Clear Water SC27P User manual

Ozone Systems
Installation & Operation Manual
SC27P
Corona Discharge Ozone Generator
Tested and certified by
WQA to NSF/ANSI 50 as a
component only.
Testedand certified by
WQAto NSF/ANSI 50 as a
componentonly.
ClearWater Tech, LLC.
Integrated Ozone Systems
850-E Capitolio Way, San Luis Obispo, Ca 93401 • 805-549-9724 • Fax: 805-549-0306 • E-mail: service@cwtozone.com • www.cwtozone.com
Copyright © 2005 -ClearWater Tech, LLC • Reproduction of any kind is prohibited • LIT135 • REV093010

1
THEORY OF OPERATION/PRODUCT DESCRIPTION CHAPTER 1
ClearWater Tech ozone systems are designed for safe, effective use in a variety of water treatment applications. The
SC27P ozone generator have been tested and certified by the Water Quality Association according to NSF/ANSI 50. Each
complete, integrated system may include the following components required for reliable, efficient ozone production and
can be divided into four general segments:
• Air preparation system • Ozone generator • Ozone injection/contacting • Ozone destruct
Air Preparation System
The ClearWater Tech SC27P ozone generator requires a source of clean, dry, oil-free, oxygen-enriched air for effective
ozone production. To meet that need, the built-in air preparation system employs pressure swing adsorption (PSA)
technology with an oil-less compressor to increase the concentration of oxygen and reduce the moisture content in the
feed gas (the air supplied to the ozone generator). This substantially improves the output capability of the ozone generator
and prevents premature failure of key internal components. These air preparation systems deliver 90%+/-3% oxygen
purity at -100°F dew point and at very low pneumatic pressures, minimizing noise and reducing compressor wear.
The air preparation system affects ozone production in grams per hour and more importantly ozone concentration, also
known as “percent by weight.” Since ozone is produced with oxygen, the greater the percent of oxygen that enters the
ozone generator will produce more grams per hour and concentration of ozone. Since the SC27P ozone generation system
incorporates PSA oxygen concentrator it will yield the highest grams per hour at the highest concentrations. Greater ozone
concentration equates to higher solubility of the ozone gas in solution, which will yield a greater oxidation potential.
Ozone Generator
The ClearWater Tech SC27P self-contained pressurized ozone generator is designed to supply high concentrations of
ozone gas (up to 10%) at 10 PSI. The oxygen feed gas produced by the air preparation system is supplied to the ozone
generator, which flows through the built-in flow meter. A stainless steel needle valve (located under the SC27P), is used
to maintain optimum pneumatic parameters inside the ozone reaction chambers. After this point the vacuum created at the
ozone injector draws the ozone gas into the water line. The ozone generator is equipped with a pressure switch, which
prevents operation if pressure within the reaction chambers drops below 9 PSI.
As the feed gas enters the fused, thermally protected reaction chambers inside the ozone generator, some of the oxygen
molecules are split while passing through the high voltage electrical field (the “corona”), forming single oxygen atoms
(O1). These oxygen atoms then recombine with other oxygen molecules in the air stream, forming ozone. The modular,
multiple reaction chamber design allows the ozone generator to keep working even if one of the chambers requires
service. Depending on the application, the ClearWater Tech ozone generator may be interlocked with an ORP controller,
PPM controller, pressure switch, timer or circulation pump.
Booster Pump Ozone Injector
Water Flow Off Gas
Vent Optional Destruct System
Ozone Generator Ozone
Destruct
Unit
Water Trap
Shown: ClearWater Tech SC27P Ozone System Contact Vessel

Theory of Operation/Product Description (continued)
2
Ozone Injection/Contacting
The ozone injector serves two purposes: One, it creates the vacuum
required to safely draw the ozone gas from the ozone generator and
two, it provides a means by which the ozone gas can become
dissolved in water. A very dynamic injection process is required to
effectively dissolve ozone in water.
ClearWater Tech injection systems use only Mazzei® injectors for
maximum mass transfer efficiency. The injector produces a
cavitation effect, enabling the ozone gas to join the water stream in
the form of extremely tiny bubbles. These bubbles must be as small
as possible in order to increase the ratio of bubble surface area to
the amount of ozone entering the water.
Depending on the application and the water treatment goals, a ClearWater Tech contacting system may also be required.
Some oxidation reactions take place so quickly that they are limited only by the rate at which the ozone is dissolved in the
water. Other reactions, such as disinfection, may require that proper ozone residual be maintained for a specific amount of
time. A correctly-sized contact vessel is used for this purpose.
Ozone Destruct
The ClearWater Tech off-gas destruct systems, consists of two components -the ozone destruct unit (a heated chamber
filled with manganese dioxide and copper oxide) and a water trap. Used in conjunction with a ClearWater Tech off gas
vent, the ozone destruct system is an effective way to vent the contact vessel(s) when it is impractical to send the off gas
to atmosphere or reintroduce it to the water.

3
SAFETY INFORMATION CHAPTER 2
SAFETY WARNINGS
Two aspects of ClearWater Tech ozone generators represent potential dangers –ozone gas and high voltage electricity.
OZONE GAS -WARNING: HIGH CONCENTRATIONS OF OZONE GAS ARE DANGEROUS
TO HUMANS. LOW CONCENTRATIONS CAN CAUSE IRRITATION TO THE
EYES, THROAT AND RESPIRATORY SYSTEM.
This ClearWater Tech corona discharge ozone
generator is designed to operate under a pressure
condition. While safety precautions have been taken,
entering the equipment area should be avoided if ozone
gas is detected. Ozone has a very distinctive odor and is
detectable at very low concentrations (0.02 ppm), which
is far below OSHA’s maximum permissible exposure
level of 0.1 ppm.
HIGH VOLTAGE -WARNING: CLEARWATER TECH OZONE GENERATORS OPERATE
AT HIGH VOLTAGE. DO NOT TAMPER WITH OR DELIBERATELY
BYPASS THE COVER OR SAFETY SWITCHES BUILT INTO THE
OZONE GENERATOR UNLESS INSTRUCTED TO DO SO BY THIS
MANUAL. IF CONTACT IS MADE WITH OPERATING HIGH VOLTAGE
COMPONENTS, ELECTRIC SHOCK WILL OCCUR.
ClearWater Tech corona discharge ozone generators take line voltage and convert it to 48 VDC. A high voltage
transformer then boosts the voltage. While each ozone generator has a door switch and other safety interlocks, proper care
must be used by a qualified electrician when making any internal adjustments or performing any maintenance procedures.

4
IMPORTANT SAFETY INSTRUCTIONS
When installing and using this electrical equipment, basic safety precautions should always be followed, including the
following:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. SAVE THESE INSTRUCTIONS.
3. All electrical connections should be made by a licensed, qualified electrician.
4. Before attempting any electrical connections, be sure all power is off at the main circuit breaker.
5. Install all electrical equipment at least five feet from any open body of water using non-metallic plumbing.
6. Install check valves and a vacuum break to prevent water from contacting the electrical equipment.
7. The electrical supply for this product must include a suitably rated switch or circuit breaker to open all
ungrounded supply conductors to comply with Section 422-20 of the National Electrical Code, ANSI/NFPA
70-1987. The disconnecting means must be readily accessible to the operator(s) but installed at least five
feet from any open body of water.
8. Be sure to bond (ground) the system using the copper-bonding lug on the bottom of the ozone generator.
The system should be bonded with solid copper wire conforming to all local, state and national electrical
codes.
9. The system should be sized appropriately for its intended use by a qualified professional familiar with the
application. This equipment must be validated by the manufacturer for its intended use; failure to do so
may void the warranty.

5
INSTALLATION PROCEDURES - Getting Started CHAPTER 3
Unpacking
Compare the ozone system equipment received to the packing list provided. Before beginning any
installation procedures, thoroughly inspect all components for damage. If damage is noticed,
promptly notify the freight carrier and request an on-site inspection. Inspect all packing materials
for small parts before discarding. Inspect all plumbing, fittings and tubing for packing material
that may have become lodged in openings.
Equipment Placement
• When placing the ozone system components in the equipment room, make sure to consider safety, maintenance
requirements, local building and fire codes, etc. The components should be easily accessible by the operators,
including equipment access doors and electrical hook-up boxes. All meters, gauges, indicator lights, and switches
should be visible and accessible. Dimensional drawings of each air preparation system and ozone generator are
included in Section A of the Appendix.
• The SC27P should be located as close as possible to the point of ozone injection. Ozone is an unstable gas and
will begin reverting back to oxygen very quickly. To determine the most favorable ozone injection point, the
following items should be considered:
• Located downstream of all other existing water system components.
• Located upstream of the residual sanitizer injection point (if so equipped).
• In a Sidestream plumbing configuration (see Figure 4-1) with recirculation, the pH adjustment
chemical injection point must be located downstream of the residual sanitizer injection point (if so
equipped).
• In a Full Flow plumbing configuration (see Figure 4-2) without recirculation, locate downstream of the
pH adjustment chemical injection point.
• Adequate protection from weather, dust and excessive heat.
• Like any electronic component, performance and longevity is enhanced by favorable operating conditions. Also,
since ozone generator is air-cooled, a relatively dust-free, well-ventilated area is required. No caustic chemicals
should be stored in the area surrounding the equipment. A minimum clearance of six inches from the vents on
either side of the ozone generator is required.
• The equipment is heavy and requires proper support. Therefore, a clean, dry, level vertical surface should be
provided for the SC27P. The system mounting bar should be securely fastened to the surface using the mounting
holes provided. Hang the SC27P from the wall mounting bar and level system on the wall with the leveling feet
provided on the backside of the system.
• The SC27P system is designed for specific voltage requirements, withstand typical outdoor elements and frequent
(though not constant) wash down, though should not be subjected to outdoor extremes including contact internally
with water and/or temperature extremes. Therefore, the equipment must be installed in an environment consistent
with the following operating parameters:
• Ambient temperature range: 20°F to 95°F continuous. If the temperature around the equipment
consistently exceeds 95°F, additional air-cooling must be provided.
• Humidity: 0 –90% relative humidity, non-condensing environment
• Line voltage: +/-10% of rated input
Note: Equipment installed in extreme environmental conditions will void manufacturer's warranty.
• Allow room for the peripheral equipment (booster pump, injector manifold, contact vessel, etc.).

6
INSTALLATION PROCEDURES – Plumbing CHAPTER 4
The ozone system should be plumbed using either a sidestream or full flow configuration. The sidestream
loop method takes a portion of the water from the main flow (see Figure 4-1) and diverts it into a
sidestream downstream of the filter (if so equipped). Ozone is introduced into the sidestream water and is
allowed contact time with the water before it is returned to the main flow at a point downstream of all other
equipment (heaters, solar panels, etc., if so equipped) in the circulation system. A booster pump is usually employed to
compensate for the flow restriction caused by the sidestream loop and the injector manifold. If a halogen-type residual
sanitizer is utilized, its injection point should be as far downstream as possible from the point at which the sidestream
water returns to the main flow. In a full flow configuration, the same system components are usually involved and appear
in the same order with respect to the direction of flow. However, all the water in the main flow is allowed contact time
with the ozone (see Figure 4-2). A booster pump may be necessary to maintain proper flow requirements. If employed, the
booster pump is located upstream of the point at which the ozone injector manifold is installed.
NOTES:
• Adequate use of unions and isolation valves is
strongly recommended to facilitate maintenance
and repairs.
• Use Schedule 80 PVC for all plumbing connections
wherever possible. Plumbing size requirements
are dictated by the water flow characteristics of
the system.
• Make sure to use proper plumbing practices and
secure all plumbing and system equipment
according to local codes.
• Ozone is a powerful oxidizer and will degrade certain
materials. Use ozone-compatible plumbing materials
for section(s) of the system that will come in contact
with ozone dissolved in water. The following is a list of
materials that are compatible with ozone:
• PVC • Stainless Steel (300 series)
• CPVC • Viton
• Kynar • EPDM
• Teflon • Concrete
• Depending on the application, other components (psi
gauge, flow meter, etc.) may be installed to assist in
monitoring system parameters.
Step 1: Arrange the ozone system equipment (booster pump, injector and contact vessel) according to mechanical print
or as dictated by equipment layout and serviceability considerations. Do not secure booster pump and contact
vessel to housekeeping pads at this point. Dry fit plumbing as appropriate to insure proper fit and location
before making permanent connections.
Step 2: Install a tee or plumbing saddle into the main water line after the filter (if so equipped) and before the flow
diversion mechanism. The purpose of the mechanism is to restrict water flow so water is diverted into the
sidestream (see Figure 4-1). If such a mechanism is not present in the system (such as a heater bypass valve,
etc.), it will require installation of a valve (butterfly, gate or ball) or a flow controller.
Step 3: Plumb a line from the tee or plumbing saddle to the booster pump. For serviceability of the equipment in the
sidestream loop, be sure to install an isolation valve between the tee or saddle and the booster pump.
Step 4: Plumb from the booster pump to the injector manifold. Make sure to note the correct direction of flow, indicated
by a blue arrow on the inlet side of the manifold body. The check valve assembly is strapped to the manifold
using wire ties. Remove the assembly; using Teflon® tape; install it onto the top opening of the injector.
Step 5: Plumb from the injector manifold to the inlet side of the contact vessel. To reduce possible backpressure to the
injector, minimize the number of elbows between the injector manifold and contact vessel. The contact vessel is
a specified size, determined by water flow requirements. ClearWater Tech contact columns and the 30, 40, 80,
and 120-gallon contact tanks have inlet and outlet fittings on the bottom of the vessel and are designated with
arrows showing the direction of flow. Note: The inlet and outlet arrows on the contact tanks are under the
base of the tank. The inlet on the 264, 463 and 850-gallon tanks is located at the top with the outlet at the
bottom.
Step 6: Using a tee or plumbing saddle, plumb from the outlet of the contact vessel back into the main water line. For
serviceability of the equipment in the side stream loop, be sure to install an isolation valve between the outlet
fitting on the contact vessel and before returning to the main water line.
Step 7: Secure the booster pump and contact vessel to solid mounting surfaces using appropriate hardware and
according to local codes. If installing a ClearWater Tech contact column, use a ClearWater Tech contact

Plumbing (continued)
7
column mounting kit and install according to the instructions below. If installing a contact tank, secure to a solid
horizontal surface using mounting flange or feet.
Step 8: Install the contact vessel venting system into the top of the vessel. If using the ClearWater Tech contact column,
the vent kit supplied includes fittings, a control valve and Teflon® tubing. The contact tank venting system
includes an air relief valve, fittings and a length of Teflon® tubing. Depending on conditions, the vented gas
may be directed to an ozone destruct system, to atmosphere or to the low-pressure side of the water system.
Note: Do not direct the tubing to the suction side of any pump in the system.
Contact Column Installation (if so equipped)
Step 1: Make sure the following hardware items are included in the contact column mounting kit:
• 'L' bracket
• 1/2” concrete anchors
• 6” clamp assembly
• Unistrut bar
• Protective end cap
• Mounting hardware
Step 2: Referring to Figure 4-3, mark the two holes for mounting the 'L' bracket to the wall. The bracket should be
located so that the 6” clamp assembly will be approximately 12” from the top of the contact column. Drill a
1/2” hole at each of the marks, about 3 1/2” deep. Insert a concrete anchor into each hole with the threaded end
facing outward. Slip the 'L' bracket over the threaded ends of the anchors, followed by a washer for each
anchor. Secure the bracket to the wall by threading a nut onto each anchor and tightening.
Step 3: Cut the unistrut bar to the desired length and attach it to the 'L' bracket using hardware provided.
Step 4: Slip the two sides of the 6” clamp into the unistrut bar and then around the contact column. Tighten the retaining
bolt, securing the contact column to the unistrut bar.
Step 5: Slip the protective end cap over the exposed end of the unistrut bar.
Sidestream Plumbing Installation Diagram
Figure 4-1
Flow Diversion
Mechanism
Filter Isolation Isolation
Valve Valve
Booster Ozone Injector
Pump
Bypass Valve
Contact
Vessel
Isolation
Service Loop Valve
Isolation Isolation
Valve Ozone Injector Valve
Booster Bypass
Pump Valve
Contact
Vessel
Full Flow Plumbing Installation Diagram
Figure 4-2

Plumbing (continued)
8
Column
Column Flange Bolts &
Flange Washers(8 ea.)
Diffuser
Riser Tube
Base Flange Gasket
Base Flange Nuts &
Washers (8ea.)
Contact Column Exploded View
Figure 4-4
Contact Column Installation Diagram
Figure 4-3
6” Clamp Assembly Bolts, nuts &
with bolt & Nut washers (2ea.)
Unistrut
(cut to length)
Unistrut “L” Bracket
Protective
End cap Concrete Anchors
with nuts &
washers (2ea.)

9
INSTALLATION PROCEDURES – Electrical CHAPTER 5
The SC27P ozone generation system is designed to
hard wire to the main power source with specific input
voltage requirements. All possible pre-wiring has been
completed at the factory. Logic Schematics have been
provided in the Appendix-Section C.
• All electrical connections should be made by a
licensed, qualified electrician. All local, state and
national codes must be observed.
• Make sure all power is off at the main circuit
breaker before making any electrical connections.
Step 1: Conforming to all local, state and national electrical codes, ground the ozone generator to a true earth ground.
Use solid copper bonding wire (usually #8 AWG) from the copper-bonding lug located on the bottom of the
ozone generator to the grounding point.
Step 2: Main Power: Wire main power to the Electrical Hook-up Box located on
the left side of the SC27P with specified input voltage, either 120VAC
60Hz (L1-Black and Neutral-White) or 220VAC 50Hz (L1-Red and
L2/Neutral-Black), single phase (1ø). Using #12 AWG, wire L1 main
power to terminal #1. Using #12 AWG, wire a system neutral to terminal #4. Using #12 AWG, wire a system
ground to terminal #6. See Figure 5-1 for Electrical Hook-up Box Terminal Strip Diagram. See Appendix-
Section A for Electrical Terminal Strip location.
Step 3: MCI (Motor Control Interlock) Power: The MCI is a fused factory-wired interlock, which may be used to
energize or de-energize the SC27P with other electrical component(s) via an input signal. If the MCI is used,
remove the factory-wired jumper between L1, terminal #1 and the MCI, terminal #2, of the Electrical Hook-up
Box Terminal Strip. Using #18 AWG, wire a 120VAC power signal (1 amp max) for a 120VAC 60Hz system
or a 220VAC power signal (1amp max) for a 220VAC 50Hz system to the top of the MCI, terminal #2. If so
required, a MCI Neutral may also be wired, using a #18 AWG wire to terminal #5. See Figure 5-1 for
Electrical Hook-up Box Terminal Strip Diagram. See Appendix-Section A for Electrical Terminal Strip
location. Note: The SC27P will not function without an input signal to the MCI, terminal #2.
Step 4: External Contactor Signal: The SC27P is equipped with an external contactor output signal. The output
voltage will be 120VAC (2 amp max) for a 120VAC 60Hz system or 220VAC (2 amp max) for a 220VAC
50Hz system. Using a #18 AWG, wire from the External Contactor, terminal #3 of the Electrical Hook-up Box
Terminal Strip, to the coil side of a contactor. If so required, an External Contactor Neutral may also be wired,
using a #18 AWG wire from the Auxiliary Neutral, terminal #5 to the coil side of the contactor. See Figure 5-1
for Electrical Hook-up Box Terminal Strip Diagram. See Appendix-Section A for Electrical Terminal Strip
location.
Step 5: External Loop: The external loop is a true dry contact interface. Note: The term ‘dry contact’ means that
this loop does not supply output nor accept input voltages. Warning: Supplying voltage to the external
loop will cause damage to the ozone generator and void warranty. Under normal operation, the external
loop will effectively interrupt the ozone output when the loop has lost continuity; this will also illuminate
“External Loop” LED and turn off the “Ozone Output” LED(s) located on the control panel of the system (see
Appendix-Section A). Note: When the external loop has lost continuity main power to the ozone
generator will remain “ON” giving power to the rest of the systems components. When continuity is
present through the external loop, ozone output will continue. This continuity will effectively turn “OFF” the
“External Loop” LED and will again illuminate the “Ozone Output” LED(s).
The external loop is located on the left side of the system, positions #9 and #10 on the terminal block (see
Appendix -Section A), and can be interfaced to any control device, i.e., pressure switch, vacuum switch, flow
switch, float switch, ORP controller, PPM controller, or timer. If the control device used supplies an output
voltage a single pole single throw (SPST) normally-open relay may be used to create a dry contact interface
(see Figure 5-2, “External Loop Electrical Interface”).
Step 6: Ozone Output Control: The SC27P ozone generator is equipped with two options for controlling the ozone
output. The first option is a Manual 0-100% Ozone Output Control and the second is a Remote 4-20mA
Control signal. See Appendix-Section A for the location of the manual ozone output control knob and remote
4-20mA control leads (orange and purple). An LED located on the systems control panel indicates the ozone
Power Consumption
Input
Voltage
120VAC
60Hz
220VAC
50Hz
SC27P
9 amps
4.5 amps

10
output control selected, see, Start-Up and Calibration Procedures, Figure 7-1A for LED function and
Appendix-Section A for LED location.
1. Manual Ozone Output Control: Turning the control knob counterclockwise will decrease the ozone output down to
0% while turning the knob clockwise will increase the ozone output up to 100%. The ozone output level is indicated
by the “Ozone Output” LED(s) on the control panel of the ozone generator, see Start-Up and Calibration Procedures,
Figure 7-1A for LED function and Appendix-Section A for LED location.
2. Remote 4-20mA Control: The ozone generator will automatically sense the 4-20mA input signal and override the
setting of the manual ozone output control. Based on the 4-20mA signal, ozone output will increase or decrease,
4mA = 0% ozone output, 20mA = 100% ozone output. The “Ozone Output” is indicated by the LED(s) on the
control panel of the ozone generator, see Start-Up and Calibration Procedures, Figure 7-1A for LED function and
Appendix-Section A for LED location. Note: If the remote 4-20mA signal fails or is missing, the system will
default to the manual ozone output setting. Check and adjust the manual ozone output control knob to avoid
over-ozonation. Following the directions in the manual of the 4-20mA control device, wire the negative (-) input
signal to the Purple wire of the ozone generator and the positive (+) input signal to the Orange wire of the ozone
generator.
Electrical Hook-Up Box Diagram
Figure 5-1

11
External Loop Electrical Interface
Figure 5-2
120V
COIL
N
Power from ORP, PPM,
pump or timer
L1
Interface Relay
External Loop
120VAC Signal
240VAC Signal
L1
L2
240V
COIL
Interface Relay
Power from ORP, PPM,
pump or timer
External Loop

12
Vacuum Break Detail
Figure 6-2
INSTALLATION PROCEDURES – Pneumatic CHAPTER 6
This section outlines the steps required to complete the
ozone system pneumatic hook-ups. The system
components include the air preparation system, ozone
generator, vacuum break, and ozone injector manifold
(see Figure 6-1). The air preparation system provides the
ozone generator with a source of dry, oil-free oxygen-
enriched air (90% +/-3% oxygen purity at -100˚F dew
point). The air is drawn from the ozone generator (where
ozone is produced from the oxygen in the air stream) and
through the vacuum break by the suction created at the
ozone injector manifold.
Figure 6-1
Vacuum break-to-injector manifold
The SC27P ozone generator incorporates a ClearWater Tech vacuum break, which provides a positive atmospheric
“break” between the ozone injector manifold and the SC27P system, preventing water from flowing back into the ozone
generator should the venturi check valve fail. If the check valve at the venturi begins to leak or fails completely, vacuum
is interrupted and water will flow toward the ozone generator. With the incorporated vacuum break the water will flow
down the riser tube (away from the ozone generator) and out to drain, protecting
the SC27P from potential water damage. All pneumatic connections have been
made between the ozone generation components of the SC27P and the vacuum
break. The only pneumatic field connections required are between the vacuum
break ozone outlet fitting and the injector manifold. Follow the steps outlined
below for this procedure, see Figure 6-2.
Step 1: Remove the vacuum break’s stainless steel cover located on the right
hand side of the SC27P.
Step 2: Remove the Fill Port Cap and fill the Riser Tube with clean water (no
particulate matter) to the fill level line of the overflow tube.
Step 3: Re-install the Fill Port Cap, hand tight. Note: Do not over tighten as
damage to PVC fittings may occur.
Step 4: Connect one end of a suitable length of Teflon® delivery line to the
vacuum breaks’ ozone outlet. The other end of the Teflon® delivery
line will be attached to the fitting threaded into the top of the check
valve assembly located on the injector manifold, do not attach this line
until directed in Chapter 7 of the “Start-up and Calibration Procedures”.
Booster Pump Ozone Injector
Water Flow
Ozone Generator
Ozone Delivery Line
Vacuum Break
Shown: ClearWater Tech SC27P Ozone System. Vacuum
break stainless steel cover removed for clarity.
Fill Port Cap
Ozone Inlet
Drain Holes
Ozone Outlet
Overflow Tube
Fill Level
Riser Tube
Flapper Check
Valve

13
START-UP & CALIBRATION CHAPTER 7
The previous sections of this manual have involved comparatively static procedures –making
electrical and pneumatic connections, fitting pipe, etc. This section involves the dynamic process of
starting up and balancing the components of the ozone system, including initiating water flow, making
air and water flow adjustments, etc.
Maximum performance and reliability is achieved when the prescribed air flow is maintained at the ozone generator while
the system is operating under pressure. Air from the air preparation system is flowing through the ozone reaction
chambers under pressure, and from the ozone generator under a slight vacuum (created by the ozone injector manifold).
The change from pressure to vacuum occurs after the stainless steel ozone outlet needle valve on the ozone generator.
SC27P Ozone Generation System and Injection Manifold
Warning: Disconnect the External Loop dry contact from the ozone generator while performing all start-up
procedures. Failure to do so may result in ozone escaping to atmosphere.
Step 1: Make sure all isolation valves in the ozone water system are open (Figures 4-1 or 4-2 show recommended
isolation valve locations).
Step 2: Apply main power to the SC27P. Switch the main power switch to the “ON” position. At this time the SC27P
will be powered up, the air preparation system and cooling fans should be “ON” and power should be present
to the External Contactor output signal. If the External Contactor output signal is interlocked to a booster
pump, the booster pump should be “ON”. Note: Ozone will not be produced until the “External Loop” is
in place and at least 9 PSI present at the PSI gauge located on the control panel.
Step 3: Start-up hydraulics. Allow the water in the system to reach hydraulic equilibrium (contact vessel full, off-gas
vent operating, etc.) and observe for plumbing leaks. Note: Water flow must be established through the
main water pump and the ozone system booster pump (if so equipped).
Step 4: Close the ball valve on the injector manifold about half way.
Step 5: Using your thumb, check for the presence of vacuum (suction) at the
ozone injection manifold check valve assembly or use a ClearWater
Tech vacuum test assembly to check vacuum at the injector port. If no
suction is present, continue to close the ball valve on the injector
manifold until vacuum is detected. If using the vacuum test assembly,
check the VAC/PSI gauge for vacuum. If the needle is in the red zone
on the pressure (PSI) side of the gauge, gradually close the ball valve on
the injector manifold until the needle moves into the green zone. If the
needle is in the red zone on the vacuum (in.Hg) side of the gauge,
gradually open the ball valve on the injector manifold until the needle
moves into the green zone. While vacuum is in the green zone you must
be able to achieve proper SCFH (Standard Cubic Feet per Hour) of air flow (see the “Pneumatic Operating
Parameters” chart for venturi SCFH required, Figure 7-2).
Step 6: The air preparation system air flow must be set to “atmospheric pressure” prior to final start-up of the SC27P.
Step 1: Check to make sure the compressor of the air preparation system is operating.
Step 2: Check the system PSI gauge for pressure, located on the control panel. If pressure is registered on
the PSI gauge open the stainless steel needle valve by turn it counter clockwise so that no pressure is
registered on the gauge. See Appendix-Section A for PSI gauge and stainless steel needle valve locations.
Step 3: Using the air flow gauge adjustment valve on the control panel, adjust the SCFH air flow according
to the “Air prep system air flow” specifications outlined in Figure 7-2.
Step 7: Connect the Teflonozone delivery line from the vacuum break to the ozone inlet fitting located at the ozone
injection manifold check valve assembly.
Step 8: Adjust the stainless steel needle valve located at the bottom the ozone generator (see Appendix-Section A)
clock-wise, adjusting the system backpressure to 10 PSI. Check the PSI gauge on the control panel, which
measures this backpressure. If there is insufficient backpressure the needle valve may be closed slightly;
similarly, if there is too much backpressure the valve may be opened slightly. Due to the pressure switch
installed, the PSI gauge must achieve 9 PSI before ozone will begin production.
Step 9: By setting the air preparation SCFH (step 6) and system backpressure PSI (step 8), the air flow gauge on the
control panel will read in CFH rather than SCFH. At this point the air flow meter becomes passive and should

Start-Up and Calibration (continued)
14
read in the range indicated on the “Ozone Generator Air Flow” line of the “Pneumatic Operating Parameters”
chart, Figure 7-2. Note: When the system is under normal operation, the “Air Prep System Air Flow” set
point will drop from the initial setting due to the system being under backpressure. DO NOT RE-
ADJUST THE AIR FLOW GAUGE ADJUSTMENT VALVE.
Step 10: Perform a final check of all air connections from the SC27P to the ozone injector manifold. Repair leaks as
required. Check all system water connections, including the ozone injector manifold, vacuum break and
contact vessel. Repair leaks as required. Note: The check valve at the ozone injector manifold may make a
humming noise. This is normal.
Step 11: Reconnect the External Loop connector to the ozone generator. Note: The Ozone LED(s) will not illuminate
and ozone will not be produced until the External Loop has been replaced.
Step 12: Observe indicating LED(s), on the control panel of the SC27P and adjust the manual ozone output control
knob to desired level setting. See Figure 7-1 A-C for proper LED function and Appendix-Section A for
location of the LED’s.
SC27P –Control Panel LED Function Figure 7-1A
LED
Function
SC27P LED Display
System Power
Main Power is “ON” to the SC27P, when LED is Illuminated
Pressure
The SC27P has sufficient pressure, when LED is Illuminated
Motor Control
Interlock (MCI)
The MCI is energized, when LED is illuminated
External Loop
The External Loop has continuity through it when the LED is not
illuminated, which indicates ozone is being produced. The External
Loop does not have continuity, when the LED is illuminated, which
indicates no ozone production.
Manual Control
Ozone output is being controlled by the Manual Ozone Output Control,
when LED is illuminated
Remote 4-20mA
Control
Ozone output is being controlled by an External 4-20mA Control signal,
when LED is illuminated
Ozone Output
Level
The ten LED’s represent 0-100%, minimum to maximum ozone output.
Each LED is equal to 10% output. These LED’s can be adjusted with
the manual ozone output control knob located on the control panel of
the SC27P or automatically with a remote 4-20mA control signal.
Drive 1 and Drive
2 -Power
Power is being sent to the high voltage Drive board, when the LED is
illuminated
Drive 1 and Drive
2 -Fault
When illuminated, this LED indicates that there is a fault with the drive
module or the Ozone Reaction Chamber. If this LED is illuminated, refer
to the Troubleshooting Guide. Notes: Upon startup, the fault LED
will remain illuminated for 30 seconds before ozone is produced
and the ozone output LED’s will not be illuminated. If the drive
module goes to a fault condition, the drive board will restart every
30 seconds. If the fault is not remedied the drive module will
continue to go into a fault mode. When the drive module is in fault
mode ozone will not be generated.
OZONE GENERATOR STATUS
SYSTEM POWER
PRESSURE
MOTOR CONTROLLED
INTERLOCK (MCI)
EXTERNAL LOOP
OZONE OUTPUT CONTROL
MANUAL CONTROL
REMOTE 4-20mA CONTROL
MAXIMUM OUTPUT
OZONE
OUTPUT
LEVEL
MINIMUM OUTPUT
GENERATOR DRIVE STATUS
GENERATOR DRIVE 1
POWER
FAULT
POWER
FAULT
GENERATOR DRIVE 2

Start-Up and Calibration (continued)
15
SC27P -Ozone Generator Drive Board LED Function Figure 7-1B
LED
Function
12V MAIN
POWER
When illuminated, this “Green” LED indicates that main power is supplied to the drive module up to the “on board”
fuse of the drive board.
XFMR
POWER
When illuminated, this “Green” LED indicates that 48V Buss power is available to the drive module transformer
(XFMR) from the “on board” fuse to the drive transformer.
OZONE
OUTPUT
The “Amber” ozone output LED will illuminate when ozone is being generated. The LED will also pulse as the
output increases or decreases with either the Manual Ozone Output Control or from a Remote 4-20mA signal.
FAULT
When illuminated, this “Red” LED indicates that there is a fault with the drive module or the Ozone Reaction
Chamber. If this LED is illuminated, refer to the Troubleshooting Guide. Notes: Upon startup, the fault LED will
remain illuminated for 30 seconds before ozone is produced. If the drive module goes to a fault condition,
the drive board will restart every 30 seconds. If the fault is not remedied the drive module will continue to
go into a fault mode. When the drive module is in fault mode ozone will not be generated.
SC27P Drive Board
Figure 7-1C
Vacuum Break
Check the water level in the vacuum break, making sure it is above the flapper valve (see Figure 6-2). If water is not
pressing downward on the flapper valve it will open, causing a loss of vacuum. A loss of vacuum means ozone cannot
flow from the vacuum break, which in turn can cause an ozone leak. Note: If the vacuum break must be refilled with
water disconnect the External Loop from the SC27P and shut down the system and follow the steps outline in
Chapter 6 “Installation Procedures –Pneumatic.” Then re-start the system by following the steps outlined in
Chapter 7 “Start-up and Calibration Procedures.”
Pneumatic Operating Parameters Figure 7-2
SC27P Operating Range Optimum
Air prep System air flow *
Ozone generator air flow (gauge –front control panel)
PSI gauge (gauge –front control panel)
Injector manifold air flow
Injector manifold injector
8 to 10 scfh
4 to 6 cfh
9 to 12 psi
8 to 12 scfh
-3 to -8 in. Hg.
10 scfh
6 cfh
10 psi
10 scfh
-5 in. Hg.
* Be sure that the SCFH flow rate is regulated to no more than 10 SCFH with the air flow gauge
adjustment valve.
Drive Board
Fuse
Variable Input Connector
DC Power Input Connector
Fault LED
Drive Board Main Power LED
Transformer –XFMR LED
Ozone Output LED
24VDC Output Connector

16
MAINTENANCE CHAPTER 8
Maintenance of the ozone system is critical to its longevity and operating efficiency. While all system
components are built to provide years of reliable service with minimum maintenance, following the
procedures outlined below is strongly recommended.
All maintenance procedures have been segmented by interval: daily, monthly, semi-annual and annual.
Daily procedures involve quick, visual checks for changes in normal operating conditions. Monthly,
semi-annual and annual procedures include cleaning and/or replacement of certain critical parts.
NOTES:
• The ozone generator warranty states that it “does
not extend to any product or part which has been
damaged or rendered defective as a result of use of
parts not sold by ClearWater Tech, or service or
unit modification not authorized by ClearWater
Tech” Please contact your ClearWater Tech dealer
if you have any questions about any maintenance
procedure before you begin that procedure.
• CAUTION: Observe all common safety practices
and review the “Safety Warnings and Instructions”
in Chapter 2 before attempting any maintenance
procedure that requires the use of tools and/or
shutting down the ozone system.
Daily Procedures
Ozone Generator
• Indicator Lights: Check all indicating LED’s on the control panel of the SC27P. See Appendix-Section A for
location and See Figure 7-1A for Control Panel LED function. See Troubleshooting Guide as required.
• Air Flow: Check the air flow meter on the SC27P control panel. Make sure air flow is within the CFH (cubic feet
per hour) range shown on the “Ozone generator air flow” line of the “Pneumatic Operating Parameters” (see
Figure 7-2). Adjust if necessary by following steps outlined in the “Start-Up & Calibration” section.
• Pressure: Check the PSI gauge located on the ozone generator cabinet door. Make sure pressure is within the
range shown on the “PSI Gauge” line of the “Pneumatic Operating Parameters” chart (see Figure 7-2). Adjust if
necessary by following steps outlined in the “Start-Up & Calibration” section.
Vacuum Break
• Water Level: Check the water level in the vacuum break. Make sure it is above the flapper valve in the overflow
tube. If the vacuum break must be refilled with water disconnect the External Loop from the SC27P and shut
down the system and follow the steps outline in Chapter 6 “ Installation Procedures –Pneumatic.” Then re-start
the system by following the steps outlined in Chapter 7 “Start-up and Calibration Procedures.”
Injection Manifold
• Check Valve: Inspect the Teflonozone delivery line that runs between the vacuum break and the check valve
assembly on the suction port of the ozone injector manifold. If water is observed in the delivery line near the
check valve assembly, the check valve has failed. See Troubleshooting Guide.
Monthly Procedures
Ozone Generator
• Cooling Fan Operation: Check to make sure the two cooling fans (mounted on the bottom panel of the SC27P.)
and the two exhaust fans (located behind the air preparation compressor) are operating. If not, refer to the
Troubleshooting Guide.
• Cooling Fan Filters: Check the cooling fan filter elements (mounted on the bottom of the SC27P) and clean as
required. Operating conditions in the equipment area will dictate the frequency required for this procedure.
Remove the filter element and clean with soap and water, drying them completely before re-installing (see Figure
8-1). Note: Fan filter stainless steel cover must be removed to access fan filters.
Booster Pump(s)
• Strainer Baskets: Check and clean the strainer basket in the booster pump(s) as required (if so equipped).

Maintenance (continued)
17
Ozone Generator Cooling Fan Assembly
Figure 8-1
System Shutdown Procedures
CAUTION: The ozone generator operates at high voltage. Follow these steps carefully before performing any
semi-annual or annual maintenance procedures.
Step 1: Turn off power to any peripheral system hydraulic components.
Step 2: Turn the Main Power switch on the SC27P to the “OFF” position. The Main Power LED’s on the control panel
should not be illuminated.
Step 3: Disconnect the power to the ozone system either at the service disconnect box (if so equipped) or main circuit
breaker.
Semi-Annual Procedures
CAUTION: Follow system shutdown procedures (outlined above) before performing any of the following steps.
Air Preparation System
• Air Inlet Filter: Replace the air compressor inlet filter. See Appendix-Section A for location. Note:
Manufacturers' recommended replacement interval is 4,000 hours of operation. Operating conditions in
the equipment area will dictate the required frequency of this procedure.
Annual Procedures
CAUTION:Follow system shutdown procedures before performing any of the following steps.
Air Preparation System
• Compressor: Following the procedures outlined in the compressor rebuild kit, rebuild the two compressor heads.
See Appendix-Section A for location. Note: Manufacturers' recommended interval is 5,000 to 12,000 hours of
operation. Compressor performance and/or operating conditions in the equipment area will dictate the
required frequency of this procedure.
Ozone Generator
• Cooling Fan Filters: Clean or replace the cooling fan filter elements as required. Note: Fan filter stainless steel
cover must be removed to access fan filters.
• Depressurization Valve: Rebuild the depressurization valve, see Appendix-Section A for location.
• Check Valve: Replace check valve located behind the system control panel, see Appendix-Section A for location.
• Reaction Chambers: Remove and disassemble one reaction chamber according to the steps outlined below (see
Figure 8-2). Check the chamber interior and dielectric tube for oil, dirt or moisture. Note: CWT pressurized
reaction chambers are anodized blue.
Removal and Disassembly
Note: Disassembly and service of the reaction chamber is a technical, delicate and critical procedure. Please
consult your ClearWater Tech dealer before attempting this procedure.
Step 1: Make sure all power to the ozone generator has been disconnected according to the “System Shutdown
Procedures” outlined above.
Step 2: Unplug the electrical connections from the drive module.
Step 3: Disconnect tubing connections from the fittings on both ends of the reaction chamber.
Step 4: Remove reaction chamber from ozone generator.
Step 5: Disconnect the high voltage lead from the drive module.
Step 6: Remove retaining screws from the two end caps (4 each).
Step 7: Using a gentle back-and-forth twisting motion, remove the non-high voltage end cap (the one without the white
power lead attached) from the heat sink/cathode assembly. Note: The stainless steel clamp must not be
removed.
Step 8: Remove the high voltage end cap and dielectric from the heat sink/cathode assembly. Note: The stainless steel
clamp must not be removed.
Step 9: With contact brush attached, remove the brush adapter nut from the high voltage end cap.
Fan
Finger Guard
Ozone Generator Bottom Panel
Fan Filter Element
Fan Filter Grill

18
High Voltage End Cap
Brush Adapter Nut
High Voltage
Lead
Stainless Steel
Washer
Viton Washer
Oxygen Inlet Fitting
Contact Brush
High Voltage Anode
Glass Dielectric
Heat Sink and Cathode
Stainless Steel Clamp
Bottom End Cap
Ozone Outlet Fitting
End Cap Retaining
Screw and Washer
Step 10: Inspect the dielectric, end caps and cathode for breakage, corrosion or debris. Clean and/or replace parts as
necessary. If cleaning and/or parts replacement is not required, re-assemble the reaction chamber per the
instructions below.
Assembly and Re-installation
Step 1: Make sure the glass dielectric is clean (free of dust, dirt, grease, oils, etc.).
Step 2: Prepare the end caps for re-assembly by replacing the O-rings. Thread the hex brush adapter nut, with contact
brush attached, onto the end of the high voltage end cap (cap with the white power lead attached) center screw.
Step 3: Using a gentle twisting motion, press the non-high voltage end cap onto the heat sink/cathode assembly until
flush with the heat sink cooling fins. Note: See Figure 8-2 for correct orientation of end cap.
Step 4: Slide the four end cap retaining screws through the holes in the non-high voltage end cap, aligning them with
the heat sink screw bosses. Thread screws into screw bosses until heads are snug against the end cap.
Step 5: Roll the high voltage anode (foil-like material) lengthwise, preserving the longer dimension. Insert the rolled
anode into the dielectric. Center the anode in the dielectric (approximately 1/2” from either end of the glass),
making sure it is rolled squarely.
Step 6: Slide the dielectric into the heat sink/cathode assembly. Seat the dielectric into the O-rings of the non-high
voltage end cap by applying pressure with a gentle twisting motion. (There must not be any dirt, debris, oils or
fingerprints on the dielectric upon re-installation).
Step 7: Slowly insert the high voltage end cap assembly into the dielectric. Note: Do not bend center wire of the
brush during this procedure. It is normal for the bristles to bend. Using a gentle twisting motion, press the
high voltage end cap onto the heat sink/cathode assembly until flush with the heat sink cooling fins.
Step 8: Slide the four end cap retaining screws through the holes in the end cap, aligning them with the heat sink screw
bosses. Thread screws into screw bosses until heads are snug against the end cap.
Step 9:Re-install complete reaction chamber assembly into the ozone generator by following the “Removal and
Disassembly” instructions in reverse order, from Step 6 to Step 2. Follow steps outlined in Chapter 7, “Start-
Up and Calibration,” to re-start the ozone system.
2” Pressurized Reaction Chamber - Exploded View
Figure 8-2

19
Vacuum Break
• Cleaning: Disconnect ozone delivery lines. Remove the vacuum break from mounting clamps. Disconnect the
overflow tube from flapper valve, open flapper and clean the seat with a soft clothe. Remove riser tube threaded
fitting and flush riser tube with water. Re-assemble and re-install vacuum break, making sure to add water to
correct level (see Figure 6-2).
Injector Manifold
• Check Valve: Replace the check valve located at the ozone injection manifold. Note: Because the system is in
the shutdown mode, no vacuum is present at the injector. Therefore, it is normal for some water to be
flowing from the injector during this procedure.
Contact Vessel
• Cleaning: Contact Column only. Inspect the diffuser slots at the top of the contact column riser tube. If they are
clear, no further maintenance is required. If the slots are fouled, disassemble the column and clean as required,
following the steps outlined below (see Figure 4-4).
Step 1: Make sure the isolation valves before and after the contact column are closed.
Step 2: Disconnect the vent line from the top of the contact column.
Step 3: Remove the bolts in the 6” base flange.
Step 4: Remove the column, lifting it over the interior riser tube.
Step 5: Remove and clean the diffuser.
Step 6: Inspect the flange gasket and replace if necessary.
Step 7: Reassemble the contact column and attach vent lines.
Table of contents
Other Clear Water Portable Generator manuals
Popular Portable Generator manuals by other brands

HP
HP 70340A quick start guide

Fluke
Fluke 291 user manual

Aquacal
Aquacal Pool Pilot Cubby Digital owner's manual

Champion Power Equipment
Champion Power Equipment 41351 Owner's Manual and Operating Instructions

Generac Power Systems
Generac Power Systems 0595-0 owner's manual

Bluetti
Bluetti AC200MAX user manual