CHINSC ELECTRIC 200 Series User manual

200 Series General Purpose Vector AC Drive
Operation Manual
Material Version: V3.4
Date of Filing: 2021-04-14
Company Standard: Q/903703SSC002-2019

200SeriesGeneralPurposeVectorACDrive Contents
I
Contents
Chapter 1 Safety and Notes ............................................................................................. 1
1.1 Safety Notes .......................................................................................................... 1
1.2 Notes ..................................................................................................................... 1
Chapter 2 Specifications and Selection............................................................................ 3
2.1 Naming Rules........................................................................................................ 3
2.2 Nameplate ............................................................................................................. 3
2.3 Model and Technical Parameters........................................................................... 3
2.4 Technical specification.......................................................................................... 8
2.5 200-N Product Outline and Installation Aperture Size .......................................... 9
2.5.1 200-N G0.4~G18.5KW Outline and Outer Size of Hang Machine Plastic
Casing AC Drive .................................................................................................... 9
2.5.2 200-N G22~G550KW Outline and Outer Size of Hang Machine Metal
Casing AC Drive ...................................................................................................10
2.6 230 Series Ball Mill Special Purpose AC Drive Product Outline Drawing and
Installation Hole Size .................................................................................................11
2.7 260 Series Engineering Type Vector AC Drive Product Outline Drawing and
Installation Hole Size .................................................................................................13
2.8 270 Series Movable crusher Special Purpose AC Drive Product Outline Drawing
and Installation Hole Size ..........................................................................................15
2.8.1 270 Series 11~18.5KW Outline and Outer Size of Hang Machine Plastic
Casing AC Drive ...................................................................................................15
2.8.2 270 Series 22~110KW Outline and Outer Size of Hang Machine Metal
Casing AC Drive ...................................................................................................15
2.8.3 270 Series 132~400KW Outline and Outer Size of Hang Machine Metal
Casing AC Drive ...................................................................................................16
2.9 280 Series Factory Explosion-proof AC Drive Movement Product Outline
Drawing and Installation Hole Size............................................................................17
2.10 Keyboard Outline Size .......................................................................................23
2.11 The Disassembly and Installation of the Keyboard ............................................24
2.12 Selection of Braking Package.............................................................................24
Chapter 3 Mechanical and Electrical Installation ...........................................................25
3.1 External Electrical Components Selection Guide.................................................25
3.2 Main Circuit Terminal and Wiring .......................................................................26
Chapter 4 Keyboard Operation and Display ...................................................................30
4.1 Introduction Of Keyboard Operation and Display Interface ................................30
4.2 Descriptions of Function Indicators .....................................................................31
4.3 Basic Function Code Inspection and Modification Method Description..............31

Contents 200 Series General Purpose Vector AC Drive
II
Chapter 5 Function Parameter Simple List.....................................................................33
Chapter 6 Key Function Parameter Explanation In Detail..............................................58
Chapter 7 Communication Protocol................................................................................68
7.1 Communication Allocation ..................................................................................68
7.2 Salve Machine Address ........................................................................................68
7.3 Function Code 03: Present Reading the Variant the Function Code.....................68
7.4 Function Code 06: Stands for the Function Code of Writing Variable .................70
Chapter 8 Troubleshooting..............................................................................................72
8.1 Faults and Actions................................................................................................72
8.2 Common Fault and Handling Methods ................................................................74

200SeriesGeneralPurposeVectorACDrive Chapter1SafetyandNotes
1
Chapter 1 Safety and Notes
1.1 Safety Notes
1. The AC drive should be installed and adjusted by professional electrical technicians, otherwise there is
a danger of electric shock!
2. Make sure the power is off before wiring, otherwise there is a danger of electric shock!
3. Ground terminal must be reliably grounded, ground resistance should be less than 0.1!
4. Do not connect the input power to the output U, V, W, otherwise the AC drive will be damaged!
5. Make sure wires diameter be accord with technical standards, otherwise fault will happen.
6. No voltage test is required for AC drive, this item has been tested when leave the factory.
7. Do not touch the AC drive terminal (Includes control terminal) after power on, otherwise there is a
danger of electric shock!
8. If you want to do parameter self-learning, please be aware of the risk of injury during motor rotation,
otherwise it may cause an accident!
9. Do not control the start and stop of the ac drive by the contactor on or off, otherwise the equipment will
be damaged!
10. AC drive cannot be repaired or maintained immediately because there is still high voltage on the filter
capacity after the power off. It needs to wait for more than 5 minutes before using a multimeter to measure
the bus voltage (the voltage between (+) and (-)) should not exceed 36V.
11. Do not share the ground terminal PE with the power line terminal N!
1.2 Notes
1. Insulation checking of motors
Make sure to separate the motor connection from the AC drive during insulation test(checking), It is
recommended to use 500V voltage megohm meter and should guarantee the measured insulation
resistance is not less than 5 m .
2. About motor thermal and noise
The output voltage of the AC drive is PWM wave, which contains certain harmonics, so the temperature
rise, noise and vibration of the motor will increase slightly compared with the operation of power
frequency.
3. The output side cannot connect to the pressure sensitive device or improved the power factor of
capacity.
4. Protection against lightning strike
This series AC drive is equipped with lightning overcurrent protection device, which has certain
self-protection ability for inductive lightning. For frequent lightning, users should also install lightning
protection at the front of the AC drive.
5. Disposing unwanted drive

Chapter 1 Safety and Notes 200 Series General Purpose Vector AC Drive
2
The electrolytic capacitor of the main circuit and the electrolytic capacitor on the printed board may
explode during incineration. The incineration of plastic will produce poisonous gas, please deal with it as
industrial waste.
6. Pay attention when the cable length is too long
When the motor cable length is longer than 50m, it is recommended to install an output reactor or output
filter. If the motor cable length exceeds 100m,An output reactor or output filter must be installed,
otherwise the motor insulation is easily damage.

All-in-one machine
Auxiliary
200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
3
Chapter 2 Specifications and Selection
2.1 Naming Rules
B/Z/F-ET - N/2N/A
200:
General purpose vector ac drive
230-QM:Ball mill special
purpose
ac drive
260-KH:
Engineering type vector ac drive
270-PS:Movable crusher special
purpose ac drive
280-FB:Factory explosion-proof
ac drive general purpose movement
Adaptive motor power
T4
200 -G15 P 18.5 T4/
0.4~700
0.4KW~700KW
Upgraded version
3 phase380±15
%
Motor Power
(
KW
)
Fan & pump type
General purpose
P
G
Type
Input voltage level
Mark
Mark
Mark
Brake unit
F
Mark
NullNull
With brake unit
B/Z
ET
Note: 1) For G22KW and G30KW type ac drive, if braking is needed, it needs to purchase our the -B
model with built-in braking.
2) For G37KW and bigger power ac drive, if braking is needed, it needs to purchase our external braking
unit.
2.2 Nameplate
2.3 Model and Technical Parameters
200 Model and technical parameters
VFD Model Input V Power Capacity
KVA
Input Current
A
Output
Current A
Adaptive
Motor KW
200-G0.4T4B-N
3 phase 380V
Range:
±15%
1.0 2.4 1.2 0.4
200-G0.75T4B-N 1.5 3.4 2.5 0.75
200-G1.5T4B-N 3.0 5.0 3.7 1.5
200-G2.2T4B-N 4.0 5.8 5.0 2.2
200-G3.0/P3.7T4B-N 5.0 8.0 7/9 3.0/3.7

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
4
200-G3.7/P5.5T4B-N 5.9 10.5 9/13 3.7/5.5
200-G5.5/P7.5T4B-2N 8.9 14.6 13/17 5.5/7.5
200-G7.5/P11T4B-2N 11.0 20.5 17/25 7.5/11
200-G11/P15T4B-N 17.0 26.0 25/32 11/15
200-G15/P18.5T4B-N 21.0 35.0 32/37 15/18.5
200-G18.5/P22T4B-N 24.0 38.5 37/45 18.5/22
200-G22/P30T4B-2N 30.0 46.5 45/60 22/30
200-G30/P37T4B-2N 40.0 62.0 60/75 30/37
200-G37/P45T4-2N 57.0 76.0 75/90 37/45
200-G45/P55T4-N 69.0 92.0 90/110 45/55
200-G55/P75T4-N 85.0 113.0 110/150 55/75
200-G75/P93T4-N 114.0 157.0 150/176 75/93
200-G93/P110T4-N 134.0 180.0 176/210 93/110
200-G110/P132T4-N 160.0 214.0 210/253 110/132
200-G132/P160T4-N 192.0 256.0 253/300 132/160
200-G160/P185T4-N 231.0 307.0 300/340 160/185
200-G185/P200T4-N 242.0 350.0 340/380 185/200
200-G200/P220T4-N 250.0 385.0 380/420 200/220
200-G220/P250T4-N 280.0 430.0 420/470 220/250
200-G250/P280T4-N 355.0 468.0 470/520 250/280
200-G280/P315T4-N 396.0 525.0 520/600 280/315
200-G315/P350T4-N 445.0 590.0 600/640 315/350
200-G350/P400T4-2N 500.0 665.0 640/690 350/400
200-G400/P450T4-2N 565.0 785.0 690/800 400/450
200-G450/P500T4-2N 650.0 825.0 800/860 450/500
200-G500/P550T4-N 700.0 883.0 860/950 500/550
200-G550T4-N 770.0 975.0 950 550
230 Model and technical parameters
VFD Model Input V Power Capacity
KVA
Input Current
A
Output
Current A
Adaptive
Motor KW
230-QM22T4B/Z-ET-A
3 phase 380V
±15%
30.0 46.5 45 22
230-QM30T4B/Z-ET-A 40.0 62.0 60 30
230-QM37T4/Z-ET-A 57.0 76.0 75 37
230-QM45T4/Z-ET-A
230-QM45T4/F-ET-A 69.0 92.0 90 45

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
5
230-QM55T4/Z-ET-A
230-QM55T4/F-ET-A 85.0 113.0 110 55
230-QM75T4/F-ET-A 114.0 157.0 150 75
230-QM93T4/F-ET-A 134.0 180.0 176 93
230-QM110T4/F-ET-A 160.0 214.0 210 110
230-QM132T4/F-ET-A 192.0 256.0 253 132
230-QM160T4/F-ET-A 231.0 307.0 300 160
230-QM185T4/F-ET-A 242.0 350.0 340 185
230-QM200T4/F-ET-A 250.0 385.0 380 200
230-QM220T4/F-ET-A 280.0 430.0 420 220
230-QM250T4/F-ET-A 355.0 468.0 470 250
230-QM280T4/F-ET-A 396.0 525.0 520 280
230-QM315T4/F-ET-A 445.0 590.0 600 315
230-QM350T4/F-ET-A 500.0 665.0 640 350
230-QM400T4/F-ET-A 565.0 785.0 690 400
230-QM450T4/F-ET-A 650.0 825.0 800 450
230-QM500T4/F-ET-A 700.0 883.0 860 500
230-QM550T4/F-ET-A 770.0 975.0 950 550
230-QM630T4/F-ET-A 1000.0 1400.0 1100 630
260 Model and technical parameters
VFD Model Input V Power Capacity
KVA
Input Current
A
Output
Current A
Adaptive
Motor KW
260-KH30T4B-A
3 phase 380V
±15%
40.0 62.0 60 30
260-KH37T4B-A 57.0 76.0 75 37
260-KH45T4-A 69.0 92.0 90 45
260-KH55T4-2N 85.0 113.0 110 55
260-KH75T4-2N 114.0 157.0 150 75
260-KH93T4-2N 134.0 180.0 176 93
260-KH110T4-2N 160.0 214.0 210 110
260-KH132T4-2N 192.0 256.0 253 132
260-KH160T4-2N 231.0 307.0 300 160
260-KH185T4-2N 242.0 350.0 340 185
260-KH200T4-2N 250.0 385.0 380 200
260-KH220T4-2N 280.0 430.0 420 220
260-KH250T4-2N 355.0 468.0 470 250

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
6
260-KH280T4-2N 396.0 525.0 520 280
260-KH315T4-2N 445.0 590.0 600 315
260-KH350T4-2N 500.0 665.0 640 350
260-KH400T4-A 565.0 785.0 690 400
260-KH450T4-A 650.0 825.0 800 450
260-KH500T4-A 700.0 883.0 860 500
260-KH550T4-A 770.0 975.0 950 550
260-KH630T4-2N 1000.0 1400.0 1100 630
260-KH700T4-2N 1200.0 1450.0 1300 700
270 Model and technical parameters
VFD Model Input V
Power Capacity
KVA
Input Current
A
Output
Current A
Adaptive
Motor KW
270-PS11T4B
3 phase 380V
±15%
17.0 26.0 25.0 11
270-PS15T4B 21.0 35.0 32.0 15
270-PS18.5T4B 24.0 38.5 37.0 18.5
270-PS22T4B 30.0 46.5 45.0 22
270-PS30T4 40.0 62.0 60.0 30
270-PS37T4 57.0 76.0 75.0 37
270-PS45T4 69.0 92.0 90.0 45
270-PS55T4 85.0 113.0 110.0 55
270-PS75T4 114.0 157.0 150.0 75
270-PS93T4 134.0 180.0 176.0 93
270-PS110T4 160.0 214.0 210.0 110
270-PS132T4 192.0 256.0 253.0 132
270-PS160T4 231.0 307.0 300.0 160
270-PS185T4 242.0 350.0 340.0 185
270-PS200T4 250.0 385.0 380.0 200
270-PS220T4 280.0 430.0 420.0 220
270-PS250T4 355.0 468.0 470.0 250
270-PS280T4 396.0 525.0 520.0 280
270-PS315T4 445.0 590.0 600.0 315
270-PS350T4 500.0 665.0 640.0 350
270-PS400T4 565.0 785.0 690.0 400

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
7
280 Model and technical parameters
VFD Model Input V Power Capacity
KVA
Input Current
A
Output
Current A
Adaptive
Motor KW
280-FB7.5T4B-X
3 phase 380V
±15%
11.0 20.5 17 7.5
280-FB11T4B-X 17.0 26.0 25 11
280-FB15T4B-X 21.0 35.0 32 15
280-FB18.5T4B-X 24.0 38.5 37 18.5
280-FB22T4B-X 30.0 46.5 45 22
280-FB30T4B-X 40.0 62.0 60 30
280-FB37T4-X 57.0 76.0 75 37
280-FB45T4-X 69.0 92.0 90 45
280-FB55T4-X 85.0 113.0 110 55
280-FB75T4-X 114.0 157.0 150 75
280-FB93T4-X 134.0 180.0 176 93
280-FB110T4-X 160.0 214.0 210 110
280-FB132T4-X 192.0 256.0 253 132
280-FB160T4-X 231.0 307.0 300 160
280-FB185T4-X 242.0 350.0 340 185
280-FB200T4-X 250.0 385.0 380 200
280-FB220T4-X 280.0 430.0 420 220
280-FB250T4-X 355.0 468.0 470 250
280-FB280T4-X 396.0 525.0 520 280

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
8
2.4 Technical specification
Item Specification
Input
Rated voltage T4 series: 3 phase 380V, ±15%
Frequency 50/60Hz ±5%
Output
Voltage T4 series : 3 phase 0~380V
Frequency 0~3000Hz
Overload ability
G Type: 150% rated current for 1 minute, 180% rated current for 3
seconds;
P Type: 120% rated current for 1 minute, 150% rated current for 3
seconds.
Control performance
Control mode Open-loop vector control, V/F control, Torque Control
Start torque Open-loop vector control: 0.5Hz 180%,VF control: 0.5Hz 150%
Speed range Open-loop vector control: 1:200,VF control: 1:100
Speed control
precision Open-loop vector control: ±0.2%,VF control: ±0.5%
Torque control precision: ±5%, time: <20ms
Protection
function
25 types
protection
function
Including over-voltage, over-current, overheat, overload,
under-voltage, short circuit, ground fault, input and output default
phase, protect the frequency AC Drive running reliably all-round
Installation environment requirement
Ambient
temperature
-10 ~+40 (ambient temperature is within 40 ~50 , derating℃℃ ℃℃
use is required), not allow to contact direct sunlight.
Humidity Less than 90%RH, without condensation
Application
environment
Non (corrosive, flammable, explosive, dust absorbent material),all
kinds of lint does not accumulate.
Vibration Less than0.6G
Elevation 0~1000m, reduce the rated specification 10% when lift 1000m for
each.
Storage
temperature
-20~60℃

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
9
2.5 200-N Product Outline and Installation Aperture Size
2.5.1 200-N G0.4~G18.5KW Outline and Outer Size of Hang Machine Plastic Casing
AC Drive
VFD Model H W D H1 W1 Installation
aperture
Weight
(Kg)
200-G0.4T4B-N
170 100 140 160 90 5 1.8
200-G0.75T4B-N
200-G1.5T4B-N
200-G2.2T4B-N
200-G3.0/P3.7T4B-N
187 125 166 177 115 5 2.5
200-G3.7/P5.5T4B-N
200-G5.5/P7.5T4B-2N
248 160 184 239 150 5 4
200-G7.5/P11T4B-2N
200-G11/P15T4B-N
320 208 190 307 193 6 7.2200-G15/P18.5T4B-N
200-G18.5/P22T4B-N

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
10
2.5.2 200-N G22~G550KW Outline and Outer Size of Hang Machine Metal Casing AC
Drive
VFD Model H W D H1 W1 Installation
aperture
Weight
(Kg)
200-G22/P30T4B-2N
200-G30/P37T4B-2N
200-G37/P45T4-2N
420 270 215 404 160 7 15
200-G45/P55T4-N
200-G55/P75T4-N 605 300 290 582 200 8 48
200-G75/P93T4-N
200-G93/P110T4-N
200-G110/P132T4-N
650 340 330 630 200 10 52
200-G132/P160T4-N
200-G160/P185T4-N 830 500 376 806
180+
180 12 107
200-G185/P200T4-N
200-G200/P220T4-N
200-G220/P250T4-N
890 500 376 866
180+
180 12 126
200-G250/P280T4-N
200-G280/P315T4-N
200-G315/P350T4-N
1080 683 396 1050 250+
250 12 177
200-G350/P400T4-N
200-G400/P450T4-N
200-G450/P500T4-N
200-G500/P550T4-N
200-G550T4-N
1320 810 450 1290 280+
280 14 262

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
11
2.6 230 Series Ball Mill Special Purpose AC Drive Product Outline Drawing and
Installation Hole Size
Dashboard
Lower door panel
Rear door panel
Cover base
Rings
H
W
W1
D1
D

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
12
VFD Model H W D W1 D1 Installation
aperture
Weight
(Kg)
230-QM22T4B/Z-ET-A
800 400 250 380 160 10 30
230-QM30T4B/Z-ET-A
230-QM37T4/Z-ET-A
230-QM45T4/Z-ET-A
900 480 300 410 240 12 58
230-QM45T4/F-ET-A
230-QM55T4/Z-ET-A
230-QM55T4/F-ET-A
230-QM75T4/F-ET-A
1000 510 370 450 310 14 95
230-QM93T4/F-ET-A
230-QM110T4/F-ET-A
230-QM132T4/F-ET-A
1400 700 400 620 320 14 135
230-QM160T4/F-ET-A
230-QM185T4/F-ET-A
230-QM200T4/F-ET-A
230-QM220T4/F-ET-A
230-QM250T4/F-ET-A
1600 905 435 825 335 14 195
230-QM280T4/F-ET-A
230-QM315T4/F-ET-A
230-QM350T4/F-ET-A
1860 1040 450 970 375 14
275
230-QM400T4/F-ET-A
230-QM450T4/F-ET-A
330
230-QM500T4/F-ET-A
230-QM550T4/F-ET-A
1940 1360 500 940 380 14 700
230-QM630T4/F-ET-A

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
13
2.7 260 Series Engineering Type Vector AC Drive Product Outline Drawing and
Installation Hole Size
Dashboard
Lower door panel
Rear door panel
Cover base
Rings
H
W
W1
D1
D

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
14
VFD Model H W D W1 D1 Installation
aperture
Weight
(Kg)
260-KH30T4B-A
800 400 250 380 160 10 28260-KH37T4B-A
260-KH45T4-A
260-KH55T4-2N
900 480 300 410 240 12 45
260-KH75T4-2N
260-KH93T4-2N
1000 510 370 450 310 14 79260-KH110T4-2N
260-KH132T4-2N
260-KH160T4-2N
1400 700 400 620 320 14 117
260-KH185T4-2N
260-KH200T4-2N
260-KH220T4-2N
260-KH250T4-2N
260-KH280T4-2N
1600 905 435 825 335 14 166260-KH315T4-2N
260-KH350T4-2N
260-KH400T4-A
1860 1040 450 970 375 14
237
260-KH450T4-A
260-KH500T4-A
280
260-KH550T4-A
260-KH630T4-2N
1940 1010/
1360 500 940 380 14 650
260-KH700T4-2N

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
15
2.8 270 Series Movable crusher Special Purpose AC Drive Product Outline
Drawing and Installation Hole Size
2.8.1 270 Series 11~18.5KW Outline and Outer Size of Hang Machine Plastic Casing
AC Drive
VFD Model H W D H1 W1 Installation
aperture Weight (Kg)
270-PS11T4B
320 208 190 307 193 6 7.2270-PS15T4B
270-PS18.5T4B
2.8.2 270 Series 22~110KW Outline and Outer Size of Hang Machine Metal Casing
AC Drive

Chapter2 Specifications and Selection 200 Series General Purpose Vector AC Drive
16
VFD Model H W D H1 W1 Installation
aperture
Weight
(Kg)
270-PS22T4B
420 270 215 404 160 7 15270-PS30T4
270-PS37T4
270-PS45T4
605 300 290 582 200 8 48
270-PS55T4
270-PS75T4
650 340 330 630 200 10 52270-PS93T4
270-PS110T4
2.8.3 270 Series 132~400KW Outline and Outer Size of Hang Machine Metal Casing
AC Drive
Equipped with mounting eye nut
W
H
W
1
H
1
D
H
2
W
2
D
1

200 Series General Purpose Vector AC Drive Chapter2 Specifications and Selection
17
Model VFD H W DH1 H2 W1 W2 D1 Installation
aperture
Eye
nut
Weight
(Kg)
270-PS132T4
480 780 360 217+217 380 67+200*3
67 700 168 Ø12 M10
270-PS160T4
270-PS185T4
600 850 376 77+200*2
+77 500 102+200*3
+102 750 168 12 M10 28
270-P200T4
270-PS220T4
270-PS250T4
270-PS280T4
270-PS315T4
900 1055 450 127+200*3
+127 800
204.5+200*
3
+204.5
955 195 14 M12 79
270-PS350T4
270-PS400T4
2.9 280 Series Factory Explosion-proof AC Drive Movement Product Outline
Drawing and Installation Hole Size
7.5~18.5 AC drive outline drawing and outline size diagram
This manual suits for next models
118
Table of contents
Other CHINSC ELECTRIC DC Drive manuals
Popular DC Drive manuals by other brands

KEBCO
KEBCO COMBIVERT F5 Reference manual

KEBCO
KEBCO COMBIVERT G6 series Instructions for use

Delta
Delta MH300 user manual

Phase Technologies
Phase Technologies SD Series Operation & installation manual

Kieback&Peter
Kieback&Peter AM24 quick start guide

GFA
GFA ELEKTROMAT SI 35.30-40,00 installation instructions