set value, the pump
switches
on
All manuals and user guides at all-guides.com

13
Parameter description
Display Designation Description
08:03 Switch-off Setting range: 2K ... (Switch-on differential - 3K)
differential AT1 Factory setting: 5K
Function:
If temperate difference between sensors of heat supplier F3 and
heat storage tank F1 is smaller than set value, the pump
switches off.
08:04 Minimum pump Setting range: OFF (----)
running time AT1 0.5 ... 60 min
Factory setting: 3 min
Function:
Minimum switch-on time of pump per start.
08:05 Minimum Setting range: OFF (----)
temperature heat 5 ... 80°C
supplier AT1 Factory setting: OFF
Function:
Irrespective of switching differentials, the pump switches on
only after the sensor of heat supplier F3 has exceeded the set
value.
08:06 Maximum Setting range: OFF (----), 30 ... 110°C
temperature heat Factory setting: 90°C
supplier AT1 Function:
Irrespective of switching differentials, the pump performs a
forced switch on after the sensor of heat supplier F3 has
exceeded the set value.
08:07 Final switch-off Setting range: OFF (----), 70 ... 210°C
temperature heat Factory setting: OFF
supplier AT1 Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat supplier F3 has
exceeded the set value.
08:08 Maximum Setting range: OFF (----), 50 ... 110°C
temperature heat Factory setting: 75°C
storage tank AT1 Function:
Irrespective of switching differentials, the pump performs a forced
switch off after the sensor of heat storage tank F1 has exceeded the set
value. This switch-off takes priority over functions 08:07 and 08:06.
All manuals and user guides at all-guides.com

14
Parameter description
Display Designation Description
08:09 Burner block Setting range: 0 ... 2 X2
heat generator AT1 Factory setting: 1
Function: 0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
08:10 Inhibition heat Setting range: OFF (----) ... 24h X2
generator AT1 Function:
A
fter burner block is active, the heat generator is also blocked for
the duration of the set time.
08:11 Activation heat Setting range: OFF (----) X3, X5
balance AT1 1 = Heat balancing via return sensor on
F2 (option)
Factory setting: OFF
Function:
The settings of parameters 08:12 to 08:14 are only active if the
heat balance function has been switched on via this parameter.
08:12 Volume flow HT- Setting range: 0.0 ... 30 l/min
medium AT 1 Factory setting: 0.0 l/min
Function:
Here the volume flow is set in litre/minute when calculating flow
rate, according to respective pump capacity.
08:13 Density HT-medium Setting range: 0.8 ... 1.2 kg/l
AT1 Factory setting: 1.05 kg/l
Function:
Using this parameter, the density of the heat transfer medium is
entered in kilogramme per litre, according to manufacturer's data.
08:14 Heat capacity HT- Setting range: 2.0 ... 5.0 kJ/kgK
medium AT1 Factory setting: 3.6 kJ/kgK
Function:
This setting value is used to enter the specific heat capacity of
the heat transfer medium according to manufacturer's
information.
08:15 Reset counter AT1 Setting range: 0 = no reset, 1 = reset counter
Factory setting: 0
Function:
When value is changed to 1 and confirmed, all counters (heat balance,
operating hours and starts) are reset.
All manuals and user guides at all-guides.com

15
Parameter description
Display Designation Description
08:18 Back Cooling Setting range: OFF (----), 5 ... 50K
Differential Factory setting: OFF
Function: If temperature F1 is over the 08:08 value and temperature F3
is under 40˚C, then the pump starts working, until F1 difference (08:18)
drops under 08:08 value.
08:19 Burner Block Setting range:
OFF (----), 5
... 80˚C
temperature Factory setting:
OFF
Function: Additionally or alternatively to 08:09, is possible to
regulate an F1 temperature, that is going to block burner (via
data bus). If the 08:19 value drops under 5K, the burner is
being activated again.
08:20
Thermostat
Switch – On
temperature
Setting range: 5˚C… (switch
–
off temperature
–
3K)
Factory setting: 30˚C
Function: If F3 temperature drops under the setting 08:20, then the pump is
being activated.
08:21
Thermostat
Switch - Off
temperature
Setting range: ( Switch – On temperature +3K)… 120˚C
Factory setting: 90˚C
Function: If F3 temperature rises over the setting 08:20, then the
pump is being deactivated.
08:22 Inverse
Setting range: 0, 1
thermostat Factory setting: 0
Function:
Inverts the pump function. 0 = normally close,
1 = normally open
08:23
Frost-protection
Solar collector
tem
p
erature
Setting range:
Off, -15˚C… 10˚C
Factory setting: Off
Function:
Solar pump switches on when the temperature from the solar
collector drops below the 08:23 value. The pump switches off
when solar temperature rises over the 08:23 value + 2,5K.
All manuals and user guides at all-guides.com

16
Parameter description
09 Parameter DeltaT2
Display Designation Description
09:01 Control mode AT2 Setting range: 0 = Delta T2 OFF
1 = Delta-T2 without return flow sensor
2 = Delta-T2 with return flow sensor
3= Thermostat function
Factory setting: 1
09:02 Switch-on Setting range: (Switch-off differential + 3K) ... 30K
differential AT2 Factory setting: 10K
Function:
If temperate difference between sensors of heat supplier F4 and
heat storage tank F2 is larger than set value, the pump
switches on.
09:03 Switch-off Setting range: 2K ... (Switch-on differential - 3K)
differential AT2 Factory setting: 5K
Function:
If temperate difference between sensors of heat supplier F4 and
heat storage tank F2 is smaller than set value, the pump
switches off.
09:04 Minimum running Setting range: OFF (----)
time pump AT2 0.5 ... 60 min
Factory setting: 3 min
Function:
Minimum switch-on time of pump per start.
09:05 Minimum Setting range: OFF (----)
temperature heat 5 ... 80°C
supplier AT2 Factory setting: OFF
Function:
Irrespective of switching differentials, the pump switches on
only after the sensor of heat supplier F4 has exceeded the set
value.
09:06 Maximum Setting range: OFF (----), 30 ... 110°C
temperature heat Factory setting: 90°C
supplier AT2 Function:
Irrespective of switching differentials, the pump performs a
forced switch on after the sensor of heat supplier F4 has
exceeded the set value.
09:07 Final switch-off Setting range: OFF (----), 70 ... 210°C
temperature heat Factory setting: OFF
supplier AT2 Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat supplier F4 has
exceeded the set value.
All manuals and user guides at all-guides.com
all-guides.com

17
Parameter description
Display Designation Description
09:08 Maximum Setting range: OFF (----), 50 ... 110°C
temperature heat Factory setting: 75°C
storage tank AT2 Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat storage tank F1
(optionally F2, if available) has exceeded the set value. This
switch-off takes priority over functions 08:07 and 08:06.
09:09 Burner block Setting range: 0 ... 2 X2
heat generator AT2 Factory setting: 1
Function: 0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
09:10 Inhibition heat Setting range: OFF (----) ... 24h X2
generator AT2 Factory setting: OFF
Function:
A
fter burner block is active, the heat generator is also blocked for
the duration of the set time.
09:15 Reset counter AT2 Setting range: 0 = no reset, 1 = reset counter
Factory setting: 0
Function:
When value is changed to 1 and confirmed, all counters (Delta T2
pump, operating hours and starts) are reset.
09:16 Changeover Setting range: 1, 2 X5
sensor F2 Factory setting: 1
Function: 1 = Sensor F2 (option) is return flow sensor
and both Delta-T controls adjust to sensor
heat storage tank 1 (F1)
2 = Sensor F2 (option) is sensor
heat storage
tank 2
All manuals and user guides at all-guides.com

Parameter description
Display Designation Description
09:19 Burner Block Setting range:
OFF (----), 5
... 80˚C
temperature Factory setting:
OFF
Function: Additionally or alternatively to 09:09, is possible to
regulate an F1 temperature, that is going to block burner (via
data bus). If the 09:19 value drops under 5K, the burner is
being activated again.
09:20
Thermostat
Switch – On
temperature
Setting range: 5˚C… (switch
–
off temperature
–
3K)
Factory setting: 30˚C
Function: If F3 temperature drops under the setting 09:20, then the pump is
being activated.
09:21
Thermostat
Switch - Off
temperature
Setting range: ( Switch – On temperature +3K)… 120˚C
Factory setting: 90˚C
Function: If F3 temperature rises over the setting 09:20, then the
pump is being deactivated.
09:22 Inverse
Setting range: 0, 1
thermostat Factory setting: 0
Function:
Inverts the pump function. 0 = normally close,
1 = normally open
09:23
Frost-protection
Solar collector
tem
p
erature
Setting range:
Off, -15˚C… 10˚C
Factory setting: Off
Function:
Solar pump switches on when the temperature from the solar
collector drops below the 09:23 value. The pump switches off
when solar temperature rises over the 09:23 value + 2,5K.
27 Sensor calibration
Display Designation Description
27:01 Calibration F1 Setting range: -5K ... +5K
Factory setting: 0K
Function: Correction of measured sensor value on
Input heat storage tank F1
27:02 Calibration F2 See 27:01 on input return heat storage tank F2 (option)
27:03 Calibration F3 See 27:01 on input heat supplier F3
27:04 Calibration F4 See 27:01 on input heat supplier F4
All manuals and user guides at all-guides.com

19
Mounting
28 Relay test
Display Designation Description
28:01 Test pump output Setting range: 0 = OFF
Delta T1 1 = ON
Factory setting: 0
Function:
By changing the value, the output switches on and off (test
function), independent of function.
28:02 Test pump output see 28:01
Delta T2
28:03 Test output
burner block
see 28:01
7. Mounting
Hazard
!
Mounting must be performed by an authorised professional electrician!
Ensure that unit is de-energised before opening it!
Drilling pattern for wall fastening
1. Remove terminal area cover from
casing.
2. For mounting, first put a screw
into the wall.
3. Hang controller into the opening.
4. Use controller as template for the
other screw holes.
All manuals and user guides at all-guides.com

20
Connection diagram
Rail mount
1. Insert mounting feet into rail
mount opening.
2. Lock hook in place by pushing
down.
8. Connection diagram
Hazard
!
Connection must be performed by an authorised professional
electrician! Ensure that unit is de-energised before opening it!
230V connections Low volta
g
e connections
L
=
Ph
ase
230V
ma
i
ns
1=L1 [230V) Connection Delta T1 pump
2=L1 [230V) Connection Delta T2 pump
C
onnec
ti
on w
ith
ou
t
f
unc
ti
on
N=Neutral 230V mains, pumps
Connection burner block [isolated)
=Earthing
Bus connections for networking [see parameter 03:03)
C
onnec
ti
ons w
ith
ou
t
f
unc
ti
on
C
onnec
ti
ons w
ith
ou
t
f
unc
ti
on
F1=Sensor heat storage tank Delta-T1 [KVT20)
F2=Sensor heat storage tank Delta T2/return flow Delta T1 [KVT20), [option)
F3=Sensor heat supplier Delta-T1 [PT1000)
F4=Sensor heat supplier Delta-T2 [PT1000)