manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Clemco
  6. •
  7. Security System
  8. •
  9. Clemco CMS-4 User manual

Clemco CMS-4 User manual

Other manuals for CMS-4

1

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

ADEMCO VISTA-20P Series Installation and setup guide

ADEMCO

ADEMCO VISTA-20P Series Installation and setup guide

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

QUICK-REFERENCE GUIDE
TURNING ON THE CMS-4 MONITOR-ALARM
1. Press and hold the POWER/MODE button until the monitor
beeps once.
THE WARM-UP SEQUENCE AUTOMATICALLY RUNS
a. All sections of the monitor’s screen turn on, the backlight turns on,
and the monitor beeps and vibrates.
b. The monitor cycles through calibration status, date/time, battery
voltage, target gas, and alarm setpoint screens.
c. After the warm-up sequence is complete, the monitor beeps 2 times
and the screen displays CO at the top left, the battery icon at the top
right, and a ppm reading at the lower right. The monitor now is in
Measuring Mode.
NOTE: If the monitor indicates a low battery (only the last bar in the
battery icon shows) or if it sounds the dead-battery alarm, replace the
battery. Refer to the operations manual for instructions.
TURNING OFF THE CMS-4 MONITOR-ALARM
1. Press and hold the POWER/MODE button. The monitor turns off after
4 beeps.
2. Release the POWER/MODE button after the monitor’s screen goes blank.
SETTING THE DATE AND TIME
1. Turn OFF the monitor. (See TURNING OFF THE CMS-4 MONITOR-ALARM
above.)
2. Press and hold the AIR and POWER/MODE buttons. Release the buttons
after the monitor beeps 1 time. The monitor beeps again and BUMP
displays in the bottom left of the screen.
3. Press the AIR button 11 times (11 beeps), and DATE displays in the
bottom left of the screen.
4. Press and release the POWER/MODE button once (1 beep).
5. Press the AIR button as often as necessary to adjust the year. Press the
POWER/MODE button to save the year. The month now flashes.
6. Repeat these steps with the AIR and POWER/MODE buttons to adjust
the month, day, hour, and minute settings.
7. After adjusting or confirming all date/time settings, END displays in the
bottom left of the screen for a few seconds, and then DATE displays.
8. Press the AIR button 3 times (3 beeps), and START displays in the
bottom left of the screen.
9. Press and release the POWER/MODE button (1 beep) to begin the
warm-up sequence. After the warm-up sequence ends, the monitor
beeps 2 times. The monitor now is in Measuring Mode.
PERFORMING A FRESH-AIR ADJUSTMENT
1. Be sure the monitor is in a fresh-air environment (free of toxic gases
and with normal oxygen content: 20.9%).
2. Turn ON the monitor by pressing and holding the POWER/MODE button
until the monitor beeps once.
3. The warm-up sequence automatically runs for about 15 seconds.
4. After the warm-up sequence is complete, the monitor beeps twice and
the screen displays CO at the top left, the battery icon at the top right,
and a ppm reading at the lower right. The monitor now is in Measuring
Mode.
5. Press and hold the AIR button. Air displays at the top of the screen and
HOLD displays at the bottom, and then this changes to AdJ displaying at
the top and RELEASE at the bottom. Release the AIR button.
6. The monitor beeps once, and the display reads as 0 ppm near the
lower-right of the screen.
ASSEMBLING THE CALIBRATION CONNECTOR
ASSEMBLY (See FIGURES 1 and 2.)
1. Required Material:
a. 0.5 LPM fixed-flow calibration connector with slide valve
b. 3/16” OD calibration tubing
c. Calibration cup
2. Slide one end of the 3/16” tubing onto the barbed end of the calibration
connector with slide valve.
3. Slide the other end of the 3/16” tubing onto the inlet barb of the
calibration cup.
NOTE: The calibration cup has directional flow. The flow-direction arrow
shows the direction of air flow. The tubing connects to the barb on the
backend of the flow arrow. The outlet barb (on the front end of the flow
arrow) remains open.
CALIBRATING THE CMS-4 MONITOR-ALARM
1. Required Material:
a. 25 ppm CO test-gas cylinder.
b. Calibration connector assembly. (See ASSEMBLING THE CALIBRATION
CONNECTOR ASSEMBLY.)
2. Perform a fresh-air adjustment. (See PERFORMING A FRESH-AIR
ADJUSTMENT.)
3. Confirm that the calibration connector’s slide valve is CLOSED
by sliding it DOWN, toward the test-gas cylinder connection.
(See FIGURE 1.)
4. Screw the calibration connector onto the test gas cylinder.
5. Turn OFF the monitor by pressing and holding the POWER/MODE button.
The monitor turns off after 4 beeps. Release the POWER/MODE button
after the monitor’s screen goes blank.
6. Press and hold the AIR and POWER/MODE buttons. Release the buttons
after the monitor beeps 1 time. The monitor beeps again and BUMP
displays in the bottom left of the screen.
7. Press the AIR button once (1 beep), and GAS CAL displays at the bottom
of the screen.
CMS-4 Carbon Monoxide Monitor-Alarm
Quick-Reference Guide for Common Functions
NOTE: This quick-reference guide is a supplement to the operations manual, which should be read in full.
8. Press the POWER/MODE button once (1 beep), and AIR displays in the
bottom left of the screen.
9. Press the AIR button once (1 beep), and A-CAL displays in the bottom
left of the screen. (NOTE: If E-CAL displays instead of A-CAL, the
monitor is in the incorrect mode. See the operations manual.)
10. Press the POWER/MODE button once (1 beep), and the calibration
value (25) displays on the right side of the screen.
11. Press the POWER/MODE button once (1 beep), and the gas reading
starts to flash.
12. Snap the calibration cup to the front of the monitor over the sensor
retainer. (The sensor retainer is located to the right of the screen.) The
arrow embedded in the calibration cup must point up and to the left.
(See FIGURE 2.)
13. Open the connector’s slide valve by sliding it UP, to the OPEN position.
(See FIGURE 1.)
14. Allow gas to flow for 1 minute and then press the POWER/MODE button
(1 beep). The monitor begins to calibrate.
15. If the calibration fails, FAIL displays at the bottom of the screen.
Refer to the operations manual.
16. If the calibration was successful, PASS briefly displays at the top
of the screen.
17. Close the connector slide valve by sliding it DOWN, remove the
calibration cup from the monitor, and unscrew the calibration
connector from the test gas cylinder.
18. Press the Air button once (1 beep), and ESCAPE displays at the bottom
of the screen.
19. Press the POWER/MODE button once (1 beep), and GAS CAL displays
at the bottom of the screen.
20. Press the Air button 13 times (13 beeps), and START displays at the
bottom of the screen.
21. Press the POWER/MODE button once (1 beep) to start the warm-up
sequence and to return to Measuring Mode.
PERFORMING A BUMP TEST
1. Required Material:
a. 25 ppm CO test-gas cylinder.
b. Calibration connector assembly. (See ASSEMBLING THE
CALIBRATION CONNECTOR ASSEMBLY.)
2. Confirm that the calibration connector’s slide valve is CLOSED
by sliding it DOWN, toward the test-gas cylinder connection.
(See FIGURE 1.)
3. Screw the calibration connector onto the test gas cylinder.
4. Turn OFF the monitor by pressing and holding the POWER/MODE
button. The monitor turns off after 4 beeps. Release the POWER/MODE
button after the monitor’s screen goes blank.
5. Press and hold the AIR and POWER/MODE buttons. Release the buttons
after the monitor beeps 1 time. The monitor beeps again, and BUMP
displays in the bottom left of the screen.
6. Press the POWER/MODE button once (1 beep), and the calibration value
(25) displays near the lower-right corner of the screen.
7. Snap the calibration cup to the front of the monitor over the sensor
retainer. (The sensor retainer is located to the right of the screen.) The
arrow embedded in the calibration cup must point up and to the left.
(See FIGURE 2.)
8. Open the connector’s slide valve by sliding it UP, to the OPEN position.
(See FIGURE 1.)
9. Press the POWER/MODE button once (1 beep). The gas reading flashes,
and the monitor counts down from 30 seconds in the lower-right corner.
10. After the countdown reaches zero, the bump test is complete.
11. If the bump test fails, a calibration is immediately and automatically
started. Continue to apply the calibration gas. AUTO CAL will appear at
the bottom of the screen, and a countdown will appear in the bottom
right. Refer to the operations manual for more information about a failed
test.
12. If the bump test passes, P (passed) displays on the left of the screen.
Proceed to Step 13.
13. Close the connector slide valve, remove the calibration cup from the
monitor, and unscrew the calibration connector from the test gas cylinder.
14. Press the POWER/MODE button once (1 beep), and END displays in the
bottom left of the screen. The monitor will then beep, and BUMP now
displays in the bottom left of the screen.
15. Press the AIR button 14 times (14 beeps), and START displays in the
bottom left of the screen.
16. Press the POWER/MODE button once (1 beep) to start the warm-up
sequence and to return to Measuring Mode.
OPEN
O
LE
S
C
!"#$!%
Flow arrow points away
from calibration tubing
Calibration Cup
CMS-4 Monitor
Open End of Calibration Cup
Upper Retaining
Clip
Lower Retaining Clip
Figure 1
Figure 2
3/16” ID Tubing
3/16” ID Tubing
Slide Valve
OPEN
CLOSE
Calibration Connector with
Fixed-Flow Slide Valve
Test Gast Cylinder