SVF-MNSeriesFrequencyInverterOperationManual Chapter1SafetyandNotes
7
Don't connect any varistor or capacitor to the output terminals of the drive,
because the drive's output voltage waveform is PWM, otherwise tripping
or damaging of components may occur; in addition, don't install circuit
breaker or contactor at the output side of the drive.
G. Circuit breakers connected to the input/output of the drive
If contactor is connected between the input power supply and the motor,
Please don’t use contactor to control drive start-stop. If it must be done,
interval time should not less than one-hour. If frequently charging and
discharging, the life of the internal capacitance of the drive will be reduced.
If circuit breaker or contactor needs to be connected between output side
of the drive and the motor, be sure to operate these circuit breakers or
contactor when the drive has no output, to avoid damaging of the drive.
H. Using outside the range of rated voltage
The drive is unsuitable to be used out of the specified range of operation
voltage; otherwise, it may be damaged. If need, please use suitable voltage
regulation device.
I. Change from 3-phase to 2-phase
It is not recommended to change the drive from 3-phase input to 2-phase
input. Otherwise it will lead to failure or damaged.
J. Protection against lightning strike
There are transient surge suppressors inside the Drive which protects it
against lighting strike. Department for frequent thunder and lightning,
users should install the drive front-end protection.
K. Derating due to altitude
Derating must be considered when the drive is installed at high altitude,
greater than 1000m. Because of the thin air, the cooling effect of drive is
deteriorated. Please contact our technical advice in this case.
L. Special usage