411-93026
Rev D
2. DESCRIPTION
Each patch panel contains MRJ21™receptacles (one per 1 x 4 RJ45 connector assembly, RJ45 are
distributed in blocks of 8 jacks). The ports are identified by numbers printed on the front and on the
back of the panel.
3. INSTALLATION
3.1. Using the screws, mount the patch panel onto the rack, refer to Figure 1.
3.2. Plug a connector (fromthe trunk cable) into each MRJ21™receptacle (at the back of the patch
panel). Refer to Figure 2. Make sure to align the keying features of the connector and receptacle.
Ensure that the connector is fully seated, then using a small cross-recessed tipped screwdriver,
turn the jack screws of the connector clockwise and tighten to a maximum torque of
0.34Nm [3 lbf-in]
CAUTION To avoid damage to the connector, DO NOT over-tighten the jack screws. DO NOT use an
automatic screwdriver.
3.3. Install the bracket onto the rack is suggested, contact your sales representative for available
brackets. It is recommended to maintain a minimum bend radius during installation of 8 x cable
outer diameter (eight times cable diameter) and after installation a minimum of 4x cable outer
diameter (four times cable diameter)
NOTE For installation procedure for the wiring distribution bracket, referto Figure 2, back cable
manager instruction and references per your sales representative.
Figure 2
(1) WARNING National and local earthing (grounding) bonding and EMC regulations and procedures
shall be followed.
Connector Plugged
into MRJ21
receptacle (6 places)
I/O Cable Connector
Plugged into HDP-22
Connector, only when
AMPTRAC™is applied