10 IK-E315-001E 
as batteries are not connected and the detectors do not function. 
Note: Since wireless radio detectors constitute a line branch, AUTOMATIC CONFIGURATION is 
possible only when the adapter in installed in a loop-shaped detection line. If it is installed in a 
radial line, only manual configuration can be carried out. 
3. In the control panel menu (at the 3rd access  level),  it  is  necessary  to  choose  the  ‘SYSTEM 
CONFIGURATION -> LINE SETUP -> MANUAL CONFIGURATION’ menu and to settle the ACR-4001 
adapter’s  ‘2’  operation  mode  (alternatively  ‘4’,  ‘6’,  ‘8’  or  ’10’  – service modes). A collective 
‘TESTING’  indicator  is  lit  in  the  control  panel  and,  after  pressing  the  button  located  near  the 
indicator, an ‘ACR-4001 IN SERVICE MODE’ communique is displayed. 
4. One of the declared detectors should be furnished with batteries. As soon as the detector enters 
the adapter operation range, the indicating diode emits red modulated flashes. In case the 
detector is unable to establish communication with the adapter, the diode emits modulated 
yellow flashes. The number of red flashes indicates the signal level (from 1 to 3). 
5. It is necessary to test, whether proper radio communication with the adapter is established in the 
place where the detector is to be installed –regular 3 diode red flashes and no yellow flashes. 
Additionally, it  is  possible to  check  in  the  control  panel  ‘SYSTEM  ELEMENTS  TESTING  -> TESTS 
SETUP -> COMMUNICATION  WITH  RADIO  DETECTOR  TEST’  menu,  the number of successful 
attempts out of latest 31 ones. Optimally  the  ‘COMMUNICATION  QUALITY’  parameter  value 
should amount to 31; it cannot be lower than 20. Three minutes should be provided for reaching 
the proper value and its stabilization. Additionally, the ‘TRANSMISSION HISTORY’ enables latest 
transmissions history analysis. In order to provide 30-dB radio band damping, the graph columns 
should be of maximum height. 
Note:  The  ‘TRANSMISSION  TIME’  parameter  should  not  exceed  10  sec.;  if  the  parameter 
amounts to more than 60 sec. for the whole 3-minute test period, it is necessary to ascertain 
that the adapter operates in the ‘2’ (or ‘4’, ‘6’, ‘8’,’10’) mode. 
6. Subsequently, the detector should be placed in a consecutive base and its transmission 
correctness should be checked as in p. 5. 
7. When all the places where detectors are to be installed are checked, the detectors should be 
furnished with batteries and mounted in the bases which were determined beforehand. It is 
important to prove at the control panel that every communication fault with the installed 
detectors has been eliminated. 
8. After confirmation that the whole circuit operates properly, the control panel should be set up in 
the ‘SYSTEM CONFIGURATION -> LINE SETUP -> MANUAL CONFIGURATION’ menu at the ‘1’ mode 
(or ‘3’, ‘5’, ‘7’, ‘9’ – normal operation mode) of the ACR-4001 adapter. The collective ‘TESTING’ 
indicator should go out; if it does not happen, it is necessary to check whether, after pressing the 
button located near the diode, the communique ‘ACR-4001 IN SERVICE MODE’ is still displayed, or 
another test is being executed. 
 
Note: In case a detector is located in a place where radio communication is hindered (i.e. the 
detector does not receive a confirmation of every information sent –it receives for instance one 
confirmation per 20 transmission attempts), it can result in faster batteries discharge and the 
detector shortened operational period. Low transmission quality is indicated at the control 
panel by the ‘LOW RADIO LINK QUALITY' technical alarm. 
 
STORAGE AND TRANSPORTATION 
8.1 Storage 
The DUR-4047 detectors should be kept in closed premises free of caustic gases and vapours at the 
temperature between +0 °C and +40 °C, and relative humidity not exceeding 80 % at +35 °C.