Set the Wall Connector as Slave by placing the rotary switch in F position.
CrimpthesuppliedRJ104P4CconnectoronMaxemsideonthedatacable.Twowires
mustbeconnected:
• Connect wire 1 (orange-white) to Pin 1
• Connect wire 2 (orange) to Pin 2
Connect the RJ10 4P4C connector to RS2 Maxem port.
ConnectthedatacabletotheIN(D+andD-)portoftheWallConnector
clamp block:
• Connectthewirefrompin1onD+
• Connect the wire from pin 2 to D-
RS2 port for
Tesla Wall Connector
LED indications Tesla Wall Connector
RS2 Pin 1 Pin 2
LEDabovelightsupingreen:everythingisconnectedproperly
MiddleLEDisblinkingred:setasSlavebutnoconnectionwithMaxem
Lower LED burns 5 secs. green: correctly set as Slave at start
RJ10 4P4C
See installation manual Tesla Wall Connector for more information
Tab above
Option 4.3 - Connecting Tesla Wall Connector
Install a circuit breaker or earth leakage circuit breaker for each charging
station at the maximal power available. See p. 10.
Follow the installation instructions of the charging station. These
instructions can be found in the installation manual of the charging
station.
Place a suitable UTP (CAT5 or CAT6) of the Wall Connector to Maxem. (To prevent
electromagneticinterferenceattheRS485connection,itisrecommendedtouseFTP
CAT6cableatdistancemorethan25m.Max:50m).
SET
OK
1 2 3
Connect the RS485 cable to the kWh-meter as follows:
• PortC:Greencore
• PortB:Whitecore
• PortA:Browncore
Place the kW-meter on a DIN rail in the installation cabinet.
Distributionboard
Chargin station
Direction of current
Connect it in such a way that it measures the consumption of the charging station.
Connection of RS485 cable
to kWh-meter
SettheaddressingofthekWh-meterto002.Asaresult,Maxemcancongureitself.
SeeAnnex2howtosettheaddressing.
18 19
A.
B.
C.
D.
E.
F.
J.
I.
H.
G.
L.
Tesla Wall Connector does not measure kWh itself, therefore a MID
kWh-meter is needed.
Cores for pull relief
Connect the RS485 cable to RS1 port on Maxem.