5. Description of device function and setting
5.1. Device setting from the manufacturer
Value assigned to Relay1 and Relay2: none
Password for setting through keys: 0000
LCD display: on
value shown at first LCD line: temperature / CO2- by device type
value shown at second LCD line: relative humidity/dew point temp. - by device type
temperature unit: °C
computed value preset: dew point temperature
relay response for error: stay unchanged at previous condition
acoustic alarm: off
LED indication: up to 1000 ppm lights green LED, between 1000 and
1200 ppm lights yellow LED and over 1200 ppm
lights red LED
altitude: 300 m above see level at the installation site
5.2. Relay outputs
Regulator is equipped with two relay outputs. It is possible to assign any input or computed value
to each relay, to set comparing alarm limit, if the relay may close if measured value is higher (HI) or
lower (Lo) than preset limit, delay for while must be preset condition true before relay close its
contact and hysteresis for return to open status. Each relay status is indicated with LED diode and
shown on LCD with corresponding symbols „ “ or „ “.
The output relays of device are not able to switch power circuits or higher voltages. In such case
we should use suitable type of power relays with coil in accordance to chapter “Common
parameters“at page 16. For wiring see Appendix A.
5.3. Carbon dioxide concentration measurement
Principle of CO2concentration measurement is based on Non-Dispersive Infrared Technology
(NDIR). It is maintenance free because of the patented autocalibration feature, compensating for the
effects of aging and therefore a guarantee for outstanding long-term stability. If the device is in
operation permanently, an auto-adjustment will start automatically after 24 hours operation each.
Measured values can be read in „SLOW mode“ (filtered, averaged) or in „FAST mode“ (current
values without averaging). SLOW mode has advantages in applications like climate control because
of filtering short time peaks. As an example exhaled air from an employee passing the sensor could
affect the climate control negatively with a short response time because the control would trigger a
change of the ventilation based on this one-time measurement. On the contrary in „FAST mode“ no
software filter is used for calculating the output value. This fact adds a noise of typ. ±30ppm which
has to be considered in terms of accuracy. Of principle measurement is the measured value of CO2
concentration depends on the value of air pressure - altitude at the installation site. For this reason, it
is suitable for accurate measurement to set the altitude of the installation site by TSensor software.
After power up there is internal check in progress and takes about 20 s. During this time LCD
display shows (----) instead of CO2concentration value.
Parameter setting description is into chapter “Extended setting mode” at page 10.