
BCD-317W/351W (external display) Service Manual
16
the door is opened, close the door for cooling 10 minutes, and then open the
fridge door, hold down the door lamp switch, checking whether there is cool
air blown out of the fridge air outlet.
d. Cut off power supply, replace the main board, power on the system when the
door is opened, close the door for cooling 10 minutes, and then open the
fridge door, hold down the door lamp switch, checking whether there is cool
air blown out of the fridge air outlet.
After the maintenance is completed, assemble all components, power on the
system to perform Step a operations, ensuring there is cold air blowing out of the
cold room, and then cut off power supply before powering it on again.
(5) The refrigerator is not cooling.
Cut off power supply, remove the electrical box cover, check whether the
terminals on the main board are properly connected, insert them well again, and
then power on the system when the door is opened, wait for 10 minutes to
observe whether the refrigerator compressor can be started. If not, refer to Item
(2); and if yes, touch the left and right-side plates by hand to check whether they
are hot or not. If not hot, it is judged to be the refrigerant leakage fault, then
conduct vacuum pumping and charge the refrigerant again.
(6) The refrigerator air fan is not running.
a. Cut off power supply, remove the electrical box cover, check whether the
terminals on the main board are properly connected, insert them well again,
power on the system, hold down the combination keys of ‘Freezer’ and ‘OK’
for 5 seconds to enter the maintenance program; turn the fan on, open the
freezer door, and place your hand on the air duct to check if there is cool air
blown out.
b. Cut off power supply, remove the freezer air duct assembly, check whether
the terminals are properly connected, and whether there is such interference
as ice, wire harness or other foreign matter. If the terminals are loose or
detached, reconnect them well; if there is ice, perform the maintenance
program first to confirm whether the fan is in good condition or not. If yes,
refer to the operation of Item (7) ; and if there is the wire harness or foreign
object interference, reshape the wire harness or remove the foreign object.
Then, power on the system, hold down the combination keys of ‘Freezer’ and
‘OK’ for 5 seconds to enter the maintenance program, turn on the fan,
checking whether the fan can be started normally. If the fan cannot start,
replace the freezing air duct assembly, and enter the maintenance program
again to check whether the fan can be started normally.
c. Replace the main board, power on the system to enter the maintenance