1. Press the PROG/RUN key. This will cause the PASSWORD prompt
to appear (unless the password protection has been disabled), as
shown below:
THE MC1000 KEYPAD
PROGRAMMING THE MC1000 DRIVE
2. Use the Vand Wkeys to scroll to the correct password value
(the factory default password is 0019) and press ENTER. The
PROGRAM mode will be entered at the start of the parameter
menu. A cursor will highlight the parameter name.
3. Use the Vand Wkeys to scroll to the desired parameter and
press ENTER. The cursor will shift from the parameter name
to the parameter value, as the example below illustrates:
4. Use the Vand Wkeys to scroll to the desired parameter value,
and press ENTER to store the new value.
5. Press PROG/RUN to exit the PROGRAM mode.
PASSWORD 0000
CURSOR
ACCEL 30.0 SEC
CURSOR
ENTER
STOP > 20.00 HZ
START
STOP
ENTER FWD
REV
AUTO
MAN
PROG
RUN
MC1000 KEYPAD FUNCTIONS
Press the START key to start the drive. The START
key is only active in LOCAL mode.
Press the STOP key to stop the drive.
NOTE: The STOP key is active in both LOCAL and
REMOTE mode.
The STOP key is also used to reset faults. If the fault
condition has passed, pressing the STOP key will clear
the fault and return the drive to a STOP condition.
UP and DOWN ARROWS - Used to change the speed
setpoint in MANUAL mode, scroll through the
parameter menu, and change parameter values.
Toggles between FORWARD and REVERSE rotation.
NOTE: Parameter 27 - ROTATION must be set to FWD
& REV, and the drive must be in LOCAL mode for this
key to be active.
Toggles between AUTOMATIC (terminal strip) and
MANUAL (keypad) speed control.
NOTE: Parameter 28 - AUTO/MAN must be set to
BOTH for this key to be active.
Used to enter and exit the PROGRAM mode to set the
parameters.
Used for: toggling the display between SPEED, LOAD,
and MOTOR VOLTAGE; confirming new parameter
values; confirming AUTO and MANUAL speed control
selections; confirming LOCAL and REMOTE start/stop
mode selections.
Press and hold the ENTER key to activate the
AUXILIARY MODE, which consists of two displays
that cycle in one second intervals. One indicates
LOCAL/REMOTE mode,AUTO/MANUALmode, and
the speed reference source, and the other is an elapsed
time meter that indicates total run time.
START
STOP
ENTER
PROG
RUN
AUTO
MAN
FWD
REV
MC1000 DISPLAYS
Shown below are examples of MC1000 displays. To scroll through the
SPEED, LOAD, and MOTOR VOLTAGE displays, press and release
the ENTER key.
Press and hold the ENTER key to activate the AUXILIARY MODE
display, which indicates the control source (LOCAL, REMOTE, or
SERIAL), AUTO or MANUAL mode, and the speed reference source.
An example is shown below (IDC = 4-20 mA signal):
LOCAL -- AUTO -- IDC
CONTROL
SOURCE
AUTO/MAN
MODE
SPEED
REFERENCE
SOURCE
AUXILIARY MODE
DISPLAY
PRESS
& HOLD
ENTER
SPEED DISPLAY
LOAD DISPLAY
MOTOR VOLTAGE
DISPLAY
○○○○
ENTER
ENTER
RUN > 85% LOAD
DRIVE
STATUS
PERCENT
LOAD
RUN > 460 VAC
DRIVE
STATUS
MOTOR
VOLTAGE
RUN > 60.00 HZ
DRIVE
STATUS
SPEED
SETPOINT
SPEED
UNITS
○○○○ ○○○○ ○○○○
ROTATION DIRECTION
(“>” = Forward, “<” = Reverse)